WTI Part No. 13762 Rev. H MPC Series Managed Power Controllers Models Covered: MPC-8H-1 MPC-8H-2 MPC-16H-1 MPC-16H-2 MPC-18H-1 MPC-18H-2 MPC-20VS20-1 MPC-20VD20-1 MPC-20VS30-1 MPC-20VD30-1 MPC-20VS20-2 MPC-20VD20-2 MPC-20VS30-2 MPC-20VD30-2 MPC-20VS16-3 MPC-20VD16-3 MPC-20VS32-3 MPC-20VD32-3 MPC-20V-1 MPC-20V-2 MPC-DISPLAY Firmware Version 1.
Warnings and Cautions: Installation Instructions Secure Racking If Secure Racked units are installed in a closed or multi-unit rack assembly, they may require further evaluation by Certification Agencies. The following items must be considered. 1. The ambient within the rack may be greater than room ambient. Installation should be such that the amount of air flow required for safe operation is not compromised. The maximum temperature for the equipment in this environment is 55°C.
Warnings and Cautions Disconnect Power If any of the following events are noted, immediately disconnect the unit from the outlet and contact qualified service personnel: 1. If the power cord becomes frayed or damaged. 2. If liquid has been spilled into the device or if the device has been exposed to rain or water. Two Power Supply Cables Note that some MPC series units feature two separate power circuits, and a separate power supply cable for each power circuit.
Agency Approvals FCC Part 15 Regulation This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Table of Contents 1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 2. Unit Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.1. MPC-H Series - Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.2. MPC-H Series - Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents 5. Basic Configuration (continued) 5.6. The Plug Group Directory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6.1. Viewing Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6.2. Adding Plug Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6.2.1. Granting User Account Access to Plugs on AUX Units . . . . . . . . . 5.6.3. Modifying Plug Groups . .
Table of Contents 7. Alarm Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 7.1. The Over Current Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2 7.1.1. Over Current Alarms - Load Shedding and Auto Recovery . . . . . . . . . . . . . . . 7-5 7.1.1.1. Load Shedding & Auto Recovery Configuration Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents 13. Operation via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1 13.1. MPC SNMP Agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1 13.2. SNMPv3 Authentication and Encryption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1 13.3. Configuration via SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents List of Figures 2.1. 2.2. 2.3. 5.1. 5.2. 5.3. 5.4. 5.5. 5.6. 5.7. 5.8. 5.9. 5.10. 5.11. 5.12. 5.13. 5.14. 5.15. 5.16. 5.17. 5.18. 9.1. 11.1. 14.1. B.1. B.2. C.1. C.2. C.3. C.4. E.1. E.2. E.3. E.4. E.5. E.6. E.7. E.8. E.9. F.1. MPC-H Series - Front Panel (Model MPC-16H Shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 MPC-H Series - Back Panel (Model MPC-16H-1 Shown) . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Introduction WTI’s MPC series Managed Power Controllers allow secure, remote metering and management of AC powered rack mount equipment via SSL, SSH, SNMP, web browser, telnet, external modem or local terminal. The MPC can monitor power to your equipment, and automatically notify you when changes in current levels, temperature, circuit breaker status or other factors exceed user-defined threshold values.
Introduction Convenient, Durable Design: The MPC is available with an optional remote display panel, which can be used to show the status of MPC units installed in hard-to-reach spots, deep inside equipment racks. When additional outlets are needed, each MPC unit can also be connected to up to three Auxiliary/Remote MPC units, allowing control of up to 80 outlets via a single IP Address .
Introduction Typographic Conventions ^ (e.g. ^X) Indicates a control character. For example, the text "^X" (Control X) indicates the [Ctrl] key and the [X] key must be pressed simultaneously. COURIER FONT Indicates characters typed on the keyboard. For example, /AC or /ON A2. [Bold Font] Text set in bold face and enclosed in square brackets indicates a specific key. For example, [Enter] or [Esc]. < > Indicates required keyboard entries. For Example: /P . [ ] Indicates optional keyboard entries.
2. Unit Description 2.1. MPC-H Series - Front Panel 1 2 3 4 5 MPC-16H www.wti.com REMOTE AUX 1 A1 A2 A3 A4 A5 A6 A7 A8 DEFAULT AUX 2 6 AUX 3 AUDIBLE ALARM ON PLUGS 8.8.8 INPUT A AMPS KWATTS VOLTS TEMP DISPLAY SELECTION 8.8.8 INPUT B B1 B2 B3 B4 B5 B6 B7 B8 PLUGS Managed Power Controller CONSOLE PORT 7 8 9 Figure 2.1: MPC-H Series - Front Panel (Model MPC-16H Shown) As shown in Figure 2.1, the MPC-H Series Front Panel includes the following components: 1.
Unit Description 5. Power Circuit B - Indicator Lights: Same as Item 1 above, except the LEDs light to indicate On/Off status of Power Circuit B outlets. (Not present on MPC-18H series units.). 6. Link Ports: Four RJ45 connectors, which can be used to link the MPC unit to up to three other MPC or BPM units, plus the optional MPC-DISPLAY, status display panel.
Unit Description 1 3 4 BUS A A-1 A-2 A-3 A-4 3 A-5 A-6 A-7 BUS A A-8 ACT LINK ALARM A B BUS B 2 B-1 B-2 B-3 B-5 B-4 6 B-6 B-7 BUS B B-8 5 6 10/100 BaseT 7 8 Figure 2.2: MPC-H Series - Back Panel (Model MPC-16H-1 Shown) 2.2. MPC-H Series - Back Panel As shown in Figure 2.2, the MPC-H Series Back Panel includes the following components: 1. Power Circuit A - Power Inlet: An IEC320-C20 AC inlet which supplies power to MPC control functions and the Circuit “A” outlets.
Unit Description 5. Power Circuit B - Switched Outlets: Same as Item 4 above. (Not present on MPC-18H series units.) 6. Power Circuit B - Circuit Breaker(s): Same as Item 3 above. (Not present on MPC-18H series units.) 7. Alarm Indicator Lights: Two LEDs which light when an alarm condition is detected at the corresponding power circuit. For information on Alarm Configuration, please refer to Section 7. Note that MPC-18H series units include only one Alarm Indicator Light. 8.
Unit Description 1 4 AUX 3 AUX 1 2 DEFAULT REMOTE DISPLAY AUDIBLE ALARM AUX 2 Ethernet 10/100 3 ACT 6 TOTAL A+B DISPLAY SELECTION 5 LINK ON KWATTS AMPS CONSOLE AMPS 7 VOLTS KWATTS TEMP 8.8.8 8.8.
Unit Description 5. Network Port: An RJ45 Ethernet port for connection to your 100Base-T, TCP/IP network. Note that the MPC features a default IP address (192.168.168.168). This allows you to connect to the unit without first assigning an IP address. Note that the Network Port also includes two, small LED indicators for Link and Data Activity. For more information on Network Port configuration, please refer to Section 5.9. 6.
Unit Description 13. Power Inlet(s): The power inlets are configured differently on MPC models, in accordance with the power rating, maximum load and the number of power circuits. Depending on your specific model, the MPC may include either one or two power inlets or either one or two power supply cables. Other MPC models may include either one or two permanently attached power supply cables.
Unit Description 4. Enable/Disable Audible Alarm: a) In the default state, the Audible Alarm is Enabled. b) To disable the Audible Alarm, press and hold the Audible Alarm button for three seconds and then release it. To enable the Audible Alarm, press and hold the Audible Alarm button for three seconds again. c) If the optional MPC-DISPLAY unit is installed, and this operation is performed at the MPC-DISPLAY unit, the audible alarm feature on all connected MPC units will also be disabled.
3. Getting Started This Quick Start Guide describes a simplified installation procedure for the MPC series hardware, which will allow you to communicate with the unit in order to demonstrate basic features and check for proper operation. Note that this Quick Start Guide does not provide a detailed description of unit configuration, or discuss advanced operating features in detail.
Getting Started Model No. Input Feeds Input Voltage Max. Load per Outlet Max. Load per Input Max.
Getting Started 3.1.2. Connect your PC to the MPC The MPC can either be controlled by a local PC, that communicates with the unit via serial port, controlled via external modem, or controlled via TCP/IP network. In order to switch plugs or select parameters, commands are issued to the MPC via either the Network Port or Console Port. Note that it is not necessary to connect to both the Network and Console Ports, and that the Console Port can be connected to either a local PC or External Modem.
Getting Started 1. Access Command Mode: The MPC includes two user interfaces; the Text Interface and the Web Browser Interface. The Text Interface is available via Local PC, SNMP, SSH Client, Telnet, or Modem, and the Web Browser interface is only available via TCP/IP network. In addition, when contacted via PDA, the MPC will also present a third interface, which is similar to the Web Browser Interface, but offers limited command functions.
Getting Started c) 3. Switch Outlet On: i. Web Browser Interface: From the Plug Control Menu, click the down arrow in the "Action" column for Plug A1 to display the drop down menu, then select "On" from the drop down menu and click on the "Execute Plug Actions" button. ii. Text Interface: Type /ON A1 and press [Enter].
4. Hardware Installation 4.1. Connecting the Power Supply Cables 4.1.1. Installing the Power Supply Cable Keepers The MPC includes cable keepers, which are designed to prevent the power supply cables from being accidentally disconnected from the unit. Note: In addition to the Power Supply Cable Keepers described in this section, a Power Outlet Cable Keeper is also available for MPC-20V series units. Please refer to Appendix F for more information.
Hardware Installation • MPC-18H-1 and MPC-18H-2: The cable keeper for these units must be installed by the user. 1. First make certain that the MPC-18H’s power supply cable is disconnected from the power source. 2. Install the two standoff screws (included with the cable keeper) in the two vacant screw holes, located next to the power inlet. When the standoff screws are in place, thread the two screws supplied with the cable keeper into the top end of both of the standoff screws. 3.
Hardware Installation 4.1.2. Connect the MPC to Your Power Supply Refer to the cautions listed below and at the beginning of this User's Guide, and then connect the MPC unit to an appropriate power supply. Note: Some MPC units are shipped with one or two detachable 125 VAC, 15 Amp "Starter" Cables. These cable(s) will allow you to connect a 120 VAC MPC unit to power for bench testing and initial start up and are adequate for applications that only require 15 Amps.
