WTI Part No. 14069 Rev.
Warnings and Cautions: Installation Instructions Secure Racking If Secure Racked units are installed in a closed or multi-unit rack assembly, they may require further evaluation by Certification Agencies. The following items must be considered. 1. The ambient within the rack may be greater than room ambient. Installation should be such that the amount of air flow required for safe operation is not compromised. The maximum temperature for the equipment in this environment is 45°C.
Warnings and Cautions Two Power Supply Cables Note that the AFS-16 features two separate power inputs, and a separate power supply cable for each power input. Make certain to disconnect both power supply cables from their power source before attempting to service or remove the unit. Disconnect Power If any of the following events are noted, immediately disconnect the unit from the outlet and contact qualified service personnel: 1. If the power cord becomes frayed or damaged. 2.
Table of Contents 1. Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 2. Unit Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.1. The Dual Power Supply Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.2. The Control Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents 5. Basic Configuration (continued) 5.7. The Circuit Group Directory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21 5.7.1. Viewing Circuit Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21 5.7.2. Adding Circuit Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22 5.7.3. Modifying Circuit Groups . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents 8. The Status Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1 8.1. Product Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1 8.2. The Network Status Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1 8.3. The Circuit Status Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents 16. Upgrading AFS-16 Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-1 17. Command Reference Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-1 17.1. Command Conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-1 17.2. Command Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents List of Figures 2.1. 2.2. 2.3. 4.1. 4.2. 4.3. 7.1. 7.2. 7.3. 9.1. 11.1. 14.1. A.1. The Power Supply Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 The Control Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 The Circuit Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Introduction The AFS-16-1 is a versatile switching system, designed for applications that require routing of analog or digital signals between a common RJ45 jack and “A” and “B RJ45 jacks. The AFS-16-1 is ideal for switching RS232, RS422/485, Ethernet/UTP or telephone lines. The system consists of a Card Rack, one Power Supply Module, one Control Module, and up to 16 Circuit Modules. Each Circuit Module is capable of switching all 8 pins of the Common RJ45 jack between Jack “A” or Jack “B”.
Introduction Environmental Monitoring and Management: The AFS-16 can constantly monitor temperature levels, ping response and other factors. If the AFS-16 detects that user defined thresholds for these values have been exceeded, the unit can promptly notify you via email, text message, SNMP trap, or Syslog message. The AFS-16 also records temperature readings to a convenient log file.
2. Unit Description The AFS-16 consists of a frame unit, one Dual Power Supply Module, one Control Module, and up to sixteen Circuit Modules. 2.1. The Dual Power Supply Module The Dual Power Supply Module, shown in Figure 2 1, provides AC power used by the Control Module and Circuit Module(s). The AFS-16 will always include one Dual Power Supply Module. Note that the Power Supply Module is not designed to be removed from the AFS-16 Rack Assembly. POWER MODULE AFS-16 ON 1 I O Figure 2.
Unit Description 2.2. The Control Module The Control Module, shown in Figure 2.2, coordinates switching of the individual Circuit Modules. The Control Module includes a Master A/B Gang Switch, status LEDs, a 10/100Base-T Ethernet connector and an RJ-45 RS232 Serial Port for connection to your PC, control device or external modem. An AUX jack is provided to allow connection to a monitored line and optional external alarm. The AFS-16 always includes one Control Module.
Unit Description Reset Switch: To reinitialize the AFS-16, hold the Reset Switch in the "down" position for approximately five seconds. When the AFS-16 is reset, all users will be disconnected from the AFS-16 and the operating system will be reloaded. RS232 Connector: An RJ-45 Serial Port for connection to your PC, control device, or external modem. Please refer to Appendix A for a description of the RS232 interface.
Unit Description 2.3. The Circuit Module The AFS-16 can accept up to sixteen Circuit Modules. Each Circuit Module includes a common jack, jacks for “A” and “B” paths, and a Manual A/B switch as described in Figure 2.3. RJ45-3 1 A B 2 A 3 C 4 B 5 Figure 2.3: The Circuit Module The AFS-16 Circuit Module includes the following components: A/B Switch: Each A/B Switch can be manually switched, or activated by commands sent to the Control Module.
3. Getting Started This section describes a simplified installation procedure for the AFS-16 hardware, which will allow you to communicate with the unit in order to demonstrate basic features and check for proper operation. Note that this Quick Start procedure does not provide a detailed description of unit configuration, or discuss advanced operating features in detail. For more information, please refer to the remainder of this User’s Guide 3.1.
Getting Started 3.3. Communicating with the AFS-16 When properly installed and configured, the AFS-16 will allow command mode access via Telnet, Web Browser, SSH client, modem, or local PC. However, in order to ensure security, both Telnet and Web Browser access are disabled in the default state. To enable Telnet and/or Web Browser access, please refer to Section 5.9.2. Notes: • Default AFS-16 serial port parameters are set as follows: 9600 bps, RTS/ CTS Handshaking, 8 Data Bits, One Stop Bit, No Parity.
Getting Started 3. Review Help Menu: If you are communicating with the AFS-16 via the text interface (SSH, Telnet or Modem), type /H and press [Enter] to display the Help Menu, which lists all available AFS-16 commands. Note that the Help Menu is not available via the Web Browser Interface. 3.4. Fallback Switching A/B fallback switching can be controlled via the Text Interface or via the Web Browser Interface. 3.4.1.
Getting Started 3.4.2. Fallback Switching - Web Browser Interface In the default state, the Web Browser Interface will not be available until you have enabled Web Access as described in Section 5.9.2. After Web Access has been enabled, access the AFS-16 Web Browser Interface as described in Section 3.3 and then proceed as follows: 1. Access the Circuit Control Menu: Click on the "Circuit Control" link on the left hand side of the screen to display the Circuit Control menu.
4. Hardware Installation 4.1. Connecting the Power Supply Cable(s) Refer to the cautions listed below and at the beginning of this User's Guide, and then connect the AFS-16 to an appropriate 100 to 240 VAC power supply. CAUTIONS: • Before attempting to install this unit, please review the warnings and cautions listed at the front of the user’s guide. • This device should only be operated with the type of power source indicated on the instrument nameplate.
