Operator`s manual

LED'S
Red
Green
Yellow
HZ.
AMP.
VOLT
VOLTAGE REGULATOR #038468
Single &
Three
Phase
DOD
5
4
3
2
0
B
+
]60HZ.
The voltage regulator
is
of
an
advanced design which ensures optimum AC alternator performance. The
regulator is equipped with complete protection circuitry to guard against operating conditions that could
be detrimental to the AC alternator.
Adjustments:
I. Volts - This potentiometer
is
used to adjust AC output voltage.
It
has an additional range
of
± 25-30
volts. At proper engine operating speed the output voltage should be held at
± 1 % from a no-load
condition to full rated generator output and from power factor
1.0 - 0.8 with engine drive speed variation
of
up to -6%.
2.
Stability - This potentiometer permits variation
of
the regulators response to generator load changes
so
as to limit over-compensation and obtain a minimum recovery time to the normal voltage output.
WESTERBEKE
GENERATORS
68