Hardware Installation 4.3. Serial Console Port Connection The MPC's Console Port is a male, RS-232C DB9 connector, wired in a DCE configuration. In the default state, the Console port is configured for 9600 bps, no parity, 8 data bits, 1 stop bit. The Console Port can be connected to either an external modem or a local PC, but not both items at the same time. Appendix B.1 describes the Console Port interface. 4.3.1.
Hardware Installation 4.5. Connecting Remote MPC Units to the AUX Ports If your application requires control of more outlets than are provided on your MPC unit, you can also connect up to three additional MPC or BPM units to the AUX ports on the MPC front panel. This allows you to control up to 80 outlets via a single IP address. To connect optional, Auxiliary MPC units to your local MPC unit, proceed as follows: 1.
Hardware Installation 4.6. Connecting the Optional MPC-DISPLAY Unit Use an RJ-45 cable to connect the optional MPC-DISPLAY unit to the MPC unit. Connect one end of the RJ-45 cable to the “Remote” connector on the MPC front panel; connect the other end of the cable to the RJ-45 receptacle on the back side of the MPC-DISPLAY unit as described in Appendix C.2. The MPC-DISPLAY unit will receive five volts of power (for operation) via the RJ-45 cable connected to the MPC unit.
5. Basic Configuration This section describes the basic configuration procedure for all MPC units. For more information on Reboot Options and Alarm Configuration, please refer to Section 6 and Section 7. 5.1. Communicating with the MPC Unit In order to configure the MPC, you must first connect to the unit, and access command mode. Note that, the MPC offers two separate configuration interfaces; the Web Browser Interface and the Text Interface.
Basic Configuration To access command mode via the Text Interface, proceed as follows: Note: When communicating with the unit for the first time, you will not be able to contact the unit via Telnet, until you have accessed command mode, via Local PC or SSH Client, and used the Network Parameters Menu to enable Telnet as described in Section 5.9. 1. Contact the MPC Unit: a) Via Local PC: Start your communications program and press [Enter]. Wait for the connect message, then proceed to Step 2.
Basic Configuration 5.1.2. The Web Browser Interface The Web Browser Interface consists of a series of web forms, which can be used to select configuration parameters and perform reboot operations, by clicking on radio buttons and/or entering text into designated fields.
Basic Configuration 5.1.3. Access Via PDA In addition to the Web Browser Interface and Text Interface, the MPC command mode can also be accessed by PDA devices. Note however, that due to nature of most PDAs, only a limited selection of MPC operating and status display functions are available to users who communicate with the unit via PDA. When the MPC is operated via a PDA device, only the following functions are available: • • • • • • • Product Status Screen (Section 8.1) Plug Status Screen (Section 8.
Basic Configuration 5.2. Configuration Menus Although the Web Browser Interface and Text Interface provide two separate means for selecting parameters, both interfaces allow access to the same set of basic parameters, and parameters selected via one interface will also be applied to the other. To access the configuration menus, proceed as follows: • Text Interface: Refer to the Help Screen (/H) and then enter the appropriate command to access the desired menu.
Basic Configuration SYSTEM PARAMETERS: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. User Directory Site-ID: (undefined) Real Time Clock: 08/13/2008 18:07:55 Invalid Access Lockout: On Command Confirmation: On Automated Mode: Off Command Prompt: MPC Temperature Format: Fahrenheit Temperature Calibration: (undefined) Voltage Calibration: (undefined) Log Configuration 21. Audit Log: On - Without Syslog 22. Alarm Log: On - Without Syslog 23. Current Metering Log: On 12.
Basic Configuration 5.3. Defining System Parameters The System Parameters menus are used to define the Site ID Message, set the system clock and calendar, and configure the Invalid Access Lockout feature and Callback feature. In the Text Interface, the System Parameters menu is also used to create and manage user accounts and passwords.
Basic Configuration • Command Confirmation: Enables/Disables the Command Confirmation feature. When enabled, a "Sure" prompt will be displayed before power switching and reboot commands are executed. When disabled, commands will be executed without further prompting. (Default = On.) • Automated Mode: When enabled, the MPC will execute switching and reboot commands without displaying a confirmation prompt, status screen or confirmation messages. For more information, please refer to Section 5.3.
Basic Configuration • Alarm Log: Enables/disables the Alarm Log, and determines whether or not the Alarm Log will send SYSLOG messages to notify you of each logged event. When enabled, the Alarm Log will create a record of all alarm activity at the MPC unit. For more information on the MPC's event logging functions, please refer to Section 5.3.4. (Default = On without Syslog.) • Current/Power Log: Enables/disables Current Metering Log and Power Metering Log.
Basic Configuration • Time Zone: Sets the time zone, relative to Greenwich Mean Time. Note that the Time Zone setting will function differently, depending upon whether or not the NTP feature is enabled and properly configured. (Default = GMT (No DST).) ◆ NTP Enabled: The Time Zone setting is used to adjust the Greenwich Mean Time value (received from the NTP server) in order to determine the precise local time for the selected time zone.
Basic Configuration 5.3.2. The Invalid Access Lockout Feature When properly configured and enabled, the Invalid Access Lockout feature will watch all login attempts made at the Network Port and serial Console Port. If the port exceeds the selected number of invalid attempts, then the port where the Invalid Attempts occurred will be automatically disabled for a user-defined length of time (Lockout Duration.
Basic Configuration To access the configuration menu for the Invalid Access Lockout feature, proceed as follows: • Text Interface: Type /F and press [Enter]. The System Parameters menu will appear as shown in Figure 5.3. At the System Parameters menu, type 4 and press [Enter] to display the Invalid Access Lockout configuration menu. • Web Browser Interface: Place the cursor over the "General Parameters" link on the left hand side of the screen.
Basic Configuration 5.3.3. Automated Mode The Automated Mode allows the MPC to execute switching and reboot commands, without displaying menus or generating response messages. Automated Mode is designed to allow the MPC to be controlled by a device which can generate commands to control power switching functions without human intervention.
Basic Configuration 5.3.4. Log Configuration This feature allows you to create records of command activity, alarm actions and current and power consumption for the local MPC unit, as well as any optional, connected AUX MPC units (if present.) The Log features are enabled and configured via the System Parameters Menus. The ability to view the Current and Power Metering logs is individually enabled for each account via the User Directory as described in Section 5.5.
Basic Configuration 5.3.4.1. The Audit Log and Alarm Log The System Parameters menu allows you to select three different configuration parameters for the Audit Log and Alarm Log. Note that the Audit Log and Alarm Log function independently, and parameters selected for one log will not be applied to the other. • Off: The Log is disabled, and command activity and/or alarm events will not be logged.
Basic Configuration 5.3.4.3. Reading and Erasing Logs To read the status logs access the command mode, then proceed as follows: • Text Interface: Type /L and press [Enter] to display the Display Log menu. Select the desired Log from the menu, key in the appropriate number and press [Enter], and then follow the instructions in the resulting submenu. • Web Browser Interface: • Audit Log: Move the cursor over the "Logs" link on the left hand side of the screen.
Basic Configuration To erase log data, access command mode via the Text Interface, using an account that permits Administrator level commands, then type /L and press [Enter] to access the Display Logs menu and then proceed as follows: • Audit Log: At the Display Logs menu, type 1 and then press [Enter]. When the Audit Log appears, type E and press [Enter] to erases the Audit Log. • Alarm Log: At the Display Logs menu, type 2 and then press [Enter].
Basic Configuration 5.3.5. Callback Security The Callback function provides an additional layer of security when callers attempt to access command mode via modem. When this function is properly configured, modem users will not be granted immediate access to command mode upon entering a valid password; instead, the unit will disconnect, and dial a user-defined number before allowing access via that number. If desired, users may also be required to re-enter the password after the MPC dials back.
Basic Configuration • Callback Attempts: The number of times that the MPC will attempt to contact the Callback number. (Default = 3 attempts.) • Callback Delay: The amount of time that the MPC will wait between Callback attempts. (Default = 30 seconds.) Notes: • After configuring and enabling Callback Security, you must then define a callback phone number for each desired user account (as described in Section 5.5) in order for this feature to function properly.
Basic Configuration The Power Source Configuration menu and/or System Parameters menu include the following power configuration parameters: • Power Factor: Can be any value from 0.1 to 1.00. (Default = 1.00.) • Power Efficiency: Can be any whole number from 1% to 100%. (Default = 100%.) • Unit to Configure (Local/AUX Unit): This item is used to determine whether power configuration parameters will be applied to your local unit, or to an optional remote unit, connected to one of the local unit's AUX Ports.
Basic Configuration 5.4. User Accounts Each time you attempt to access command mode, you will be prompted to enter a username (login) and password. The username and password entered at login determine which plug(s) you will be allowed to control and what type of commands you will be allowed to invoke. Each username / password combination is defined within a "user account.
Basic Configuration In the default state, the MPC includes one predefined account that provides access to Administrator commands and allows control of all of the MPC's switched power outlets. The default username for this account is "super" (lowercase, no quotation marks), and the password for the account is also "super".
Basic Configuration 5.4.3. Port Access The Port Access parameter can be used to grant connection access to the MPC's DB-9 Console port, RJ-45 Remote port and RJ-45 AUX ports. Normally, the Console port is used for connection to a local control device such as a laptop, the Remote port is used for connection to the optional MPC-DISPLAY unit, and the AUX ports are used for connection to additional remote MPC or BPM units.
Basic Configuration 5.5. Managing User Accounts The User Directory function is employed to create new accounts, display parameters for existing accounts, modify accounts and delete accounts. Up to 128 different user accounts can be created. The "User Directory" function is only available when you have logged into command mode using an account that permits Administrator commands. • Text Interface: Type /F and press [Enter] to access the System Parameters Menu.
Basic Configuration ADD USERNAME TO DIRECTORY: 1. 2. 3. 4. 5. 6. 7. 8. 9. Username: Password: Access Level: Port Access: Plug Access: Plug Group Access Service Access Current/Power Metering Callback Phone #: (undefined) (undefined) User (undefined) (undefined) (undefined) Serial Port, Telnet/SSH, Web On (undefined) Enter: # to select, to return to previous menu ... Figure 5.5: The Add User Menu (Text Interface) Figure 5.