Hardware Installation RJ-45 DB-9F Pin No. 1 8 CTS 2 1 DCD 3 2 RXD 4 5 GND 5 Pin 8 Pin 1 Pin No. Signal Pin 1 X 6 3 TXD 7 4 DTR 8 7 RTS Female Figure 4.1: DX9F-DTE-RJ Snap Adapter Interface RJ-45 DCE Serial Port AFS-16 DB-9M DTE Console Port Straight RJ-45 Cable PC, Laptop or Other Device with DB-9M DTE Interface DX9F-DTE-RJ Snap Adapter Figure 4.2: Connecting DB-9M DTE Devices to the AFS Control Module's Serial Port 4.3.
Hardware Installation Enable Disable E D Figure 4.3: Circuit Module Jumper 4.5. Module Set Up 4.5.1. Circuit Module Set Up The A/B Switch Jumper on the Circuit Module card (Figure 4.3) enables/disables the individual Circuit Module’s A/B Switch. If you wish to disable manual A/B switching control at a specific Module, then the A/B Switch Jumper on that Module must be set in the "Disable" position. 4.5.2.
5. Basic Configuration This section describes the basic configuration procedure for AFS-16 units. For information on Alarm Functions, please refer to Section 7. 5.1. Communicating with the AFS-16 Unit In order to configure the AFS-16, you must first connect to the unit, and access command mode. Note that, the AFS-16 offers two separate configuration interfaces; the Web Browser Interface and the Text Interface.
Basic Configuration To access command mode via the Text Interface, proceed as follows: Note: When communicating with the unit for the first time, you will not be able to contact the unit via Telnet until you have accessed command mode via Local PC or SSH Client and used the Network Parameters Menu to enable Telnet as described in Section 5.3. 1. Contact the AFS-16 Unit: a) Via Local PC: Start your communications program and press [Enter]. Wait for the connect message, then proceed to Step 2.
Basic Configuration 5.1.3. Access Via PDA In addition to the Web Browser Interface and Text Interface, the AFS-16 command mode can also be accessed by PDA devices. Note however, that due to nature of most PDAs, only a limited selection of AFS-16 operating and status display functions are available to users who communicate with the unit via PDA. When the AFS-16 is operated via a PDA, only the following functions are available: • • • • • Product Status Screen (Unit Info) (Section 8.
Basic Configuration 5.2. Configuration Menus Although the Web Browser Interface and Text Interface provide two separate means for selecting parameters, both interfaces allow access to the same set of basic parameters, and parameters selected via one interface will also be applied to the other. To access the configuration menus, proceed as follows: • Text Interface: Refer to the Help Screen (/H) and then enter the appropriate command to access the desired menu.
Basic Configuration 5.3. Defining System Parameters The System Parameters menus are used to define the Site ID Message, set the system clock and calendar, set up log functions and calibrate temperature readings. To access the System Parameters menu via the Text Interface, type /F and press [Enter]. To access the System Parameters menu via the Web Browser Interface, place the cursor over the "General Parameters" link, wait for the flyout menu to appear and then click on the "System Parameters" link.
Basic Configuration • Log Configuration: In the Text Interface, this item provides access to a submenu which is used to configure the Audit Log, Alarm Log and Temperature Log as described in Section 5.3.3. In the Web Browser Interface, these parameters are directly accessed via the System Parameters menu. Audit Log: When enabled, the Audit Log will create a record of all A/B switching at the AFS-16 unit, including switching that was initiated by alarms. (Default = On without Syslog.
Basic Configuration 5.3.1. The Real Time Clock and Calendar The Real Time Clock menu is used to set the AFS-16's internal clock and calendar. The configuration menu for the Real Time Clock offers the following options: • Date: The Month, Date, Year and day of the week for the real-time clock/calendar. • Time: Sets the Hour, Minute and Second for the AFS-16’s real time clock/calendar. Key in the time using the 24-hour (military) format. • Time Zone: Sets the time zone, relative to Greenwich Mean Time.
Basic Configuration 5.3.2. The Invalid Access Lockout Feature When properly configured and enabled, the Invalid Access Lockout feature will watch all login attempts made at the Network Port and RS232 Port. If either port exceeds the selected number of invalid attempts, then that port will be automatically disabled for a user-defined length of time (Lockout Duration.
Basic Configuration In the Text Interface, the Invalid Access Lockout configuration menu is accessed via the System Parameters menu. In the Web Browser Interface, the Invalid Access Lockout configuration is accessed via the "General Parameters" link. The Invalid Access Lockout configuration menus allow you to select the following: • Lockout Enable: Enables/Disables the Invalid Access Lockout feature. (Default = On.
Basic Configuration 5.3.3.1. The Audit Log and Alarm Log The System Parameters menu allows you to select three different configuration parameters for the Audit Log and Alarm Log. Note that the Audit Log and Alarm Log function independently, and parameters selected for one log will not be applied to the other. • Off: The Log is disabled, and command activity and/or alarm events will not be logged. • On - With Syslog: The Log is enabled, and A/B switching and/or alarm events will be logged.
Basic Configuration To erase log data, access command mode via the Text Interface, using an account that permits Administrator level commands, then type /L and press [Enter] to access the Display Logs menu and then proceed as follows: • Audit Log: At the Display Logs menu, type 1 and then press [Enter]. When the Audit Log appears, type E and press [Enter] to erases the Audit Log. • Alarm Log: At the Display Logs menu, type 2 and then press [Enter].
Basic Configuration In both the Text Interface and Web Browser Interface, the Callback Security Menu offers the following options: • Callback Enable: This prompt offers five different configuration options for the Callback Security feature: (Default = On - Callback (Without Password Prompt.) Off: All Callback Security is disabled.
Basic Configuration 5.3.5. Scripting Options The Scripting Options submenu provides access to parameters that are used to set up the AFS-16 unit for running various scripts. Notes: • To access Scripting Options parameters via the Text Interface, first type /F and press [Enter] to display the System Parameters Menu, then key in the number for the Scripting Options item and press [Enter].
Basic Configuration 5.3.5.1. Automated Mode The Automated Mode allows the AFS-16 to execute A/B switching commands, without displaying menus or generating response messages. Automated Mode is designed to allow the AFS-16 to be controlled by a device which can generate commands to control power switching functions without human intervention.
Basic Configuration 5.4. User Accounts Each time you attempt to access command mode, you will be prompted to enter a username and password. The username/password entered at login determine which circuit(s) you will be allowed to control and what type of commands you will be allowed to invoke. Each username / password combination is defined within a "user account.
Basic Configuration 5.4.2. Granting Circuit Module Access Each account can be granted access to a different selection of Circuit Modules. Note also, that several accounts can be allowed access to the Circuit Module. When accounts are created, the Circuit Access parameter in the Add User or Modify User menu can be used to grant or deny access to each Circuit Module by that account.
