Operator`s manual

4-Pole Generator Voltage
Load
Speed Frequency 120V (110)
240V (220)
Applied
(rpm)
(Hertz) Plants
Plants
None
1830 62 122 240
(1530)
(52)
(112)
(224)
Half
1800
60
120 240
(1500)
(50)
(110)
(220)
Full 1755 59 110 220
(1455)
(49)
(100)
(200)
The output voltage should be checked periodically to ensure proper operation of the generating plant and
the appliances
it supplies.
If an AC voltmeter or ampmeter is not installed to monitor voltage and load, check it with a portable meter
and amp-probe.
Preventive
Maintenance
(Generator)
Maintenance on the generator
is
minimal.
1.
Keep the generator clean,
dry
and well-ventilated.
2.
Make sure all connections are clean and tight and that cables carrying AC voltage are properly supported
and protected against chafing.
3.
The rear armature bearing is lubricated and sealed; therefore, no maintenance is required.
If
the bearing
becomes rough or noisy, replace it.
Generator
Troubleshooting
A complete and illustrated text on troubleshooting the BC series of generators
is
furnished in booklet form
and incorporated in the Technical Manual which
is
available through your local dealer.
Westerbeke Generators
58