Technical Literature

6
BLOWER PERFORMANCE
* Denotes factory set cooling speed
** Denotes factory set electric heating speed
NOTE: Airflow performance is with a dry coil
Model number External Static Pressure Drop - inches water column
Q6SE 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
* Tap T1 823 38.39 784 40.30 712 44.37 646 48.91 580 54.47 510 61.95 436 72.46 - -
** Tap T2 969 32.60 924 34.19 866 36.48 800 39.49 717 44.06 652 48.46 591 53.46 522 60.52
X24
Tap T3 1068 29.58 1010 31.28 947 33.36 906 34.87 814 38.81 743 42.52 674 46.88 617 51.21
Tap T4 1188 26.59 1142 27.67 1068 29.58 1022 30.91 954 33.12 861 36.69 803 39.34 763 41.41
Tap T5 1330 23.75 1274 24.80 1221 25.88 1164 27.14 1105 28.59 1044 30.26 957 33.01 881 35.86
**
Tap T1 890 35.50 832 37.97 766 41.25 687 45.99 624 50.63 576 54.85 502 62.94 419 75.40
*
Tap T2 969 32.60 924 34.19 866 36.48 800 39.49 717 44.06 652 48.46 591 53.46 522 60.52
X30
Tap T3 1188 26.59 1142 27.67 1068 29.58 1022 30.91 954 33.12 861 36.69 803 39.34 763 41.41
Tap T4 1382 22.86 1334 23.68 1273 24.82 1220 25.90 1164 27.14 1097 28.80 1020 30.97 947 33.36
Tap T5 1640 19.26 1604 19.70 1547 20.42 1490 21.20 1437 21.99 1381 22.88 1324 23.86 1249 25.30
**
Tap T1 1137 27.79 1075 29.39 1012 31.22 950 33.26 863 36.61 770 41.03 694 45.52 619 51.04
Tap T2 1242 25.44 1187 26.62 1128 28.01 1057 29.89 993 31.82 921 34.30 827 38.20 754 41.90
X36 *
Tap T3 1418 22.28 1370 23.06 1308 24.15 1251 25.25 1204 26.24 1123 28.13 1064 29.69 974 32.44
Tap T4 1567 20.16 1515 20.85 1459 21.65 1397 22.62 1338 23.61 1272 24.84 1184 26.68 1107 28.54
Tap T5 1700 18.58 1658 19.06 1596 19.80 1534 20.60 1481 21.33 1421 22.23 1358 23.27 1279 24.70
**
Tap T1 1257 25.13 1199 26.35 1133 27.89 1070 29.53 982 32.17 906 34.87 830 38.06 761 41.52
Tap T2 1374 22.99 1332 23.72 1270 24.88 1220 25.90 1153 27.40 1077 29.34 972 32.50 901 35.07
X42
Tap T3 1574 20.07 1520 20.79 1470 21.49 1418 22.28 1356 23.30 1295 24.40 1214 26.02 1095 28.85
*
Tap T4 1733 18.23 1678 18.83 1637 19.30 1575 20.06 1528 20.68 1467 21.54 1408 22.44 1334 23.68
Tap T5 1848 17.10 1795 17.60 1741 18.15 1708 18.50 1641 19.25 1593 19.83 1541 20.50 1477 21.39
*
Tap T1 952 33.19 901 35.07 864 36.57 728 43.40 672 47.01 583 54.19 508 62.19 - -
**
Tap T2 1646 19.19 1593 19.83 1520 20.79 1476 21.41 1417 22.30 1349 23.42 1265 24.98 1198 26.37
X48
Tap T3
1764 17.91 1705 18.53 1626 19.43 1570 20.12 1525 20.72 1451 21.77 1403 22.52 1304 24.23
Tap T4 1962 16.10 1916 16.49 1838 17.19 1787 17.68 1720 18.37 1670 18.92 1595 19.81 1537 20.56
Tap T5 2391 13.21 2334 13.54 2301 13.73 2242 14.09 2180 14.49 2132 14.82 2074 15.23 2017 15.66
Tap T1 1088 29.04 1032 30.61 958 32.98 878 35.98 789 40.04 715 44.19 641 49.29 570 55.43
**
Tap T2 1764 17.91 1705 18.53 1626 19.43 1570 20.12 1525 20.72 1451 21.77 1403 22.52 1304 24.23
X60 *
Tap T3 1962 16.10 1916 16.49 1838 17.19 1787 17.68 1720 18.37 1670 18.92 1595 19.81 1537 20.56
Tap T4 2106 15.00 2059 15.34 2000 15.80 1944 16.25 1878 16.82 1828 17.28 1751 18.04 1689 18.71
Tap T5 2391 13.21 2334 13.54 2301 13.73 2242 14.09 2180 14.49 2132 14.82 2074 15.23 2017 15.66