Basic Configuration 5.5. Managing User Accounts The User Directory function is employed to create new accounts, display parameters for existing accounts, modify accounts and delete accounts. Up to 128 different user accounts can be created. The "User Directory" function is only available when you have logged into command mode using an account that permits Administrator commands.
Basic Configuration • Circuit Access: Determines which AFS-16 Circuit Modules this account will be allowed to access. (Defaults; Administrator & SuperUser = All Circuit Modules On, User and ViewOnly = All Circuit Modules Off.) Notes: • In the Text Interface, Circuit Access is configured by selecting item 4 and then selecting the desired ports from the resulting submenu.
Basic Configuration • Callback Number: Assigns a number that will be called when this account attempts to access command mode via modem, and the Callback Security Function has been enabled as described in Section 5.3.5. (Default = undefined.) Notes: • If the Callback Number is not defined, then Callbacks will not be performed for this user.
Basic Configuration 5.6. Circuit Configuration The Circuit Parameters menu allows you to select parameters for the AFS-16 Circuit Modules. This allows you to assign names to the A, C, and B connectors on each Circuit Module, and also define a default A/B setting for each A/B Switch. Note that the Circuit Parameters menu is only available when you have logged into command mode using an account that permits Administrator commands.
Basic Configuration 5.7. The Circuit Group Directory The Circuit Group Directory allows you to designate "groups" of circuits that are dedicated to a similar function, and will most likely be switched at the same time. Circuit Groups allow you to direct A/B switching commands to a series of circuits, without addressing each circuit individually. For example, a set selection of AFS circuits could be assigned to a circuit group named, "Servers".
Basic Configuration 5.7.2. Adding Circuit Groups The "Add Circuit Group to Directory" option allows you to create new Circuit Groups and assign circuit access rights to each group. Note that the Add Circuit Group function is only available when you have accessed command mode using a password that permits Administrator Level commands. The Add Circuit Group Menu can be used to define the following parameters for each new account: • Circuit Group Name: Assigns a name to the Circuit Group.
Basic Configuration 5.8. Serial Port Configuration The Serial Port Configuration menus allow you to select parameters for the AFS-16 Control Module's RS232 Serial Port. The Serial Port can be configured for connection to a local PC or Modem. In addition, the Serial Port Configuration menu can also be used to set communications parameters, disable Administrator level commands and also select a number of other Serial Port Parameters described in Section 5.8.2.
Basic Configuration • Sequence Disconnect: Enables/Disables and configures the Resident Disconnect command. This offers the option to disable the Sequence Disconnect, select a one character format or a three character format. (Default = One Character.) • Inactivity Timeout: Enables and selects the Timeout Period for this port. If enabled, the Serial Port will disconnect when no additional data activity is detected for the duration of the timeout period. (Default = 5 Minutes.
Basic Configuration 5.9. Network Configuration The Network Parameters Menus are used to select parameters and options for the Network Port and also allow you to implement various security and authentication features. Although the Web Browser Interface and Text Interface allow definition of essentially the same parameters, parameters are arranged differently in the two interfaces. In the Text Interface, most network parameters are defined via one menu.
Basic Configuration 5.9.1. Network Port Parameters In the Text Interface, these parameters are found in the main Network Configuration menu. In the Web Browser Interface, these parameters are found by placing the cursor over the "Network Configuration" link on the left hand side of the screen, and then clicking on the "Network Port Parameters" link in the resulting fly-out menu. • Administrator Mode: Permits/denies port access to accounts that allow Administrator level commands.
Basic Configuration 5.9.2. Network Parameters In the Text Interface, these parameters are accessed via the Network Configuration menu (Figure 5.9.) In the Web Browser Interface, these parameters can be found by clicking the "Network Parameters" link on the left hand side of the screen to display the Network Parameters menu. Note: The IP Address, Subnet Mask, Gateway Address and DHCP status cannot be changed via the Web Browser Interface.
Basic Configuration • HTTPS Port: Selects the TCP/IP port number that will be used for HTTPS connections. (Default = 443.) Notes: • In the Text Interface, HTTP and HTTPS parameters reside in a separate submenu. To enable and configure HTTP and HTTPS Access via the Text Interface, access the Network Configuration Menu as described in Section 5.9, then type 23, press [Enter] and use the resulting submenu (Figure 14.1) to select parameters as described in Section 14.
Basic Configuration 5.9.3. IP Security The IP Security feature allows the AFS-16 to restrict unauthorized IP addresses from establishing inbound Telnet connections to the unit. This allows you to grant Telnet access to only a specific group of IP addresses, or block a particular IP address completely. In the default state, the AFS-16 accepts incoming IP connections from all hosts. In the Text Interface, IP Security parameters are defined via item 5 in the Network Configuration menu (Figure 5.9.
Basic Configuration 5.9.3.1. Adding IP Addresses to the Allow and Deny Lists To add an IP Address to the Allow or Deny list, and begin configuring the IP Security feature, proceed as follows. Notes: • Both the Allow and Deny list can include Linux operators, wild cards, and net/mask pairs. • In some cases, it is not necessary to enter all four "digits" of the IP Address. For example, if you wish to allow access to all IP addresses that begin with "192," then you would only need to enter "192.
Basic Configuration 5.9.3.2. Linux Operators and Wild Cards In addition to merely entering a specific IP address or partial IP address in the Allow or Deny list, you may also use any standard Linux operator or wild card. In most cases, the only operator used is "EXCEPT" and the only wild card used is "ALL," but more experienced Linux users may note that other operators and wild cards may also be used. EXCEPT: This operator creates an exception in either the "allow" list or "deny" list.
Basic Configuration 2. Mostly Open: Access is granted by default, and the only clients denied access, are those explicitly listed in the Deny list, and as exceptions in the Allow list. To allow access to all clients except 192.255.255.192 and 168.112.112.05, the Allow and Deny lists would be defined as follows: • Allow List: 1. ALL EXCEPT 192.255.255.192, 168.112.112.05 • Deny List: 1. 192.255.255.192, 168.112.112.
Basic Configuration 5.9.6. SNMP Access Parameters These menus are used to select access parameters for the SNMP feature. The SNMP Access Parameters menus allow the following parameters to be defined: Note: After you have configured SNMP Access Parameters, you will then be able to manage the AFS-16's User Directory and display unit status via SNMP, as described in Section 13. • Enable: Enables/disables SNMP Polling. (Default = Off.