Basic Configuration 5.5.2. Adding User Accounts The "Add Username" option allows you to create new accounts and assign usernames, passwords and plug and plug group access rights to each account. Note that the Add User function is only available when you have accessed command mode using a password that permits Administrator Level commands.
Basic Configuration • Plug Access: Determines which outlet(s) this account will be allowed to control. (Defaults; Administrator and SuperUser = All Plugs On, User = All Plugs Off, ViewOnly = All Plugs Off.) Notes: • If your installation includes optional AUX units, please refer to Section 5.5.2.1 for additional instructions regarding granting user account access to plugs on AUX units.
Basic Configuration • Service Access: Determines whether this account will be able to access command mode via Serial Port, Telnet/SSH or Web. For example, if Telnet/SSH Access is disabled for this account, then this account will not be able to access command mode via Telnet or SSH. (Default = Serial Port = On, Telnet/SSH = On, Web = On.) • Current/Power Metering: Enables/Disables current and power metering for this account.
Basic Configuration 5.5.2.1. Granting User Account Access to Plugs on AUX Units Web Browser Interface To grant a user account access to plugs on AUX units, simply select the desired plugs from the "Configure Plug Access" drop down menu as you normally would and then click on the "Add User" button. Text Interface When Plug Access for each user account is defined via the Text Interface, the following procedure is used to grant access to plugs on optional AUX/Remote units: 1.
Basic Configuration 5.5.3. Modifying User Accounts The "Edit User Directory" function allows you to edit existing user accounts in order to change parameters, plug access rights or Administrator Command capability. Note that the Edit/Modify User function is only available when you have accessed command mode using a password that permits Administrator Level commands. To modify a user account, proceed as follows: • Text Interface: From the User Directory menu, type 3 and press [Enter].
Basic Configuration 5.6. The Plug Group Directory The Plug Group Directory allows you to designate "groups" of plugs that are dedicated to a similar function, and will most likely be switched or rebooted all at the same time or controlled by the same type of user account. For example, an individual equipment rack might include an assortment of devices that belong to different departments or clients.
Basic Configuration 5.6.1. Viewing Plug Groups The "View Plug Group Directory" option allows you to view the configuration of each Plug Group. Note that the View Plug Group Directory function is only available when you have accessed command mode using a password that permits Administrator Level commands. To view Plug Group details, proceed as follows: • Text Interface: Type /G and press [Enter] to display the Plug Group Directory menu. From the Plug Group Directory menu, type 1 and press [Enter].
Basic Configuration ADD PLUG GROUP: 1. Plug Group Name: 2. Plug Access: (undefined) (undefined) Enter: # to select, to return to previous menu ... Figure 5.7: The Add Plug Group Menu (Text Interface) Figure 5.
Basic Configuration 5.6.2. Adding Plug Groups The "Add Plug Group to Directory" option allows you to create new Plug Groups and assign plug access rights to each group. Note that the Add Plug Group function is only available when you have accessed command mode using a password that permits Administrator Level commands. To create new Plug Groups, proceed as follows: • Text Interface: Type /G and press [Enter] to display the Plug Group Directory menu.
Basic Configuration 5.6.2.1. Granting User Account Access to Plugs on AUX Units Web Browser Interface To grant a plug group access to plugs on AUX units, simply select the desired plugs from the "Add Plug Groups" menu as you normally would and then click on the "Add Plug Groups" button. Text Interface When Plug Access for each plug group is defined via the Text Interface, the following procedure is used to grant access to plugs on optional AUX/Remote units: 1.
Basic Configuration 5.6.3. Modifying Plug Groups The "Modify Plug Group" function allows you to edit existing Plug Groups in order to change plug access rights. Note that this function is only available when you have accessed command mode using a password that permits Administrator Level commands. To modify an existing Plug Group , proceed as follows: • Text Interface: Type /G and press [Enter] to display the Plug Group Directory menu. From the Plug Group Directory menu, type 3 and press [Enter].
Basic Configuration PLUG_PARAMETERS - LOCAL 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. A1 A1 A1 A1 A2 A2 A2 A2 A3 A3 A3 A3 A4 A4 A4 A4 Plug Name: Boot/Seq. Delay: Power Up Default: Boot Priority : Plug Name: Boot/Seq. Delay: Power Up Default: Boot Priority : Plug Name: Boot/Seq. Delay: Power Up Default: Boot Priority : Plug Name: Boot/Seq. Delay: Power Up Default: Boot Priority : Local_InfeedA_Outlet1 0.5 Secs On 1 Local_InfeedA_Outlet2 0.5 Secs On 2 Local_InfeedA_Outlet3 0.
Basic Configuration 5.7. Defining Plug Parameters The Plug Parameters Menu is used to define Plug Names, boot/sequence delay times and Power Up Default values for each of the MPC's Switched AC Outlets. Note that this function is only available when you have accessed command mode using a password that permits Administrator Level commands. To define Plug Parameters, proceed as follows: • Text Interface: Type /PL and then press [Enter]. The Plug Parameters Menu will be displayed as shown in Figure 5.9.
Basic Configuration • Power Up Default: Determines how this plug will react when the Default command (/D) is invoked, or after power to the unit has been interrupted and then restored. After the default command is invoked, or power is restored, the MPC will automatically switch each plug On or Off as specified by the Power-Up Default. (Default = On).
Basic Configuration 5.7.1. The Boot Priority Parameter Normally, when an "On" or "Reboot" command is invoked, the MPC will switch on its plugs in their default, numeric order. Although in many cases, the default, numeric order will work fine, there are other cases where an individual device (such as a router) must be switched on first, in order to support a second device that will be switched on later.
Basic Configuration 5.7.1.2. Example 2: Change Plug A5 to Priority 2 In the second Example shown in Figure 5.12, we start out with Boot Priorities for the plugs set as they were at the end of Example 1; Plug A3 is first, Plug A1 is second, Plug A2 is third, Plug A4 is fourth, and Plug A6 is sixth. Next, the Boot Priority for Plug A5 is changed to Priority 2.
Basic Configuration PORT PARAMETERS #01: COMMUNICATION SETTING 1. Baud Rate: 2. Bits/Parity: 3. Stop Bits: 4. Handshake: 9600 8-None 1 RTS/CTS GENERAL PARAMETERS 11. Administrator Mode: 12. Logoff Char: 13. Sequence Disc: 14. Inact Timeout: 15. Command Echo: 16. Accept Break: Permit ^X One Char 5 Min On On PORT MODE PARAMETERS 21. Port Name: 22. Port Mode: 23. DTR Output: 24. Modem Params: Enter # to change, to exit and save configuration... Figure 5.
Basic Configuration 5.8. Serial Port Configuration The Serial Port Configuration menus allow you to select parameters for the MPC's serial Console Port, as well as the Remote Port and AUX Ports. • Console Port: The serial Console Port (Port 1) can be configured for connection to a local PC or Modem or used for connection to serial console ports on other rack equipment.
Basic Configuration General Parameters: • Administrator Mode: Permits/denies port access to Administrator and SuperUser level accounts. When enabled (Permit), the port will be allowed to invoke Administrator and SuperUser level commands, providing they are issued by an account that permits them. If disabled (Deny), then accounts that permit Administrator and SuperUser level commands will not be allowed to access command mode via this port. (Default = Permit).
Basic Configuration Port Mode Parameters: • Port Name: Allows you to assign a name to the Console Port. (Default = undefined.) • Port Mode: The operation mode for this port. (Default = Normal Mode) Depending on the Port Mode selected, the MPC will also display the additional prompts listed below. In the Text Interface, these parameters are accessible via a submenu, which will only be active when the appropriate port mode is selected.
Basic Configuration AUX PORT PARAMETERS: REMOTE SETTINGS 1. Port Function: 2. Baud Rate: 3. Bits/Parity: 4. Stop Bits: 5. Handskake: 6. Inact Timeout: Remote ---------------- AUX2 SETTINGS 13. Port Function: 14. Baud Rate: 15. Bits/Parity: 16. Stop Bits: 17. Handskake: 18. Inact Timeout: Aux2 ---------------- AUX1 SETTINGS 7. Port Function: 8. Baud Rate: 9. Bits/Parity: 10. Stop Bits: 11. Handskake: 12. Inact Timeout: Aux1 ---------------- AUX3 SETTINGS 19. Port Function: 20. Baud Rate: 21.
Basic Configuration 5.8.2. Remote Port and AUX Port Configuration In most applications, it is not necessary to change the configuration of the Remote Port or AUX Port. If you do not intend to use the Remote or AUX ports, or if you intend to use the Remote Port and AUX Ports for connection to the optional MPC-DISPLAY unit and additional MPC units, then the factory default settings for these ports will work fine and you will not need to change the configuration of these ports.
Basic Configuration • Baud Rate: Any standard rate from 300 bps to 115.2K bps. (Default = 9600 bps) • Bits/Parity: (Default = 8-None) • Stop Bits: (Default = 1) • Handshake Mode: XON/XOFF, RTS/CTS (hardware), Both, or None. (Default = RTS/CTS) • Inactivity Timeout: Enables and selects the Timeout Period for this port. If enabled, the port will disconnect when no additional data activity is detected for the duration of the timeout period. (Default = 5 Minutes.
Basic Configuration NETWORK PARAMETERS: COMMUNICATION SETTING 1. IP Address: 2. Subnet Mask: 3. Gateway Addr: 4. DHCP: 5. IP Security: 6. Static Route: 7. DNS Servers: 207.212.30.80 255.255.255.0 207.212.30.1 Off Off Off (undefined) GENERAL PARAMETERS 11. Administrator Mode:Permit 12. Logoff Char: ^X 13. Sequence Disc: One Char 14. Inact Timeout: Off 15. Command Echo: On 16. Accept Break: On SERVERS AND CLIENTS 21. Telnet Access: 22. SSH Access: 23. Web Access: 24. SYSLOG Addr: 25. SNMP Access: 26.
Basic Configuration 5.9. Network Configuration The Network Parameters Menus are used to select parameters and options for the Network Port and also allow you to implement IP Security features, which can restrict access based on the user’s IP Address. Although the Web Browser Interface and Text Interface allow definition of essentially the same parameters, parameters are arranged differently in the two interfaces. In the Text Interface, most network parameters are defined via one menu.
