Programming instructions
- Page 11 -
IL 30-471 (E)
DELAY FUNCTION PROGRAMMING
TDNE - Time Delay Normal To Emergency
Table 9
TDNE Range Select
RANGE SW3-4 SW3-5
0.1 sec. to 60 sec. ON ON
0.16 min. to 10 min. OFF ON
1.0 min. to 60 min. ON OFF
3.0 min. to 200 min. OFF OFF
TDEN - Time Delay Emergency To Normal
Table 10
TDEN Range Select
RANGESW3-6 SW3-7
0.1 sec. to 60 sec. ON ON
0.16 min. to 10 min. OFF ON
1.0 min. to 60 min. ON OFF
3.0 min. to 200 min. OFF OFF
TDEC - Time Delay Engine Cool Down
Table 11
TDEC Range Select
RANGE SW3-8 SW3-9
0. 1 sec. to 60 sec. ON ON
0.16 min. to 10 min. OFF ON
1.0 min. to 60 min. ON OFF
3.0 min. to 200 min. OFF OFF
ADDING EXTRA ON-BOARD PROGRAMMABLE
OPTIONS:
When it is desired, extra on-board programmable control
options can be added to a Robonic with the single board
controller. The list of the installable on-board options are
as follows;
1. Overvoltage sensing on Normal Source.
2. Underfrequency sensing on Normal Source.
3. Overfrequency sensing on Normal Source.
4. Overvoltage sensing on Emergency Source.
5. Overfrequency sensing on Emergency Source.
6. Time Delay Normal to Emergency.
7. Time Delay Emergency to Normal.
8. Time Delay Engine Cool Down.
9. Preferred Source Selection.
After the factory programmed “Option Key” which contains
the choice option(s) and the associated parts, if required,
are received, turn off the Normal Source and make sure
to disable the Emergency Source by turning the Gen set
start control to manual. Plug the ‘Option Key” into the 1 0-
pin socket (J2) that is located in the centre of the control-
ler circuit board. The Key is not polarized and can be
plugged in either way. Install any extra parts if supplied.
Turn the Normal Source back on. The new option
function(s ) will be programmed into the single board con-
troller.
NOTE:
The DIP switches located and accessed from the bot-
tom-left portion of the control board must be properly
set according to application requirements for the added
control option(s). Please refer to the section that con-
tains the instruction for DIP Switch Setting.
120 208 220 240 380 400 415 480 600
65% 78 135 143 156 247 260 270 312 390
70% 84 146 154 168 266 280 291 336 420
75% 90 156 165 180 285 300 311 360 450
80% 96 166 176 192 304 320 332 384 480 Std. UV Dropout
85% 102 177 187 204 323 340 353 408 510
90% 108 187 198 216 342 360 374 432 540 Std. UV Pickup
95% 114 198 209 228 361 380 394 456 570
100% 120 208 220 240 380 400 415 480 600
105% 126 218 231 252 399 420 435 504 630 Std. OV Pickup
110% 132 229 242 264 418 440 457 528 660
115% 138 239 253 276 437 460 477 552 690 Std. OV Dropout
120% 144 249 264 288 456 480 498 576 720
125% 150 260 275 300 475 500 519 600 750
130% 156 270 286 312 494 520 540 624 780
135% 162 281 297 324 513 540 560 648 810
Table 12
Normal System Voltage