Basic Configuration • Authentication Protocol: Determines which authentication protocol will be used. The AFS-16 supports both MD5 and SHA1 authentication. (Default = MD5.) Notes: • The Authentication Protocol that is selected for the AFS-16 must match the protocol that your SNMP client will use when querying the AFS-16 unit. • The Authentication Protocol option is not available when the Version parameter is set to V1/V2 • SNMP Contact: (Default = undefined.) • SNMP Location: (Default = undefined.
Basic Configuration 5.9.8. LDAP Parameters The AFS-16 supports LDAP (Lightweight Directory Access Protocol,) which allows authentication via the "Active Directory" network Directory Service. When LDAP is enabled and properly configured, command access rights can be granted to new users without the need to define individual new accounts at each AFS-16 unit, and existing users can also be removed without the need to delete the account from each AFS-16 unit.
Basic Configuration • Search Bind Password: Sets the Password for the user who is allowed to search the LDAP directory. (Default = undefined.) • User Search Base DN: Sets the directory location for user searches. (Default = undefined.) • User Search Filter: Selects the attribute that lists the user name. Note that this attribute should always end with "=%S" (no quotes.) (Default = undefined.) • Group Membership Attribute: Selects the attribute that lists group membership(s). (Default = undefined.
Basic Configuration 5.9.8.2 Viewing LDAP Groups If you need to examine an existing LDAP group definition, the "View LDAP Groups" function can be used to review the group's parameters and Circuit Access settings. 5.9.8.3. Modifying LDAP Groups If you need to modify an existing LDAP Group in order to change parameters or circuit access rights, the "Modify LDAP Group" function can be used to reconfigure group parameters.
Basic Configuration 5.9.9. TACACS Parameters The TACACS Configuration Menus offer the following options: • Enable: Enables/disables the TACACS feature at the Network Port. (Default = Off.) • Primary Address: Defines the IP address or domain name (up to 64 characters) for your primary TACACS server. (Default = undefined.) • Secondary Address: Defines the IP address or domain name (up to 64 characters) for your secondary, fallback TACACS server (if present.) (Default = undefined.
Basic Configuration Circuit Access: Selects the default Circuit Access setting for new TACACS users. The Circuit Access setting determines which Circuit Module(s) each account will be allowed to control. (Defaults; Administrator and SuperUser = All Circuits On, User = All Circuits Off, ViewOnly = All Circuits Off.) Notes: • Administrator and SuperUser level accounts always have access to all circuits.
Basic Configuration 5.9.10. RADIUS Parameters The RADIUS Configuration Menus offer the following options: • Enable: Enables/disables the RADIUS feature at the Network Port. (Default = Off.) • Primary Address Defines the IP address or domain name (up to 64 characters long) for your primary RADIUS server. (Default = undefined.) • Primary Secret Word: Defines the RADIUS Secret Word for the primary RADIUS server. (Default = undefined.
Basic Configuration 5.9.10.1. Dictionary Support for RADIUS The RADIUS dictionary file can allow you to define a user and assign command access rights and port access rights from a central location. The RADIUS dictionary file, "dictionary.wti" is included on the CDROM along with this user's guide.
Basic Configuration 5.9.11. Email Messaging Parameters The Email Messaging menu is used to define parameters for email messages that the AFS-16 can send to notify you when an alarm is triggered. To define email message parameters, you must access the AFS-16 Command Mode using a password that permits access to Administrator Level commands. The Email Configuration menu offers the following options: • Enable: Enables/Disables the Email Messaging feature.
Basic Configuration 5.10. Save User Selected Parameters It is strongly recommended to save all user-defined parameters to an ASCII file as described in Section 15. This will allow quick recovery in the event of accidental deletion or reconfiguration of port parameters. When changing configuration parameters via the Text Interface, make certain that the AFS-16 has saved the newly defined parameters before exiting from command mode.
6. Ping-No-Answer Fallback Switching The Ping-No-Answer function can be used to automatically switch one or more circuit modules when an attached device fails to respond to a Ping Command. In addition, the Ping-No-Answer function can also be configured to send an email, text message, Syslog Message or SNMP Trap to notify you whenever a Ping-No-Answer Action occurs. Please refer to Section 7.3 for instructions on setting up email alarm notification for Ping-No-Answer Actions.
Ping-No-Answer Fallback Switching • Consecutive Failures: Determines how many consecutive failures of the Ping command must be detected in order to initiate Ping-No-Answer fallback switching. For example, if this value is set to "3", then after three consecutive Ping failures, the specified Circuit Module(s) will then be switched. (Default = 3.) • Toggle: Enables/Disables the Ping-No-Answer Fallback function for the specified IP address.
Ping-No-Answer Fallback Switching 6.2. Viewing Ping-No-Answer Profiles After you have defined one or more Ping-No-Answer profiles, you can review the parameters selected for each profile using the View Ping-No-Answer feature. To view the configuration of an existing Ping-No-Answer profile, you must access command mode using a password that allows Administrator level commands. 6.3.
7. Alarm Configuration The AFS-16 can generate alarms when temperature readings exceed user-defined trigger levels, when input voltage is lost and then restored to the unit, when a Ping-NoAnswer condition is detected and when the Invalid Access Lockout feature is triggered. In addition, the AFS-16 can also generate an alarm when the Monitor/Alarm Input feature detects a signal change at the Control Module AUX connector.
Alarm Configuration AUX Connector 1 0 Pin Out Pin Signal 3 Normally Closed 2 Common 1 Normally Open Back Edge of Control Card Figure 7.1: Control Module AUX Connector - Output Contacts 7.1. The Output Contacts In addition to providing notification when an alarm is generated, the Over Temperature Alarms, Ping-No-Answer Alarm, Invalid Access Lockout Alarm and Monitor Input Alarm all offer the option to switch the output contacts on the Control Module AUX Connector when an alarm is triggered.
Alarm Configuration 7.2. The Over Temperature Alarms The Over Temperature Alarms are designed to inform you when the temperature level inside your equipment rack reaches or exceeds certain user-defined levels. There are two separate Over Temperature Alarms; the Initial Threshold alarm and the Critical Threshold Alarm.