Basic Configuration 5.9.1. Network Port Parameters In the Text Interface, these parameters are found in the main Network Configuration menu (Figure 5.17.) In the Web Browser Interface, these parameters are found by placing the cursor over the "Network Configuration" link on the left hand side of the screen, and then clicking on the "Network Port Parameters" link in the resulting fly-out menu. • Administrator Mode: Permits/denies port access to accounts that allow Administrator or SuperUser level commands.
Basic Configuration 5.9.2. Network Parameters In the Text Interface, these parameters are accessed via the Network Configuration menu (Figure 5.17.) In the Web Browser Interface, these parameters are found by placing the cursor over the "Network Configuration" link on the left hand side of the screen, and then clicking on the "Network Parameters" link in the resulting fly-out menu. Note: The IP Address, Subnet Mask, Gateway Address and DHCP status cannot be changed via the Web Browser Interface.
Basic Configuration • HTTPS Port: Selects the TCP/IP port number that will be used for HTTPS connections. (Default = 443.) Notes: • In the Text Interface, HTTP and HTTPS parameters reside in a separate submenu. To enable and configure HTTP and HTTPS Access via the Text Interface, access the Network Configuration Menu as described in Section 5.9, then type 23, press [Enter] and use the resulting submenu (Figure 14.1) to select parameters.
Basic Configuration 4. If the client’s IP Address is not found in the Deny list, the client will be allowed to connect, even if the address was not found in the Allow list. Notes: • If the MPC finds an IP Address in the Allow list, it will not check the Deny list, and will allow the client to connect.
Basic Configuration 5.9.3.2. Linux Operators and Wild Cards In addition to merely entering a specific IP address or partial IP address in the Allow or Deny list, you may also use any standard Linux operator or wild card. In most cases, the only operator used is "EXCEPT" and the only wild card used is "ALL," but more experienced Linux users may note that other operators and wild cards may also be used. EXCEPT: This operator creates an exception in either the "allow" list or "deny" list.
Basic Configuration 2. Mostly Open: Access is granted by default, and the only clients denied access, are those explicitly listed in the Deny list, and as exceptions in the Allow list. To allow access to all clients except 192.255.255.192 and 168.112.112.05, the Allow and Deny lists would be defined as follows: • Allow List: 1. ALL EXCEPT 192.255.255.192, 168.112.112.05 • Deny List: 1. 192.255.255.192, 168.112.112.
Basic Configuration 5.9.6. SNMP Access Parameters These menus are used to select access parameters for the SNMP feature. To define or change SNMP MIB parameters, proceed as follows: • Text Interface: Type /N and press [Enter] to display the Network Parameters Menu (Figure 5.17.) At the Network Parameters Menu, type 25 and press [Enter] to display the SNMP Access Parameters Menu. • Web Browser Interface: Place the cursor over the "Network Configuration" link on the left hand side of the screen.
Basic Configuration • SNMPv3 User Name: Sets the User Name for SNMPv3. Note that this option is not available when the Version parameter is set to V1/V2. (Default = undefined.) • SNMPv3 Password: Sets the password for SNMPv3. Note that this option is not available when the Version parameter is set to V1/V2. (Default = undefined.) • SNMPv3 Password Confirm: This prompt is used to confirm the SNMPv3 password that was entered at the prompt above.
Basic Configuration 5.9.7. SNMP Trap Parameters These menus are used to select parameters that will be used when SNMP traps are sent. For more information on SNMP Traps, please refer to Section 12. To define or change SNMP Trap parameters, proceed as follows: • Text Interface: Type /N and press [Enter] to display the Network Parameters Menu (Figure 5.17.) At the Network Parameters Menu, type 26 and press [Enter] to display the SNMP Trap Parameters Menu.
Basic Configuration 5.9.8. LDAP Parameters The MPC supports LDAP (Lightweight Directory Access Protocol,) which allows authentication via the "Active Directory" network Directory Service. When LDAP is enabled and properly configured, command access rights can be granted to new users without the need to define individual new accounts at each MPC unit, and existing users can also be removed without the need to delete the account from each MPC unit.
Basic Configuration • TLS/SSL: Enables/Disables TLS/SSL encryption. Note that when TLS/SSL encryption is enabled, the LDAP Port should be set to 636. (Default = Off.) • Bind Type: Sets the LDAP bind request password type. Note that in the Text Interface, when the Bind Type is set to "Kerberos" LDAP menu will include an additional prompt (item 14) that is used to select Kerberos parameters as described in Section 5.9.8.5.
Basic Configuration 5.9.8.1. Adding LDAP Groups Once you have defined several users and passwords via your LDAP server, and assigned those users to LDAP Groups, you must then grant command and port access rights to each LDAP Group at each individual MPC unit.
Basic Configuration • Plug Group Access: This item is used to determine which plug groups the members of this LDAP Group will be allowed to control. (Default = undefined.) • Service Access: This item determines how members of this LDAP Group will be allowed to access command mode. The Service Access parameter is used to allow members of this LDAP group to access command mode via Serial Port or Telnet/ SSH or any combination thereof. (Default = Serial Port = On, Telnet/SSH = On.
Basic Configuration 5.9.8.3. Modifying LDAP Groups If you want to modify an existing LDAP Group in order to change parameters or plug access rights, the "Modify LDAP Group" function can be used to reconfigure group parameters. To Modify an existing LDAP Group, access the MPC command mode using a password that permits access to Administrator Level commands, and then proceed as follows: • Text Interface: Type /N and press [Enter] to display the Network Parameters Menu (Figure 5.17.
Basic Configuration 5.9.8.5. LDAP Kerberos Set Up Kerberos is a network authentication protocol, which provides a secure means of identity verification for users who are communicating via a non-secure network. To access the LDAP Kerberos Set Up menu, access the command mode using a password that permits access to Administrator Level commands and then proceed as follows: • Text Interface: Type /N and press [Enter] to display the Network Parameters Menu (Figure 5.17.
Basic Configuration 5.9.9. TACACS Parameters To access the TACACS Configuration Menus, proceed as follows: • Text Interface: Type /N and press [Enter] to access the Network Configuration Menu. From the Network Configuration Menu, type 28 and press [Enter] to display the TACACS Configuration Menu. • Web Browser Interface: Place the cursor over the "Network Configuration" link on the left hand side of the screen.
Basic Configuration 5.9.10. RADIUS Parameters To access the RADIUS Configuration Menus, proceed as follows: • Text Interface: Type /N and press [Enter] to access the Network Configuration Menu. From the Network Configuration Menu, type 29 and press [Enter] to display the RADIUS Configuration Menu. • Web Browser Interface: Place the cursor over the "Network Configuration" link on the left hand side of the screen.
Basic Configuration 5.9.10.1. Dictionary Support for RADIUS The RADIUS dictionary file can allow you to define a user and assign command access rights and plug access rights from a central location. The RADIUS dictionary file, "dictionary.wti" is included on the CDROM along with this user's guide.
Basic Configuration Example: The following command could be used to set the command access level to "User", allow access to Serial Ports 1, 3, 5 and 7 and Plugs 1 and 2, and also allow access to the first two of five defined plug groups: tom Auth-Type:=Local, User-Password=="tom1" Login-Service=Telnet, Login-TCP-Port=Telnet, User-Name="HARRY-tom", WTI-Super="1", WTI-Plug-Access="1100", WTI-Group-Access="11000", 5-69
Basic Configuration 5.9.11. Email Message Parameters The Email Parameters menu is used to define parameters for email messages that the MPC can send to notify you when an alarm is triggered. To define email message parameters, access the MPC Command Mode using a password that permits access to Administrator Level commands and then proceed as follows: • Text Interface: Type /N and press [Enter] to access the Network Configuration Menu.
Basic Configuration 5.10. Save User Selected Parameters It is strongly recommended to save all user-defined parameters to an ASCII file as described in Section 15. This will allow quick recovery in the event of accidental deletion or reconfiguration of port parameters. When changing configuration parameters via the Text Interface, make certain that the MPC has saved the newly defined parameters before exiting from command mode.
6. Reboot Options In addition to performing reboot cycles in response to commands, the MPC can also be configured to automatically reboot outlets when an attached device does not respond to a Ping command (Ping-No-Answer Reboot) or according to a user defined schedule (Scheduled Reboot.) • Ping-No-Answer Reboot: When the Ping-No-Answer feature is enabled, the MPC will Ping a user selected IP address at regular intervals.
Reboot Options 6.1. Ping-No-Answer Reboot A Ping-No-Answer Reboot can be used to reboot one or more outlets when an attached device does not respond to a Ping Command. In addition, the Ping-No-Answer Reboot feature can also be configured to send an email, Syslog Message or SNMP Trap to notify you whenever a Ping-No-Answer Reboot occurs. Please refer to Section 7.6 for instructions on setting up email alarm notification for Ping-No-Answer reboots.
Reboot Options • Consecutive Failures: Determines how many consecutive failures of the Ping command must be detected in order to initiate a Ping-No-Answer Reboot. For example, if this value is set to "3", then after three consecutive Ping failures, a Ping-No-Answer Reboot will be performed. (Default = 3.) • Reboot: Enables/Disables the Ping-No-Answer Reboot function for the specified IP address. When this item is disabled, the MPC will not reboot the specified outlet(s) when a Ping-No-Answer is detected.
Reboot Options 6.1.1.1. Granting Access to Plugs on AUX Units Web Browser Interface To grant access to plugs on AUX units, simply select the desired plugs from the "Configure Plug Access" drop down menu and then click on the "Add Ping No Answer" button. Text Interface When Plug Access for a Ping No Answer Reboot is defined via the Text Interface, the following procedure is used to grant access to plugs on optional AUX/Remote units: 1.
Reboot Options 6.1.3. Modifying Ping-No-Answer Reboot Profiles After you have defined a Ping-No-Answer profile, you can modify the configuration of the profile using the Modify Ping-No-Answer feature. To modify the configuration of an existing Ping-No-Answer profile, access the command mode using a password that allows Administrator level commands and then proceed as follows: • Text Interface: Access the Ping-No-Answer Reboot Directory menu as described in Section 6.1, then type 3 and press [Enter].
Reboot Options 6.2. Scheduled Reboot The Scheduled Reboot feature can be used to reboot one or more outlets according to a user-defined schedule, or to automatically turn outlets Off and then On according to a user defined schedule. To configure a Scheduled Reboot, access command mode using a password that permits access to Administrator level commands and then proceed as follows: • Text Interface: Type /RB and press [Enter]. The Reboot Options Menu will be displayed.
