1. Highlighted on the strapping chart is the maximum safe fill level @
95% of the nominal volume. DO NOT FILL ABOVE THIS LEVEL
2. The dip chart volume is taken from the lowest point in the tank.
3. When programming a level monitoring system, the difference in floor
height at the port location (where the instrument is mounted) should
be subtracted from the fill height for each volume increment line to
equate to corresponding fill height at the instrument location.
Depth (mm) Depth (in)
Fuel Level
(Litre)
Fuel Level (US
Gallon)
Fuel Level (Imp
Gallon)
55
2.2
252
66.6
55.4
110
4.3
504
133.1
110.9
165
6.5
756
199.8
166.4
220
8.7
1008
266.4
221.8
275
10.8
1261
333.0
277.3
330
13.0
1513
399.6
332.7
385
15.2
1765
466.2
388.2
440
17.3
2017
532.8
443.6
495
19.5
2269
599.4
499.1
550
21.7
2521
666.0
554.5
605
23.8
2770
731.7
609.3
660
26.0
3014
796.3
663.1
715
28.1
3254
859.6
715.8
770
30.3
3489
921.8
767.5
825
32.5
3720
982.7
818.3
880
34.6
3946
1042.4
868.0
935
36.8
4168
1100.9
916.7
976
38.4
4330
1143.9
952.5
990
39.0
4384
1158.2
964.4
1045
41.1
4558
1204.2