Programming instructions
- Page 10 -
IL 30-471 (E)
Pickup (Hz) Dropout (Hz) SW2-9 SW3-1
59 57 ON ON
58 56 OFF ON
57 55 ON OFF
56 54 OFF OFF
49 47 ON ON
48 46 OFF ON
47 45 ON OFF
46 44 OFF OFF
NORMAL SOURCE
Underfrequency Sensing Programming
Table 5
Underfrequency Pickup and Dropout
Pickup (Hz) Dropout (Hz) SW3-2 SW3-3
59 57 ON ON
58 56 OFF ON
57 55 ON OFF
56 54 OFF OFF
49 47 ON ON
48 46 OFF ON
47 45 ON OFF
46 44 OFF OFF
EMERGENCY SOURCE
Underfrequency Sensing Programming
Table 7
Underfrequency Pickup and Dropout
Pickup (Hz) Dropout (Hz) SW2-9 SW3-1
61 63 ON ON
62 64 OFF ON
63 65 ON OFF
64 66 OFF OFF
51 53 ON ON
52 54 OFF ON
53 55 ON OFF
54 56 OFF OFF
Overfrequency Sensing Programming
Table 6
Overfrequency Pickup and Dropout
Pickup (Hz) Dropout (Hz) SW3-2 SW3-3
61 63 ON ON
62 64 OFF ON
63 65 ON OFF
64 66 OFF OFF
51 53 ON ON
52 54 OFF ON
53 55 ON OFF
54 56 OFF OFF
Overfrequency Sensing Programming
Table 8
Overfrequency Pickup and Dropout
NOTE:
Underfrequency sensing and/or Overfrequency sensing functions
may be programmed into the ATS Controller through the “Option
Program Key”. In the case which both “Uf” and Of” Sensing
functions are activated, the same DIP switch settings will be
applied to both functions. Two equivalent sizes of sensing
hysteresises will be assigned to below and above the system
line frequency respectively.
NOTE:
Underfrequency sensing and/or Overfrequency sensing functions
may be programmed into the ATS Controller through the “Option
Program Key”. In the case which both “Uf” and Of” Sensing
functions are activated, the same DIP switch settings will be
applied to both functions. Two equivalent sizes of sensing
hysteresises will be assigned to below and above the system
line frequency respectively.