Reboot Options The Add Scheduled Reboot menu allows you to define the following parameters for each new Scheduled Reboot: • Scheduled Reboot Name: Assigns a name to this Scheduled Reboot. (Default = undefined.) • Plug Action: Determines whether the Scheduled Reboot will result in the outlet(s) being switched Off, or cycled Off and then On again (Reboot.
Reboot Options 6.2.1.1. Granting Access to Plugs on AUX Units Web Browser Interface To grant access to plugs on AUX units, simply select the desired plugs from the "Configure Plug Access" drop down menu and then click on the "Add Scheduled Reboot" button. Text Interface When Plug Access for a Scheduled Reboot is defined via the Text Interface, the following procedure is used to grant access to plugs on optional AUX/Remote units: 1.
Reboot Options 6.2.3. Modifying Scheduled Reboots After you have defined a Scheduled Reboot, you can edit the configuration of the Reboot action using the Modify Scheduled Reboot feature. To modify the configuration of an existing Scheduled Reboot action, access the command mode using a password that allows Administrator level commands and then proceed as follows: • Text Interface: Access the Scheduled Reboot Directory menu as described in Section 6.2, then type 3 and press [Enter].
7. Alarm Configuration When properly configured, the MPC can meter current, temperature and voltage readings, and log this information for future review. In addition, the MPC can also generate alarms when current or temperature readings exceed user-defined trigger levels, when input voltage is lost or restored to the unit, when a circuit breaker is open, when communication with the AUX units is disrupted, when a Ping-No-Answer condition is detected, and when the Invalid Access Lockout feature is triggered.
Alarm Configuration 7.1. The Over Current Alarms The Over Current Alarms are designed to inform you when current consumption reaches or exceeds user-defined levels.
Alarm Configuration To configure the Over Current Alarms, access the MPC command mode using a password that permits Administrator Level commands, and then proceed as follows: • Text Interface: Type /AC and then press [Enter] to display the Alarm Configuration Menu. From the Alarm Configuration Menu, key in the number for the alarm that you wish to configure and then press [Enter].
Alarm Configuration • Email Message: Enables/Disables email notification for this alarm. (Default = On.) Note: The Email Message parameter offers four different options: On, Off, On (Copy to All Triggers) or Off (Copy to All Triggers). If either of the "Copy to All Triggers" options is selected, then email notification for all other alarms will be switched On or Off as indicated by this parameter.
Alarm Configuration 7.1.1. Over Current Alarms - Load Shedding and Auto Recovery The Load Shedding feature is used to switch specific, user-defined, non-essential plugs On or Off whenever current load exceeds the Alarm Set Threshold value. This allows the MPC to automatically shut Off plugs in order to reduce current load when the load approaches user-defined critical levels.
Alarm Configuration 3. After defining the "Unit to Configure" parameter, use items 2, 3, and 4 to select Load Shedding parameters for the selected branch or line. The Branch/Line Load Shedding Configuration Menus offer the following parameters: 1. Enable: Enables/Disables Load Shedding for the corresponding alarm. When enabled, the MPC will switch the user specified plugs whenever current load exceeds the Alarm Set Threshold value. (Default = Disable.) 2.
Alarm Configuration 7.1.1.2. Load Shedding & Auto Recovery Configuration - Web Browser Interface In the Web Browser Interface, Load Shedding and Auto Recovery parameters are defined as follows: 1. Access the Over Current Alarm Configuration Menu as described in Section 7.1. 2. At the Over Current Alarm Configuration Menu, use the two drop down menus next to the Load Shedding button to determine the Local/AUX MPC unit and the desired Branch or Line.
Alarm Configuration • Plug Access: Determines which Plug(s) will be switched when the current load exceeds the Alarm Set Threshold and the Load Shedding feature is triggered at the selected unit/branch/line. For example, if plugs A1, A2 and A3 are selected, then these plugs will be switched On or Off whenever the current load exceeds the Alarm Set Threshold at the selected unit/branch/line. (Default = undefined.
Alarm Configuration 7.1.1.3. Granting Access to Plugs on AUX Units Web Browser Interface To grant access to plugs on AUX units, simply select the desired plugs from the "Configure Plug Access" drop down menu and then click on the "Change Load Shedding" button. Text Interface When Plug Access is defined via the Text Interface, the following procedure is used to grant access to plugs on optional AUX/Remote units: 1. From the Load Shedding menu, type 4 and press [Enter] to display the Plug Access menu.
Alarm Configuration 7.2. The Over Temperature Alarms The Over Temperature Alarms are designed to inform you when the temperature level inside your equipment rack reaches or exceeds certain user-defined levels. There are two separate Over Temperature Alarms; the Initial Threshold alarm and the Critical Threshold Alarm.
Alarm Configuration Both the Over Temperature (Initial Threshold) alarm and the Over Temperature (Critical Threshold) alarm offer the following parameters: • Trigger Enable: Enables/Disables the trigger for this alarm. When Disabled, this alarm will be suppressed. (Default = On.) Note: To cancel an alarm without correcting the condition that caused the alarm, simply toggle the Trigger Enable parameter Off and then back On again. • Alarm Set Threshold: The trigger level for this alarm.
Alarm Configuration • Address 1, 2, and 3: These parameters are used to select which of the three email addresses, defined via the "Email Messages" menu (see Section 5.9.11,) will receive the email alarm notification messages generated by this alarm. The Address parameters can be used to select one, or any combination of the addresses defined via the Email Messages menu. (Default = All On.
Alarm Configuration 7.2.1.1. Load Shedding & Auto Recovery Configuration - Text Interface In the Text Interface, Load Shedding parameters for the Over Temperature Alarm are defined as follows: 1. Access the Over temperature Alarm Configuration Menu as described in Section 7.2. 2. At the Over Temperature Alarm Configuration Menu, type 5 and press [Enter] to access the Load Shedding Configuration Menu. The following parameters will be available: 3. 1.
Alarm Configuration 5. Plug Group Access: Determines which Plug Group(s) will be switched when the Load Shedding feature is triggered. For example, if you have defined a Plug Group named "test", which includes Plugs B3, B4 and B5, and then selected the "test" Plug Group via the Plug Group Access parameter, then all of the plugs in the "test" Plug Group will be switched On or Off whenever the temperature exceeds the Alarm Set Threshold. (Default = undefined.
Alarm Configuration • Plug Access: Determines which Plug(s) will be switched when the temperature exceeds the Alarm Set Threshold and the Load Shedding feature is triggered at the selected unit. For example, if plugs A1, A2 and A3 are selected, then these plugs will be switched On or Off whenever the temperature exceeds the Alarm Set Threshold at the selected unit/branch/line. (Default = undefined.
Alarm Configuration 7.2.1.3. Granting Access to Plugs on AUX Units Web Browser Interface To grant access to plugs on AUX units, simply select the desired plugs from the "Configure Plug Access" drop down menu and then click on the "Change Load Shedding" button. Text Interface When Plug Access is defined via the Text Interface, the following procedure is used to grant access to plugs on optional AUX units: 1. From the Load Shedding menu, type 4 and press [Enter] to display the Plug Access menu.
Alarm Configuration 7.3. The Circuit Breaker Open Alarm The Circuit Breaker Alarm is intended to provide notification in the event that one of the MPC's circuit breakers is opened. When a circuit breaker is open, the MPC can provide prompt notification via Email, Syslog Message or SNMP Trap. Notes: • In order for the MPC to provide alarm notification via Email, communication parameters must first be defined as described in Section 5.9.11.
Alarm Configuration • Email Message: Enables/Disables email notification for this alarm. (Default = On.) Note: The Email Message parameter offers four different options: On, Off, On (Copy to All Triggers) or Off (Copy to All Triggers). If either of the "Copy to All Triggers" options is selected, then email notification for all other alarms will be switched On or Off as indicated by this parameter.
Alarm Configuration The Lost Communication with AUX Units Alarm Configuration Menu offers the following parameters: • Trigger Enable: Enables/Disables the trigger for this alarm. When Disabled, this alarm will be suppressed. (Default = On.) Note: To cancel an alarm without correcting the condition that caused the alarm, simply toggle the Trigger Enable parameter Off and then back On again.
Alarm Configuration 7.5. The Lost Voltage (Line In) Alarm The Lost Voltage (Line In) Alarm is intended to provide notification when one of the power input lines connected to the MPC unit, is lost or disconnected. When one of the power supplies is lost, the MPC can provide notification via Email, Syslog Message or SNMP Trap. Notes: • The Lost Voltage (Line In) alarm will provide notification when one of the available power supplies is lost or disconnected.
Alarm Configuration • Email Message: Enables/Disables email notification for this alarm. (Default = On.) Note: The Email Message parameter offers four different options: On, Off, On (Copy to All Triggers) or Off (Copy to All Triggers). If either of the "Copy to All Triggers" options is selected, then email notification for all other alarms will be switched On or Off as indicated by this parameter.
Alarm Configuration 7.6. The Ping-No-Answer Alarm The Ping-No-Answer Alarm is intended to provide notification when one of the IP addresses defined via the Ping-No-Answer Reboot feature (as described in Section 6.1) fails to respond to a Ping command. When one of the user-defined IP addresses fails to answer a Ping command, the MPC can provide notification via Email, Syslog Message or SNMP Trap.
Alarm Configuration The Ping-No-Answer alarm configuration menu offers the following parameters: • Trigger Enable: Enables/Disables the trigger for this alarm. When Disabled, this alarm will be suppressed. (Default = On.) Note: To cancel an alarm without correcting the condition that caused the alarm, simply toggle the Trigger Enable parameter to Off and then back On again.
Alarm Configuration 7.7. The Invalid Access Lockout Alarm The Invalid Access Lockout Alarm is intended to provide notification when the MPC has locked the Network port due to repeated, invalid attempts to access command mode. Normally, the Invalid Access Lockout feature (discussed in Section 5.3.2) will lock the network port whenever the MPC detects that a user-defined number of invalid passwords have been entered at the Network Port.
Alarm Configuration The Invalid Access Lockout alarm configuration menu offers the following parameters: • Trigger Enable: Enables/Disables the trigger for this alarm. When Disabled, this alarm will be suppressed. (Default = On.) Note: To cancel an alarm without unlocking the port, simply toggle the Trigger Enable parameter Off and then back On again.
