User`s guide

17-26
PollCat NetLink II - Users Guide
^B91 Console Port Communication Parameters
(Administrator Mode Only) Defines the baud rate, parity, data bits, and
stop bits for the Console Port. This command uses the following format:
^B91,baud,parity,data,stop [Enter]
Where:
baud Baud Rate: Any standard rate from 300 bps to 115.2 Kbps.
Note that it is only necessary to enter the first two
characters of the baud rate. If an asterisk is entered in this
field, the port will be set at the default rate specified by
set-up switches 1, 2, and 3.
parity Parity Bits: None (n), Odd (o), or Even (e)
data Data Bits: 7 or 8
stop Stop Bits: 1 or 2
Corresponding Menu Function: Console Port Configuration Menu.
^B92 Serial PBX Port Communication Parameters
(Administrator Mode Only) Defines the baud rate, parity, data bits, and
stop bits for the Serial PBX Port. This command uses the following format:
^B92,baud,parity,data,stop [Enter]
Where:
baud Baud Rate: Any standard rate from 300 bps to 115.2 Kbps.
Note that it is only necessary to enter the first two characters
of the baud rate. If an asterisk is entered in this field, the
port will be set to the default rate specified by Set-Up
switches 4 and 5.
parity Parity Bits: None (n), Odd (o), or Even (e)
data Data Bits: 7 or 8
stop Stop Bits: 1 or 2
Corresponding Menu Function: Serial PBX Port Configuration Menu.