Programming instructions

- Page 14 -
IL 30-471 (E)
Programming and adjustments for plug-in sensing
control modules.
TIME DELAY MODULE
Style Number 782OC96GO1
The Timer Card is a multi-range timer. The card may be
used as a replacement for older single range timer cards
in existing equipment.
The card may be “programmed” for any one of five timing
ranges by simply moving a jumper to the appropriate po-
sition. The actual time desired is then set with a front
accessible potentiometer.
Programming the Timer Card
1. If the Timer Card must be removed from a Transfer
Switch that is in service, it is a good idea to disable
the logic first by separating the logic disconnect plug,
so that a possibly undesired transfer is avoided.
CAUTION: Disconnecting the logic WILL cause the
Engine Generator to start unless it has been disabled.
2. The card is supplied with a single jumper, which must
be placed on the Range Select Terminals as follow:
RANGE SELECT TIMING RANGE *
1 1 - 60 Seconds
4 4 - 240 Seconds (.07 - 4 Min.)
8 8 - 480 Seconds (.13 - 8 Min.)
32 .5 - 32 Minutes
64 1 - 64 Minutes
*NOTE: Timing ranges shown are guaranteed. Actual
available range may be slightly larger.
VOLTAGE SENSING MODULE
Style Number 782OC97GO1
The card may be used as a replacement for older ver-
sions of the plug-in cards in existing equipment.
The card may be “programmed” to perform a voltage sens-
ing function, either undervoltage or overvoltage.
Programming of the card is accomplished by positioning
jumpers on the positions labelled J1 through J7 on the
board itself. This allows easy filed modification of the card
at the user’s discretion. Both the function and the pickup
and dropout values may be easily changed by following
the instructions provided.
Cards shipped from the factory are programmed to the
user’s original specification, or to the standard pickup and
dropout values as follows:
FUNCTION PICKUP DROPOUT
Undervoltage 90% 80%
Overvoltage 105% 115%
Programming the card
Reprogramming of the card may be accomplished by us-
ing the attached instructions with Table 13 and 14 or Table
13A and 14A.
It is recommended that you remove ALL jumpers from Jl
through J7. As supplied from the factory there are erictigh
jur-npers to program the card for any function and value.
The card may be programmed for either UNDERVOLTAGE
or OVERVOLTAGE. Attempting to program the card for
both voltage sensing functions at the same time WILL
CAUSE THE CARD TO MALFUNCTION AND POSSI-
BLY DAMAGE THE ELECTRONICS ON THE CARD!!
NOTE:
If the card is to be used as a replacement for older ver-
sions of the plug-in cards in existing equipment, please
check the Date Code that is stamped on the nameplate of
the Control Transformer Module (16OD997GO1-G24).
* For Robonics with control transformer mod-
ule’s date code dated AFTER Sept. 1/92,
follow Table 13 and 14 to program the voltage
sensing function.
* For Robonics with control transformer mod-
ule’s date code dated BEFORE Sept. 1/92,
follow Table 13A and 14A to programme the
sensing function.