Alarm Configuration 7.8. The Power Cycle Alarm The Power Cycle Alarm can provide notification when all input power to the MPC unit is lost and then restored. When one of the power supplies is lost, the MPC can provide notification via Email, Syslog Message or SNMP Trap. Notes: • The Power Cycle alarm can provide notification when all input power to the MPC unit is lost and then restored. This alarm will not function when only one power input line is disconnected.
Alarm Configuration • Address 1, 2, and 3: These parameters are used to select which of the three email addresses defined via the "Email Messages" menu (see Section 5.9.11) will receive the email alarm notification messages generated by this alarm. The Address parameters can be used to select one, or any combination of the addresses defined via the Email Messages menu. (Default = All On.
8. The Status Screens The Status Screens are used to display status information about the switched outlets, Network Port, Plug Groups, Current and Power Metering and the Alarm Log and Audit Log. The Status Screens are available via both the Text Interface and Web Browser Interface. 8.1.
The Status Screens 8.2. The Network Status Screen The Network Status screen shows activity at the MPC's 16 virtual network ports, and lists the TCP Port Number, Active/Free Status and current user name for each virtual network port. To view the Network Status Screen, access command mode using a password that permits access to Administrator Level commands and then proceed as follows: • Text Interface: Type /SN and press [Enter].
The Status Screens 8.3. The Plug Status Screen The Plug Status screen shows the On/Off status of the MPC's switched outlets, and lists user-defined Plug Names, Boot/Sequence Delay values, and Default On/Off settings. Note: • When the Plug Status Screen is viewed by an account with "Administrator" or "SuperUser" command access, all MPC plugs are listed.
The Status Screens 8.4. The Plug Group Status Screen The Plug Group Status screen shows the configuration details and On/Off status for the MPC's user-defined Plug Groups. Notes: • When the Plug Group Status Screen is viewed by an account with "Administrator" or "SuperUser" command access, all MPC plugs and plug groups are listed.
The Status Screens 8.5. The Current Metering Status Screen The Current Metering Status screen is used to display up-to-date readings for Amps, Watts, Voltage and temperature for the MPC unit as well as any optional AUX MPC units that may be connected. To view the Current Metering Log screen, access the MPC command mode and then proceed as follows: • Text Interface: Type /M and press [Enter]. • Web Browser Interface: Place the cursor over the "Current Metering" link on the left hand side of the screen.
The Status Screens 8.6. The Current History Screen The Current History Screen is used to display current, voltage and temperature readings as a function of time. In the Web Browser Interface, the Current History can be displayed as a graph, downloaded in CSV format, or downloaded in XML format. In the Text Interface, the Current History can be displayed as straight, ASCII data, or can be downloaded in CSV or XML format.
The Status Screens To save Current History data, access command mode using an account that permits Administrator level commands, and then proceed as follows: • Text Interface: Type /L and press [Enter] to show the Display Logs menu. From the Display Logs menu, type 3 and press [Enter] to display the Current History menu, which allows you to either display the Current History log in ASCII format, download and save in CSV or XML format, or erase the Current History Log.
The Status Screens 8.7. The Power Range Status Screen The Power Range Status Screen can be used to display power consumption readings over a user-selected period of time, for the MPC unit as well as any optional remote MPC units that may be connected. To view the Power Range Status Screen, access the MPC command mode using an account that permits access to Administrator or SuperUser level commands and then proceed as follows: • Text Interface: Type /L and press [Enter] to access the "Display Logs" menu.
The Status Screens 8.8. The Power History Screen The Power History Screen provides a graph that shows power consumption versus time. To view the Power History Screen, access the MPC command mode using an account that permits access to Administrator or SuperUser level commands, and then proceed as follows: Text Interface: Type /L and press [Enter] to access the "Display Logs" menu.
9. Operation The MPC offers two separate command interfaces; the Web Browser Interface and the Text Interface. Both interfaces offer essentially the same command options and features, and in most cases, parameters defined via the Web Browser Interface will also apply when communicating via the Text Interface (and vice versa.) 9.1. Operation via the Web Browser Interface When using the Web Browser Interface, switching commands are invoked via the Plug Control Screen and Plug Group Control Screen. 9.1.1.
Operation 3. Initiating a Reboot Cycle: From the Plug Control Menu, click the down arrow in the "Action" column for the desired outlet(s), then select "Reboot" from the dropdown menu and click on the "Confirm Plug Actions" button. 4. Switching Outlets Off: From the Plug Control Menu, click the down arrow in the "Action" column for the desired outlet(s), then select "Off" from the dropdown menu and click on the "Confirm Plug Actions" button. 5.
Operation 3. Initiating a Reboot Cycle: From the Plug Group Control screen, locate the Plug Group(s) that you wish to control, then click the down arrow in the task selector box in the "Action" column and use the dropdown menu to select the "Reboot" option. Then click on the "Confirm Plug Group Actions" button to execute the Reboot command. 4.
Operation COMMAND MENU: Version 1.
Operation 9.2.2. Switching and Reboot Commands - Text Interface These commands can be used to switch or reboot the MPC’s switched plugs, and can also be used to set plugs to the user-defined Power-Up Default values. Plugs may be specified by name or number. Notes: • If a switching or reboot command is directed to a plug that is already being switched or rebooted by a previous command, then the new command will be placed in a queue until the plug is ready to receive additional commands.
Operation When switching and reboot commands are executed, the MPC will display a "Sure?" prompt, wait for user response, and then complete the command. The unit will pause for a moment while the command is executed, and then return to the Plug Status Screen. To Switch Plugs, or initiate a Reboot Cycle, proceed as follows: 1. Switch Plug(s) On: a) Local MPC Units or Individual MPC Units: To power-on a plug or Plug Group, type /ON n and press [Enter].
Operation 3. Reboot Plug(s): a) Local MPC Units or Individual MPC Units: To initiate a Boot cycle, type /BOOT n and press [Enter]. Where "n" is the alphanumeric number or name of the desired plug or Plug Group. Note that the "/BOOT" command can also be entered as "/BO". For example: /BOOT B3 [Enter] or /BO ATMSWTCH [Enter] b) AUX/Remote MPC Units: If your local MPC unit is connected to one or more optional AUX/Remote MPC units, type /BOOT aux n and press [Enter].
Operation 9.2.3. Applying Commands to Several Plugs - Text Interface As described below, switching and reboot commands can be applied to only one Switched AC Outlet, or to an assortment of outlets. In addition, when optional AUX/ Remote MPC units have been connected to the AUX ports, the same command line can also be used to switch outlets on several different AUX units. Note: When switching and reboot operations are initiated, Boot/Sequence Delay times will be applied as described in Section 5.7. 1.
Operation 2. Switch a Series of Plugs: To apply a command to a series of plugs, enter the alphanumeric number for the plugs that mark the beginning and end of the series, separated by a colon. a) Switch a Series of Plugs on Local Unit: When switching a series of plugs on your local MPC unit, simply enter the numbers for the plugs that mark the beginning and end of the series, separated by a colon.
Operation 9.2.4. Connecting to Serial Ports - Text Interface In addition to their default functions, the Console Port, Remote Port and AUX ports can also be used for connection to serial console ports on rack mounted devices, providing convenient back door access. Normally, the Remote Port is used for connection to the optional MPC-DISPLAY unit, the AUX ports are used for connection to additional, remote MPC units, and the Console port is used for connection to a local control device.
Operation 9.3. The Automated Mode The Automated Mode allows the MPC to execute switching and reboot commands, without displaying menus or generating response messages. Automated Mode is designed to allow the MPC to be controlled by a device which can generate commands to control power switching functions without human intervention.
Operation 9.4. Manual Operation In addition to the command driven functions available via the Web Browser Interface and Text Interface, some MPC functions can also be controlled manually. For a summary of front panel control functions, please refer to Section 2.1 and Section 2.3. 9.5.
10. SSH Encryption In addition to standard Telnet protocol, the MPC also supports SSH connections, which provide secure, encrypted access via network. In order to communicate with the MPC using SSH protocol, your network node must include an appropriate SSH client. Note that when the /K (Send SSH Key) command is invoked, the MPC can also provide you with a public SSH key, which can be used to streamline connection to the MPC when using SSH protocol.
11. Syslog Messages The Syslog feature can create log records of each Alarm Event. As these event records are created, they are sent to a Syslog Daemon, located at an IP address defined via the Network Parameters menu. 11.1. Configuration If you wish to employ this feature, you must set the real-time clock and calendar via the System Parameters Menu, and define the IP address for the Syslog Daemon via the Network Port Configuration menu. To configure the Syslog function, please proceed as follows: 1.
Syslog Messages TEST NETWORK OPTIONS: 1. 2. 3. 4. SNMP Trap Test Manager 1 SNMP Trap Test Manager 2 Syslog Test Ping Enter: # to select, to exit ... Figure 11.1: The Test Menu (Text Interface, Administrator Mode Only) 11.2. Testing Syslog Configuration After you have configured the MPC as described in Section 11.1, the /TEST command can be used to make certain that the function is properly set up.
12. SNMP Traps SNMP is an acronym for "Simple Network Management Protocol". The SNMP Trap function allows the MPC to send Alarm Notification messages to two different SNMP managers, each time one of the Alarms discussed in Section 7 is triggered. Note: • The SNMP feature cannot be configured via the SNMP Manager. • SNMP reading ability is limited to the System Group. • The SNMP feature includes the ability to be polled by an SNMP Manager.
SNMP Traps 12.2. Testing the SNMP Trap Function After you have finished setting up the SNMP Trap function, it is recommended to test the configuration to ensure that it is working correctly. To test configuration of the SNMP Trap function, proceed as follows: 1. Configure the SNMP Trap function as described in Section 12.1. 2. Access the Text Interface command mode using an account that permits Administrator level commands, then invoke the "/TEST" command at the MPC command prompt.
13. Operation via SNMP If SNMP Access Parameters have been defined as described in Section 5.9.6, then you will be able to manage user accounts, control power and reboot switching and display unit status via SNMP. This section describes SNMP communication with the MPC unit, and lists some common commands that can be employed to manage users, control switching and reboot actions and display unit status. 13.1.