Alarm Configuration • Email Message: Enables/Disables email notification for this alarm. (Default = On.) Note: If either of the "Copy to All Triggers" options is selected, then email notification for other alarms will be switched On or Off as indicated by this parameter. Address 1, 2, and 3: These parameters are used to determine which of the three email addresses defined via the "Email Messages" menu will receive the email alarm notification messages generated by this alarm.
Alarm Configuration 7.3. The Ping-No-Answer Alarm The Ping-No-Answer Alarm is intended to provide notification when one of the IP addresses defined via the Ping-No-Answer function (as described in Section 6) fails to respond to a Ping command. When one of the user-defined IP addresses fails to answer a Ping command, the AFS-16 can provide notification via Email, Syslog Message or SNMP Trap.
Alarm Configuration • Email Message: Enables/Disables email notification for this alarm. (Default = On.) Note: If either of the "Copy to All Triggers" options is selected, then email notification for other alarms will be switched On or Off as indicated by this parameter. Address 1, 2, and 3: These parameters are used to determine which of the three email addresses defined via the "Email Messages" menu will receive the email alarm notification messages generated by this alarm.
Alarm Configuration 7.4. The Invalid Access Lockout Alarm The Invalid Access Lockout Alarm can provide notification when the AFS-16 has locked a port due to repeated, invalid attempts to access command mode. Normally, the Invalid Access Lockout feature (discussed in Section 5.3.2) will lock a port whenever the AFS-16 detects that a user-defined number of invalid passwords have been entered at the port.
Alarm Configuration • Email Message: Enables/Disables email notification for this alarm. (Default = On.) Note: If either of the "Copy to All Triggers" options is selected, then email notification for other alarms will be switched On or Off as indicated by this parameter. Address 1, 2, and 3: These parameters are used to determine which of the three email addresses defined via the "Email Messages" menu (see Section 5.9.11) will receive the email alarm notification messages generated by this alarm.
Alarm Configuration 7.5. The Power Cycle Alarm The Power Cycle Alarm can provide notification when input power to the AFS-16 unit is lost and then restored. When the power supply is lost and then restored, the AFS-16 can provide notification via Email, Syslog Message or SNMP Trap. To configure the Power Cycle Alarm, you must access the AFS-16 command mode using a password that permits Administrator Level commands.
Alarm Configuration 7.6. Monitor/Alarm Input The Monitor/Alarm Input feature allows the AFS-16 to monitor Pin 4 on the Control Module's AUX connector, and then switch circuit modules, and/or activate an audible alarm or other external device and/or send notification when the signal at Pin 4 changes. To configure the Monitor/Alarm Input feature, you must access the AFS-16 command mode using a password that permits Administrator Level commands.
Alarm Configuration • Contact Output Enable: Activates/deactivates the Output Contacts on the Control Module AUX Connector. When the Contact Output Enable parameter is set to "On", the Common line will be switched from the Normally Closed contact to the Normally Open contact. For more information on the Output Contacts, please refer to Section 7.1. (Default = On.
Alarm Configuration Low High 1 0 Figure 7.2: Control Module Jumper AUX Connector Control Card Jumper 1 Pin Out Pin Signal 5 Ground 4 Monitor Input 0 Back Edge of Control Card Figure 7.3: Control Module AUX Connector - Monitor Input and Ground 7.6.1.
Alarm Configuration 7.6.1.1. Monitor Input Signal - Trigger When Low To set up the Monitor/Alarm Input feature to trigger an alarm when the signal at AUX connector pin 4 (the Monitor Input) goes Low, configure the AFS-16 as follows: 1. Control Card Jumper Setting: Set the Jumper to the "1" position (default.) This will set the non-active, non-alarm signal state to "High" as shown in Figure 7.2. 2.
8. The Status Screens The Status Screens are used to display status information about the AFS-16 hardware and firmware, Network Port, Circuit Modules, Circuit Groups and other features. The Status Screens are available via both the Text Interface and Web Browser Interface. 8.1. Product Status The Product Status Screen lists the model number, power rating and software version for your local AFS-16 unit. To display the Product Status Screen via the Text Interface, type /J * and then press [Enter].
The Status Screens 8.3. The Circuit Status Screen The Circuit Status Screen shows the current status of the AFS-16's Circuit Modules, and also lists the unit's current temperature, Monitor/Alarm Input status, and Alarm Contact Output status. Note: • When the Circuit Status screen is viewed by an account with Administrator or SuperUser command access, all AFS-16 Circuit Modules present are listed.
The Status Screens 8.4. The Circuit Group Status Screen The Circuit Group Status screen shows the configuration details and A/B switching status for the AFS-16's user-defined Circuit Groups. Notes: • When the Circuit Group Status Screen is viewed by an account with Administrator or SuperUser command access, all AFS-16 Circuit Modules and Circuit Groups will be shown.
The Status Screens 8.5. The Event Logs 8.5.1. The Audit Log The Audit Log provides a record of most command activity at the AFS-16 unit, including A/B switching, and login and logout activity. Note that the Audit Log does not include user information regarding access to configuration menus or status screens. To view the Audit Log, access command mode using a password that permits Administrator or SuperUser level commands and then proceed as follows: • Text Interface: Type /L and press [Enter].
The Status Screens 8.5.2. The Alarm Log The Alarm Log provides a record of all alarm events that were initiated by the Over Temperature Alarms, Ping-No-Answer Alarm, Invalid Access Lockout Alarm, Power Cycle Alarm and Monitor/Alarm Input feature. To view the Alarm Log, access command mode using a password that permits Administrator or SuperUser level commands and then proceed as follows: • Text Interface: Type /L and press [Enter]. The "Display Logs" menu will be shown.
9. Operation As discussed in Section 5, the AFS-16 offers two separate command interfaces; the Web Browser Interface and the Text Interface (also known as the "Command Line Interface" or "CLI.") Both interfaces offer essentially the same command options and features, and in most cases, parameters defined via the Web Browser Interface will also apply when communicating via the Text Interface (and vice versa.) 9.1.
Operation 3. A/B Switching: From the Circuit Control Menu, click the down arrow in the "Action" column for the desired circuit(s), then select position "A" or position "B" from the dropdown menu and click on the "Confirm Circuit Actions" button. Next the AFS-16 will display a screen which lists the selected switching action(s) and asks for confirmation before proceeding. Click on the "Execute Circuit Actions" button to complete the command. 4.
