Technical Literature
3
PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS
13 SEER — High Efficiency — Single Phase
ACCESSORIES - Condensing Unit
Start Assist Kit - 912933
Providesadditionalstartingtorqueforthecompressor
motorwhenoperatingwithlowlinevoltageorhighoper-
atingtemperatures.
Extreme Wind Condition Mounting Kit - 920900
Model Number FS4BD 018KB 024KB 030KB 036KB 042KB 048KB 060KB
Electrical
Data
Volts-Cycles-Phase(1) 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1
TotalAmps 9.3 13.5 14.8 18.0 19.4 23.2 27.8
DelayFuseMax.(2) 20 25 30 35 40 50 60
Min.CircuitAmpacity 11.6 16.7 18.3 22.2 23.9 28.7 34.4
Component
Data
Coil
Area 8.3 8.3 10.0 10.0 15.3 15.3 17.9
Rows-FPI 1-18 1-18 1-18 1-18 1-18 1-18 1-18
TubeDia Micro-Channel Micro-Channel Micro-Channel Micro-Channel Micro-Channel Micro-Channel Micro-Channel
FanMotor
Type PSC PSC PSC PSC PSC PSC PSC
Amps 0.35 0.7 0.7 1.4 1.5 1.5 1.5
HP 0.05 0.1 0.1 0.25 0.25 0.25 0.25
FanBlade
Dia-#Blades 18”-2 18”-3 18”-3 18”-4 24”-2 24”-2 24”-2
SCFM 2600 2800 3000 3000 3500 3500 3800
CompressorData
RLA 9.0 12.8 14.1 16.6 17.9 21.8 26.4
LRA 48.0 58.3 73.0 79.0 112.0 117.0 134.0
RefrigerantsuctionlineO.D.
NOTE:Liquidlineis3/8”O.D.for
entirelength.
0-24ft. 3/4” 3/4” 3/4” 3/4” 7/8” 7/8” 7/8”
25-39ft. 3/4” 3/4” 3/4” 7/8”(3) 7/8” 7/8” 1-1/8”(4)
40-75ft. 3/4” 3/4” 3/4” 7/8”(3) 7/8” 7/8” 1-1/8”(4)
ApproximateWeight(lbs.)
Net 109 125 138 140 179 179 188
Ship 114 130 144 146 187 187 197
SoundRatingdb 74 74 74 76 79 79 79
(1) Operating Voltage Range: 187v min. — 253v max.
(2) HACR Type Circuit Breakers may be used.
(3) Requires 7/8" to 3/4" reducer from line to unit.
(4) Requires 7/8" to 1-1/8" reducer from line to unit.
(5) Additional charge for line sets above 15 feet.
Values based on suction line as follows with 3/8" liquid line.
a) 3/4" = 0.6 oz. per additional foot.
b) 7/8" = 0.7 oz. per additional foot.
c) 1 1/8 = 0.8 oz per additional foot.