Operation via SNMP 13.3. Configuration via SNMP MPC User accounts can be viewed, created, modified, and deleted via SNMP. User accounts are arranged in a table of 128 rows, and indexed 1-128. User account parameters, as seen through the SNMP, are summarized below. • userTable::userName – 32 character username • userTable::userPasswd – 16 character password • userTable::userAccessLevel – Account access level.
Operation via SNMP 13.3.1. Viewing Users To view users, issue a GET request on any of the user parameters for the index corresponding to the desired user. 13.3.2. Adding Users For an empty index, issue a SET request on the desired parameters. Minimum requirement is a username and password to create a user, all other parameters will be set to defaults if not specified. To create the user, issue a SET request on the userSubmit object. 13.3.3.
Operation via SNMP 13.4. Plug Control via SNMP 13.4.1. Controlling Plugs ON, OFF, BOOT, and DEFAULT commands can be issued for plugs via SNMP. Plugs are arranged in a table of N rows, where N is the number of plugs in the system. Plug parameters are described below. • plugTable::plugID – String indicating the plug's ID. • plugTable::plugName - String indicating the plug's user-defined name.
Operation via SNMP 13.5. Viewing MPC Status via SNMP Status of various components of the MPC can be retrieved via SNMP. Plug Status, and Environmental Status are currently supported. 13.5.1. Plug Status The status of each plug in the system can be retrieved using the command below. • plugTable::plugStatus – The status of the plug. 0 – Plug is OFF 1 – Plug is ON • plugTable::plugName - String indicating the plug's user-defined name. 13.5.2.
Operation via SNMP 13.5.3. System Environment Status The system environment status for the local MPC unit and all connected AUX units can be retrieved for the entire system. • environmentBranchATotalCurrent – Total Branch A current for MPC system (LOCAL and AUX units.) Note that Total Current will be reported in tenths of an Amp (divide result by ten to determine value in Amps.
14. Setting Up SSL Encryption This section describes the procedure for setting up a secure connection via an https web connection to the MPC. Note: SSL parameters cannot be defined via the Web Browser Interface. In order to set up SSL encryption, you must contact the MPC via the Text Interface. There are two different types of https security certificates: "Self Signed" certificates and "Signed" certificates.
Saving and Restoring Configuration Parameters 14.1. Creating a Self Signed Certificate To create a Self Signed certificate, access the Text interface via Telnet or SSH, using a password that permits access to Administrator level commands and then proceed as follows: 1. Type /N and press [Enter] to display the Network Parameters menu. 2. At the Network Parameters menu, type 23 and press [Enter] to display the Web Access menu (Figure 14.1.
Saving and Restoring Configuration Parameters 4. 5. After you have defined parameters 5 through 11, type 12 and press [Enter] (Create CSR) to create a Certificate Signing Request. By default, this will overwrite any existing certificate, and create a new Self Signed certificate. a) The MPC will prompt you to create a password. Key in the desired password (up to 16 characters) and then press [Enter]. When the MPC prompts you to verify the password, key it again and then press [Enter] once.
Saving and Restoring Configuration Parameters 3. 4. Upload the Signed Certificate to the MPC: After the "signed" certificate is returned from the security service, return to the Web Access menu. a) Access the MPC command mode via the Text Interface using an account that permits Administrator level commands as described previously, then type /N and press [Enter] to display the Network Parameters menu, and then type 23 and press [Enter] to display the Web Access menu.
15. Saving and Restoring Configuration Parameters Once the MPC is properly configured, parameters can be downloaded and saved as an ASCII text file. Later, if the configuration is accidentally altered, the saved parameters can be uploaded to automatically reconfigure the unit without the need to manually assign each parameter. Saved parameters can also be uploaded to other identical MPC units, allowing rapid set-up when several identical units will be configured with the same parameters.
Saving and Restoring Configuration Parameters 15.2. Restoring Saved Parameters This section describes the procedure for using your terminal emulation program to send saved parameters to the MPC. 1. Start your terminal emulation program and access the MPC’s Text Interface command mode using an account that permits Administrator level commands. 2. Configure your terminal emulation program to upload an ASCII text file. 3. Upload the ASCII text file with the saved MPC parameters.
Saving and Restoring Configuration Parameters 15.3. Restoring Previously Saved Parameters If you make a mistake while configuring the MPC unit, and wish to return to the previously saved parameters, the Text Interface's "Reboot System" command (/I) offers the option to reinitialize the MPC unit using previously backed up parameters. This allows you to reset the unit to previously saved parameters, even after you have changed parameters and saved them.
16. Upgrading MPC Firmware When new, improved versions of the MPC firmware become available, the "Upgrade Firmware" function can be used to update the unit. Updates can be uploaded via FTP or SFTP protocols. Notes: • The FTP/SFTP servers can only be started via the Text Interface. • All other ports will remain active during the firmware upgrade procedure.
Upgrading MPC Firmware 5. Open your FTP/SFTP application and (if you have not already done so,) login to the MPC unit, using a username and password that permit access to Administrator level commands. 6. Transfer the md5 format upgrade file to the MPC. 7. After the file transfer is complete, the MPC will install the upgrade file and then reboot itself and break all port connections. Note that it will take approximately 10 minutes to complete the installation process.
17. Command Reference Guide 17.1. Command Conventions Most commands described in this section conform to the following conventions: • Text Interface: Commands discussed in this section, can only be invoked via the Text Interface. These commands cannot be invoked via the Web Browser Interface. • Slash Character: Most MPC Text Interface commands begin with the Slash Character (/).
Command Reference Guide 17.2. Command Summary Function Command Syntax Command Access Level Admin.
Command Reference Guide 17.3. Command Set This Section provides information on all Text Interface commands, sorted by functionality 17.3.1. Display Commands /S Display Plug Status Screen Displays the Plug Status Screen, which lists the current On/Off state, plus the plug number, plug name, Boot/Sequence Delay value and Default On/Off value for each plug. For more information, please refer to Section 8.3. Note: In Administrator Mode and SuperUser Mode, all MPC outlets are displayed.
Command Reference Guide /H Help Displays a Help Screen, which lists all available Text Interface commands along with a brief description of each command. Note: In the Administrator Mode, the Help Screen will list the entire MPC Text Interface command set. In SuperUser Mode, User Mode and ViewOnly Mode, the Help Screen will only list the commands that are allowed by the account's access level.
Command Reference Guide 17.3.2. Control Commands /X Exit Command Mode Exits command mode. When issued at the Network Port, also ends the Telnet session. Note: If the /X command is invoked from within a configuration menu, recently defined parameters may not be saved.
Command Reference Guide /ON Switch Plug(s) ON Switches selected plugs(s) or Plug Group(s) On, as described in Section 9.2.2. When the /ON command is used to switch more than one plug, Boot/Sequence Delay Period will be applied as described in Section 5.7. Note: When this command is invoked in Administrator Mode or SuperUser Mode, it can be applied to all MPC plugs and Plug Groups.
Command Reference Guide /OFF Switch Plug(s) OFF Switches selected plugs(s) or Plug Group(s) Off, as described in Section 9.2.2. When the /OFF command is used to switch more than one plug, Boot/Sequence Delay Period will be applied as described in Section 5.7. The /OFF command can also be entered as /OF. Note: When this command is invoked in Administrator Mode or SuperUser Mode, it can be applied to all MPC plugs and Plug Groups.
Command Reference Guide /DPL Set All Plugs to Default States Sets all switched outlets to their user-defined default state. For information on setting outlet defaults, please refer to Section 5.7. Notes: • When this command is invoked in Administrator Mode or SuperUser Mode, it will be applied to all MPC outlets. When invoked in User Mode, the command will only be applied to the plugs that are allowed by the account.
Command Reference Guide /D Third Party Disconnect Invoke the /D command at your resident port to disconnect two other ports. Notes: • The /D command cannot disconnect your resident port • Users are limited to the ports that are specifically allowed by their accounts. Availability: Administrator, SuperUser, User Format: /D[/Y] [x] [Enter] Where: /Y (Optional) suppresses the "Sure?" prompt. x Is the number or name of the port(s) to be disconnected. To disconnect all allowed ports, enter an asterisk.
Command Reference Guide /UL Unlock Port (Invalid Access Lockout) Manually cancels the MPC’s Invalid Access Lockout feature. Normally, when a series of failed login attempts are detected, the Invalid Access Lockout feature can shut down the network port for a user specified time period in order to prevent further access attempts. When the /UL command is invoked, the MPC will immediately unlock all network ports that are currently in the locked state.
Command Reference Guide /G Plug Group Parameters Displays a menu that is used to View, Add, Modify or Delete Plug Groups. For more information on Plug Groups, please refer to Section 5.6. Availability: Administrator Format: /G [Enter] /N Network Port Parameters Displays a menu which is used to select parameters for the Network Port. Also allows access to the IP Security function, which can restrict network access by unauthorized IP addresses.
Command Reference Guide /I Reboot System (Default) Reinitializes the MPC unit and offers the option to keep user-defined parameters or reset to default parameters. As described in Section 5.10.1, the /I command can also be used to restore the unit to previously saved parameters.
Appendix A. Specifications Physical/Environmental: Models MPC-8H-1, MPC-8H-2, MPC-18H-1 and MPC-18H-2: Width: 19” (48.3 cm) (Including Rack Brackets) Depth: 8.7” (22.1 cm) Height: 1.75” (4.5 cm) One Rack U Models MPC-16H-1 & MPC-16H-2: Width: 19” (48.3 cm) (Including Rack Brackets) Depth: 8.7” (22.1 cm) Height: 3.5” (8.9 cm) Two Rack U Models MPC-20V-1 & MPC-20V-2: Width: 4.5” (11.4 cm) Depth: 3.0” (7.6 cm) Length: 31” (78.7 cm) Zero Rack U All Other MPC-V Series Models: Width: 4" (10.2 cm) Depth: 3.
Appendix B. Interface Descriptions DB9 RS232 Port DCD RXD TXD DTR GND RTS CTS 1 2 3 4 5 6 7 8 9 Carrier Detect Data In Data Out Ready Out X Request to Send Clear to Send X Figure B.1: RS232 Console Port Interface B.1. Serial Console Port (RS232) DCD and DTR hardware lines function as follows: 1. 2. When connected: a) If either port is set for Modem Mode, the DTR output at either port reflects the DCD input at the other end.