Operation 3. A/B Switching - Circuit Groups: From the Circuit Group Control Menu, click the down arrow for the desired Circuit Group(s), then select "A" or "B" from the dropdown menu and click on the "Confirm Circuit Group Actions" button. Next the AFS-16 will display a screen which lists the selected switching action(s) and asks for confirmation before proceeding. Click on the "Execute Circuit Group Actions" button to execute the command(s.) 4.
Operation COMMAND MENU: Version 1.
Operation 9.2.2. A/B Switching Commands - Text Interface These commands can be used to switch AFS-16’s circuit modules, and can also be used to set circuits to the user-defined default A/B positions. Circuits may be specified by number, name or Circuit Group Name. Notes: • When the Port and Circuit Status Screen is displayed by an account that permits Administrator or SuperUser level commands, all switched circuits will be displayed.
Operation 4. The "Toggle" Command: As an alternative to the /TA and /TB commands, the /T (Toggle) command can also be used to perform A/B switching. Type /T n,p and press [Enter]. Where "n" is the number or name of the desired Circuit or Circuit Group and "p" is the desired A/B position. For example: /T 2,B [Enter] or /T SERVERS,A [Enter] 5.
Operation 9.3. Manual Operation In addition to the command driven A/B switching functions that are available via the Web Browser Interface and Text Interface, the AFS-16 Circuit Modules can also be manually switched. Circuit Modules can be individually controlled using the A/B switch on the Circuit Module front panel, or all 16 Circuit Modules can be manually switched using the Master A/B Gang Switch on the Control Module front panel.
10. Telnet & SSH Functions 10.1. SSH Encryption In addition to standard Telnet protocol, the AFS-16 also supports SSH connections, which provide secure, encrypted access via network. In order to communicate with the AFS-16 using SSH protocol, your network node must include an appropriate SSH client. Note that when the /K (Send SSH Key) command is invoked, the AFS-16 can also provide you with a public SSH key, which can be used to streamline connection to the AFS-16 when using SSH protocol.
Telnet & SSH Functions 10.2. Creating an Outbound Telnet Connection The AFS-16 includes a /TELNET command, that can be used to create an outbound Telnet connection. In order to use the /TELNET command, you must access the AFS-16's Text Interface command mode using an account that permits Telnet Access and Outbound Access, via the AFS-16 Control Module's Serial RS232 Port as described below.
Telnet & SSH Functions 10.3. Creating an Outbound SSH Connection The AFS-16's /SSH command can be used to create an outbound SSH connection. In order to use the /SSH command, you must access the AFS-16's Text Interface command mode using an account that permits SSH Access and Outbound Access, via the AFS-16 Control Module's RS232 Serial Port as described below.
11. Syslog Messages The Syslog feature can create log records of each Alarm Event. As these event records are created, they are sent to a Syslog Daemon, located at an IP address defined via the Network Parameters menu. 11.1. Configuration In order to employ this feature, you must set the real-time clock and calendar via the System Parameters Menu, and define the IP address for the Syslog Daemon via the Network Port Configuration menu. To configure the Syslog function, please proceed as follows: 1.
Syslog Messages TEST NETWORK OPTIONS: 1. 2. 3. 4. SNMP Trap Test Manager 1 SNMP Trap Test Manager 2 Syslog Test Ping Enter: # to select, to exit ... Figure 11.1: The Test Menu (Text Interface) 11.2. Testing Syslog Configuration After you have configured the AFS-16 as described in Section 11.1, the /TEST command can be used to make certain that the function is properly set up.
12. SNMP Traps SNMP is an acronym for "Simple Network Management Protocol". The SNMP Trap function allows the AFS-16 to send Alarm Notification messages to two different SNMP managers, each time one of the Alarms discussed in Section 7 is triggered. Note: • The SNMP feature cannot be configured via the SNMP Manager. • SNMP reading ability is limited to the System Group. • The SNMP feature includes the ability to be polled by an SNMP Manager.
SNMP Traps 12.2. Testing the SNMP Trap Function After you have finished setting up the SNMP Trap function, it is recommended to test the configuration to ensure that it is working correctly. To test configuration of the SNMP Trap function, proceed as follows: 1. Configure the SNMP Trap function as described in Section 12.1. 2. Access the Text Interface command mode using an account that permits Administrator or SuperUser level commands, then invoke the "/TEST" command at the AFS-16 command prompt.
13. Operation via SNMP If SNMP Access Parameters have been defined as described in Section 5.9.6, then you will be able to manage user accounts, control power and reboot switching and display unit status via SNMP. This section describes SNMP communication with the AFS-16 unit, and lists some common commands that can be employed to manage users, control switching and reboot actions and display unit status. 13.1.
Operation via SNMP • userTable::userCircuitAccess – A string of up to 16 characters, with one character for each of the 16 possible Circuit Modules on the AFS-16 unit. A ‘0’ indicates that the account does not have access to the circuit, and a ‘1’ indicates that the user does have access to the circuit. Note: The number of circuits specified in the userCircuitAccess string must not exceed the number of Circuit Modules available on your AFS-16 unit.
Operation via SNMP 13.4. Circuit Control via SNMP 13.4.1. Controlling Circuits A/B Switching and Default commands can be issued for circuits via SNMP. Circuits are arranged in a table of N rows, where N is the number of circuits in the system. Circuit parameters are described below. • circuitTable::circuitID – String indicating the circuit's ID • circuitTable::circuitName - String indicating the circuit's user-defined name.
Operation via SNMP 13.5. Viewing AFS-16 Status via SNMP Status of various components of the AFS-16 can be retrieved via SNMP. Circuit Status, and Environmental Status are currently supported. 13.6.1. Circuit Status The status of each circuit in the system can be retrieved using the command below. • circuitTable::circuitStatus – The status of the circuit.
Operation via SNMP 13.7. Sending Traps via SNMP Traps that report various unit conditions can be sent to an SNMP Management Station from the AFS-16. The following traps are currently supported.
14 Setting Up SSL Encryption This section describes the procedure for setting up a secure connection via an https web connection to the AFS-16. Note: SSL parameters cannot be defined via the Web Browser Interface. In order to set up SSL encryption, you must contact the AFS-16 via the Text Interface. There are two different types of https security certificates: "Self Signed" certificates and "Signed" certificates.
Setting Up SSL Encryption 14.1. Creating a Self Signed Certificate To create a Self Signed certificate, access the Text interface via Telnet or SSH, using a password that permits access to Administrator level commands and then proceed as follows: 1. Type /N and press [Enter] to display the Network Parameters menu. 2. At the Network Parameters menu, type 23 and press [Enter] to display the Web Access menu (Figure 14.1.
Setting Up SSL Encryption 4. 5. After you have defined parameters 5 through 11, type 12 and press [Enter] (Create CSR) to create a Certificate Signing Request. By default, this will overwrite any existing certificate, and create a new Self Signed certificate. a) The AFS-16 will prompt you to create a password. Key in the desired password (up to 16 characters) and then press [Enter]. When the AFS-16 prompts you to verify the password, key it again and then press [Enter] once.
Setting Up SSL Encryption 3. 4. Upload the Signed Certificate to the AFS-16: After the "signed" certificate is returned from the security service, return to the Web Access menu. a) Access the AFS-16 command mode via the Text Interface using an account that permits Administrator level commands as described previously, then type /N and press [Enter] to display the Network Parameters menu, and then type 23 and press [Enter] to display the Web Access menu.
15. Saving and Restoring Configuration Parameters Once the AFS-16 is properly configured, parameters can be downloaded and saved as an ASCII text file. Later, if the configuration is accidentally altered, the saved parameters can be uploaded to automatically reconfigure the unit without the need to manually assign each parameter. Saved parameters can also be uploaded to other identical AFS-16 units, allowing rapid set-up when several identical units will be configured with the same parameters.
Saving and Restoring Configuration Parameters 15.2. Restoring Saved Parameters This section describes the procedure for using your terminal emulation program to send saved parameters to the AFS-16. 1. Start your terminal emulation program and access the AFS-16’s Text Interface command mode using an account that permits Administrator level commands. 2. Configure your terminal emulation program to upload an ASCII text file. 3. Upload the ASCII text file with the saved AFS-16 parameters.
Saving and Restoring Configuration Parameters 15.3. Restoring Previously Saved Parameters If you make a mistake while configuring the AFS-16 unit, and wish to return to the previously saved parameters, the Text Interface's "Reboot System" command (/I) offers the option to reinitialize the AFS-16 using previously backed up parameters. This allows you to reset the unit to previously saved parameters, even after you have changed parameters and saved them.
16. Upgrading AFS-16 Firmware When new, improved versions of the AFS-16 firmware become available, the "Upgrade Firmware" function can be used to update the unit. Updates can be uploaded via FTP or SFTP protocols. Notes: • The FTP/SFTP servers can only be started via the Text Interface. • All other ports will remain active during the firmware upgrade procedure.
Upgrading RSM-8R4 Firmware 4. To proceed with the upgrade, select either option 1 or option 2. The AFS-16 will display a message that indicates that the unit is waiting for data. Leave the current Telnet/SSH client session connected at this time. 5. Open your FTP/SFTP application and (if you have not already done so,) login to the AFS-16 unit, using a username and password that permit access to Administrator Level commands. 6. Transfer the md5 format upgrade file to the AFS-16. 7.
17. Command Reference Guide 17.1. Command Conventions Most commands described in this section conform to the following conventions: • Text Interface: Commands discussed in this section, can only be invoked via the Text Interface. These commands cannot be invoked via the Web Browser Interface. • Slash Character: Most AFS-16 Text Interface commands begin with the Slash Character (/).
Command Reference Guide 17.2. Command Summary Function Command Syntax Command Access Level Admin.
Command Reference Guide 17.3. Command Set This Section provides information on all Text Interface commands, sorted by functionality 17.3.1. Display Commands /S Display Circuit Status Screen Displays the Circuit Status Screen, which lists the current status of the AFS-16's Circuit Modules. For more information, please refer to Section 8.3. Note: In Administrator Mode and SuperUser Mode, all AFS-16 circuits are displayed.
Command Reference Guide /L Log Functions Provides access to a menu which allows you to display the Audit Log, Alarm Log and Temperature Log. For more information on Log Functions, please refer to Section 5.3.4. Availability: Administrator, SuperUser Format: /L [Enter] /J Display Site ID / Unit Information Displays the user-defined Site I.D. message.
Command Reference Guide /TA Toggle to "A" Position Toggles a Circuit or a Circuit Group to the "A" position. Note: When this command is invoked in Administrator Mode or SuperUser Mode, it can be applied to all AFS-16 Circuits and Circuit Groups. When this command is invoked in User Mode, it can only be applied to the Circuits and/or Circuit Groups that have been enabled for your account.
Command Reference Guide /T Toggle Command This command can be used to toggle any Circuit or Circuit Group to either the "A" position or the "B: position. Note: When this command is invoked in Administrator Mode or SuperUser Mode, it can be applied to all AFS-16 Circuits and Circuit Groups. When this command is invoked in User Mode, it can only be applied to the Circuits and/or Circuit Groups that have been enabled for your account.
Command Reference Guide /K Send SSH Key Instructs the AFS-16 to provide you with a public SSH key for validation purposes. This public key can then be provided to your SSH client, in order to prevent the SSH client from warning you that the user is not recognized when you attempt to create an SSH connection. For more information, please refer to Section 10.1. Availability: Administrator Format: /K k [Enter] Where k is a required argument, which indicates the key type.
Command Reference Guide /SSH Outbound SSH Creates an outbound SSH connection as described in Section 10.3. Notes: • In order for the /SSH command to function, Telnet/SSH and Outbound Service Access must be enabled for your user account as described in Section 5.5. In addition, SSH Access and Outbound Access must also be enabled via the Network Parameters menu, as described in Section 5.9.2. • If you have logged in via the Network Port, the /SSH command will not function.
Command Reference Guide /G Circuit Group Parameters Displays a menu that is used to View, Add, Modify or Delete Circuit Groups. For more information on Circuit Groups, please refer to Section 5.7. Availability: Administrator Format: /G [Enter] /N Network Port Parameters Displays a menu which is used to select parameters for the Network Port. Also allows access to the IP Security function, which can restrict network access by unauthorized IP addresses and domain names.
Command Reference Guide /I Reboot System (Default) Reinitializes the AFS-16 unit and offers the option to keep user-defined parameters or reset to default parameters. As described in Sections 5.10.1 and 15.3, the /I command can also be used to restore the unit to previously saved parameters.
Appendix A. Interface Description RJ-45 Pin No. Control Module RS232 Serial Port Pin 1 Pin 8 RTS 1 Request to Send DTR 2 Ready Out TXD 3 Data Out GND 4 Ground 5 RXD 6 Data In DCD 7 Carrier Detect CTS 8 Clear to Send Figure A.1: Serial Port Interface A.1. Serial Port (RS232) DCD and DTR hardware lines function as follows: 1. 2. When connected: a) If either port is set for Modem Mode, the DTR output at either port reflects the DCD input at the other end.