Appendices B.2. RJ-45 AUX Port Interface The MPC AUX Port is described in Figure B.2 below. Note: The MPC AUX ports do not support DTR or DCD lines. RJ-45 Pin No. RTS 1 2 Request to Send X TXD 3 Data Out GND 4 Ground 5 Pin 8 Pin 1 RXD 6 7 Data In X Clear to Send CTS 8 Figure B.
Appendix C. Connecting Devices to AUX & Remote Ports As discussed in Section 2, the MPC unit includes three RJ-45 AUX Ports and one RJ-45 Remote Port. Typically, the AUX ports are used for connection to up to three additional MPC units (allowing control of up to 80 plugs), and the Remote Port is used for connection to the optional MPC-DISPLAY unit (allowing you to easily see readings on MPC units that may be buried deep within an equipment rack.
Appendices C.2. Connecting an MPC-DISPLAY Unit to an MPC Master Unit Use an RJ-45 Straight Cable to connect the optional MPC-DISPLAY unit to your MPC series master unit. Connect one end of the cable to the RJ-45 serial port on the back of the MPC-DISPLAY unit, and the other end of the cable to the "Remote" port on the face of the MPC series master unit. When connecting an MPC-DISPLAY unit to your MPC master unit, please refer to Figure C.
Appendices C.3. Connecting Other RJ-45 DCE Devices to the AUX & Remote Ports An RJ-ROLL Rollover cable can be used to connect the following RJ-45 DCE devices to the MPC's RJ-45 serial ports: • Cisco Routers with RJ-45 DCE Console Port • Sun Routers with RJ-45 DCE Console Port • Other Devices with RJ-45 DCE Console Port When connecting an RJ-45 DCE device to the MPC, please refer to Figure C.
Appendix D. Customer Service Customer Service hours are from 8:00 AM to 5:00 PM, PST, Monday through Friday. When calling, please be prepared to give the name and make of the unit, its serial number and a description of its symptoms. If the unit should need to be returned for factory repair it must be accompanied by a Return Authorization number from Customer Service.
Appendix E. Rack Mounting The MPC offers a variety of different mounting options to allow the unit to be easily mounted in almost any equipment rack available. In addition to the standard "L" brackets included with all units, MPC-20V series units can also be mounted using mounting buttons, "Hook" Brackets for Dell™ style racks or Zero-U Pocket Brackets for APC© style racks or any rack that features a "pocket" or channel for Zero Unit mounting. E.1.
Appendices 4 1 2 3 5 Figure E.1: Mounting Holes; MPC-20V Back Panel Equipment Rack MPC-20V Unit Retaining Screws “L” Bracket Figure E.2: Attaching the "L" Brackets to the Equipment Rack (MPC-20V Shown) 2. Attaching the "L" Brackets to the Equipment Rack: Determine which direction the MPC unit will face in the rack, then line the "U" slots in the "L" Bracket up with two holes in the equipment rack mounting strip.
Appendices E.2. Mounting Buttons The Mounting Buttons allow MPC-20V series (vertical) units to be mounted in any equipment rack that includes mounting button holes, as shown in Figure E.4. Depending on the location of the mounting button holes in your equipment rack, this can allow the MPC-20V to be mounted on the posts at the rear of the equipment rack, or in some cases, even mounted on the outside of the rack corner posts. 1. 2.
Appendices E.3. Hook Bracket Mounting (MPC-20V Series Only) The Hook Brackets allow MPC-20V series (vertical) units to be easily mounted in Dell™ style equipment racks. The Hook Brackets can be used to mount the MPC-20V in any rack that includes Dell style mounting rails as shown in Figure E.5. The Hook Brackets, which are supplied in a right and left hand pair, allow MPC-20V units to be mounted to any one of the four corner posts in a Dell style equipment rack. 1. 2.
Appendices E.4. Zero-U Pocket Bracket Mounting (MPC-20V Series Only) The Zero-U Pocket Brackets allow you to mount MPC-20V series units in APC© style racks, that include a pocket or channel for zero unit mounting as shown in Figures E.6 and E.7.
Appendices E.5. Universal Mounting Bracket (MPC-20V Series Only) The Universal Mounting Brackets are used to mount vertical format MPC units to equipment rack posts or mounting pads. The Universal Mounting Brackets are often used in cases where the power supply cable enters the rack from above, and allow the unit to be easily mounted upside down. To mount the unit using the Universal Mounting Brackets, proceed as follows: 1. 2.
Appendices Universal Mounting Bracket Screw Holes Retaining Screws MPC Back Panel Figure E.8: Attaching the Universal Mounting Bracket to the MPC Unit Universal Mounting Bracket Screw Hole Retaining Screw Rack Post MPC Front Panel Figure E.
Appendix F. Output Cable Keeper The Output Cable Keeper extends approximately two inches above the face of the MPC-20V series unit, and provides a convenient means to tie output cables in place, to prevent cables from being accidentally disconnected. To install the Output Cable Keeper on your MPC-20V series unit, please proceed as follows: 1.
Appendices Trademark and Copyright Information WTI and Western Telematic are trademarks of Western Telematic Inc.. All other product names mentioned in this publication are trademarks or registered trademarks of their respective companies. Information and descriptions contained herein are the property of Western Telematic Inc.. Such information and descriptions may not be copied, disseminated, or distributed without the express written consent of Western Telematic Inc.. © Copyright Western Telematic Inc.
Index A Accept Break Network Port Serial Port Access Level LDAP Group Accounting Port RADIUS Add LDAP Group Ping-No-Answer Reboot Plug Groups Scheduled Reboot User Accounts Via SNMP Address Circuit Breaker Open Alarm Invalid Access Lockout Alarm Lost Communication Alarm Lost Voltage Alarm Over Current Alarms Over Temperature Alarms Ping-No-Answer Alarm Power Cycle Alarm Administrator Network Port Serial Port Supervisor Mode Administrator Mode Network Port Agency Approvals Alarm Clear Threshold Over Current
Index Circuit Breaker Open Alarm Address Email Message Notify Upon Clear Resend Delay Subject Trigger Enable Clock and Calendar Command Access Level Command Confirmation Command Echo Network Port Serial Port Command Mode Access Logging Out Command Prompt Command Reference Guide Command Set Text Interface Common Name Communication Configuration Menus Restore Previous Restoring Saving Via SNMP Confirmation Prompt Connecting Ports Consecutive Failures Ping-No-Answer Reboot Console Port Administrator Configurat
Index 5-70 5-70 5-70 5-70 5-70 5-70 5-70 5-70 5-70 5-70 5-70 14-1 to 14-3 5-16 2-4 Email Parameters Authentication Type Domain From Address From Name Password Port Number Send Test Email SMTP Server To Address User Name Encryption Erasing Logs Ethernet Port Exit Command Mode Text Interface External Modem 17-5 4-4 F Fallback Fallback Local RADIUS TACACS Fallback Timer RADIUS TACACS Firmware Upgrade From Address Email Parameters From Name Email Parameters Front Panel Buttons 5-61 5-67 5-66 5-67 5-66 16-1
Index LDAP (continued) User Search Base DN User Search Filter Viewing LDAP Groups LEDs Line Power Source Link Ports Horizontal Units Load Shedding Auto Recovery Branch Load Shedding Enable Line Load Shedding Plug Access Plug Group Access Plug State Locality Lockout Attempts Lockout Duration Lockout Enable Logging Out Text Interface Login Logoff Character Network Port Serial Port Log Configuration Log Function Reading and Erasing Syslog Log Functions Text Interface Lost Communication Alarm Address Email Mess
Index Network Port Administrator Horizontal Units SuperUser Supervisor Mode Vertical Units Network Port Parameters Network Status Screen Text Interface Normal Mode DTR Output Notify Upon Clear Circuit Breaker Open Alarm Invalid Access Lockout Alarm Lost Communication Alarm Lost Voltage Alarm Over Current Alarms Over Temperature Alarms Ping-No-Answer Alarm NTP Enable NTP Timeout Primary NTP Address Secondary NTP Address NTP Enable NTP Timeout 4-4, 17-11 5-51 2-4 5-51 5-51 2-6 5-51 to 5-52 8-2 to 8-3 17-3 5-
Index Plug Group Access LDAP Group Load Shedding Ping-No-Answer Reboot Scheduled Reboot Plug Group Control Initiating a Reboot Cycle Web Browser Interface Plug Group Status Screen Text Interface Plug Name Plug Order Plug Parameters Boot/Sequence Delay Boot Priority Plug Name Power Up Default Plug Status Screen Text Interface Pocket Brackets Port Kerberos Port Access User Accounts Port Connection Port Mode Serial Port Port Name Serial Port Port Number Email Parameters Power Configuration Power Cycle Alarm Ad
Index Reset String Modem Mode Restore Configuration Restoring Parameters RS232 Port Interface RSA Client S Safety Information Saving Parameters Text Interface Scheduled Reboot Adding Day Deleting Modifying Plug Access Plug Action Plug Group Access Recurrance Scheduled Reboot Name Time Turn On Day Turn On Time Viewing Search Bind DN Search Pind Password Secondary Address RADIUS TACACS Secondary Host Secondary NTP Address Secondary Secret Word RADIUS Secret Word TACACS Self Signed Certificate Send Test Email
Index SSH Access Encryption Keys SSH Access SSH Port SSL Certificate Common Name Country Create CSR Email Address Locality Organizational Name Organizational Unit State or Province Upload Signed Certificate State or Province Static Route Status Screens Stop Bits Serial Port Subject Circuit Breaker Open Alarm Invalid Access Lockout Alarm Lost Communication Alarm Lost Voltage Alarm Over Current Alarms Over Temperature Alarms Ping-No-Answer Alarm Power Cycle Alarm Subnet Mask Network Port SuperUser Network Por
Index Trigger Enable Circuit Breaker Open Alarm Invalid Access Lockout Alarm Lost Communication Alarm Lost Voltage Alarm Over Current Alarms Over Temperature Alarms Ping-No-Answer Alarm Power Cycle Alarm Turn On Day Scheduled Reboot Turn On Time Scheduled Reboot 7-17 7-25 7-19 7-20 7-3 7-11 7-23 7-26 6-7 6-7 U Unit Description Unit to Configure Load Shedding Power Configuration Universal Mounting Bracket Unlock Port Text Interface Upgrade Firmware Upgrading Firmware Upload CRT Server Key Signed Certificat