Appendix B. Specifications Switch Card: Up to 16 Modules Interface: RJ45-3, Three Jacks, 8 Pins Switched Common Jack to A or B Jack. Contacts: High Reliability, Mechanical Relays, Break-Before-Make Contacts with 1 Amp @ 30 VDC Rating, 100 Million Cycle Life. Switching: Manual: Individual Toggle Switch, Gang Switching from Control Module. Code/Web Browser: By Slot Number or by Name.
Appendix C. Customer Service Customer Service hours are from 8:00 AM to 5:00 PM, PST, Monday through Friday. When calling, please be prepared to give the name and make of the unit, its serial number and a description of its symptoms. If the unit should need to be returned for factory repair it must be accompanied by a Return Authorization number from Customer Service.
Appendices Trademark and Copyright Information WTI and Western Telematic are trademarks of Western Telematic Inc.. All other product names mentioned in this publication are trademarks or registered trademarks of their respective companies. Information and descriptions contained herein are the property of Western Telematic Inc.. Such information and descriptions may not be copied, disseminated, or distributed without the express written consent of Western Telematic Inc.. © Copyright Western Telematic Inc.
Index A A/B Gang Switch 2-2 A/B Switch 2-4 Jumper 2-4 A/B Switching Text Interface 9-4 to 9-6 Web Browser Interface 9-1 to 9-3 Accept Break Network Port 5-26 Serial Port 5-24 Access Level 5-15, 5-17, 17-2 LDAP Group 5-36 TACACS 5-38 Accounting Port RADIUS 5-40 Accounts 5-15 to 5-23 Adding 5-17 Default 5-15 Add Circuit Group 5-22 LDAP Group 5-36 PNA Profile 6-1 User Accounts 5-17 Via SNMP 13-2 Address Invalid Access Lockout Alarm 7-8 Monitor/Alarm Input 7-10 Over Temperature Alarms 7-4 Ping No Answer Alarm 7
Index Circuit Status Screen 8-2 Text Interface 9-4, 17-3 Circuits to Switch Monitor/Alarm Input 7-11 CLI 5-1 to 5-2 Clock and Calendar 5-5, 5-7 to 5-8 Command Access Level 5-17, 17-2 Command Confirmation 5-13 Command Echo Network Port 5-26 Serial Port 5-24 Command Line Interface 5-1 to 5-2, 17-1 to 17-10 Command Mode Access 5-1 to 5-3 Logging Out 9-7, 17-4 Command Reference Guide 17-1 to 17-10 Command Set Text Interface 17-3 to 17-10 Common Name 14-2 Communication 5-1 to 5-3 Configuration 5-1 to 5-43 Circui
Index F Fallback Fallback Local RADIUS TACACS Fallback Timer RADIUS TACACS Firmware Upgrade Firmware Version From Address Email Parameters From Name Email Parameters 5-36 5-40 5-38 5-40 5-38 16-1 to 16-2, 17-10 8-1 5-42 5-42 G Gang Switch Gateway Address Network Port General Parameters Group Membership Attribute Group Membership Value Type 5-27 5-5 to 5-15 5-36 5-36 5-24 5-28 4-1 to 4-3 9-4, 17-3 5-27 5-2 5-27 5-27 5-28 I Inactivity Timeout Network Port 5-26 Serial Port 5-24 Initialization String Modem
Index Local Control Device Locality Local PC Access Lockout Attempts Lockout Duration Lockout Enable Log Configuration Log Function Reading and Erasing Syslog Text Interface Logging Out Text Interface Login Logoff Character Network Port Serial Port M Management Utility Manual Control Manual Operation Master A/B Gang Switch Menus MIB Parameters Modem Access Modem Mode Hang Up String Initialization String Periodic Reset Value Reset String Modem Phone Number Modem Port Configuration Modify Circuit Group LDAP G
Index Notify Upon Clear Invalid Access Lockout Alarm Over Temperature Alarms Ping No Answer Alarm NTP Enable NTP Timeout Primary NTP Address Secondary NTP Address NTP Enable NTP Timeout 7-7 7-3 7-5 5-7 5-7 5-7 5-7 5-7 5-7 O Operation Organizational Name Organizational Unit Outbound Access Outbound SSH Outbound Telnet Over Temperature Alarms Address Alarm Clear Threshold Alarm Set Threshold Contact Output Enable Email Message Notify Upon Clear Resend Delay Subject Trigger Enable 9-1 to 9-7 14-2 14-2 5-39
Index S Privacy SNMPv3 Product Information Product Status Screen Public Key 5-33 17-4 8-1 10-1 Q Quick Start Procedure 3-1 to 3-4 R RADIUS Accounting Port Authentication Port Debug Dictionary Support Enable Fallback Local Fallback Timer Primary Address Primary Secret Word Retries Secondary Address Secondary Secret Word Set Up Read Only SNMP Parameters Real Time Clock Date NTP Enable NTP Timeout Primary NTP Address Secondary NTP Address Test NTP Servers Time Time Zone Reboot System Resend Delay Invalid
Index SNMP Adding Users Circuit Status Configuration Configuration Via Controlling Circuit Groups Controlling Circuits Deleting Users Modifying Users Sending Traps SNMP Traps Testing Unit Environment Status Unit Operation Via Viewing Users View Unit Status SNMP Agent SNMP Parameters Access Authentication Authentication Protocol Enable Privacy Read Only Read Only Community Read/Write Community SNMP Contact SNMP Location SNMPv3 SNMPv3 Password SNMPv3 User Name Version SNMP Trap Configuration SNMP Managers Tes
Index T TACACS Access Level 5-38 Authentication Port 5-38 Configuration 5-38 Default User Access 5-38 Enable 5-38 Fallback Local 5-38 Fallback Timer 5-38 Plug Access 5-39 Plug Group Access 5-39 Primary Address 5-38 Secondary Address 5-38 Secret Word 5-38 Service Access 5-39 Tech Support Apx-3 Telnet Access 5-18 Outbound 5-28, 17-7 Telnet Command 17-7 Telnet Access 5-2, 5-27 Telnet Port 5-27 Temperature Calibration 5-5 Temperature Format 5-5 Temperature Log 8-5, 5-9, 5-10, 5-6 Test Ping Test 6-2 Test Menu 11