NORMAL SOURCE
Undervoltage Sensing Programming
Table 1
Undervoltage Pickup and Dropout
Pickup (%) Dropout (%) SW1-1 SW1-2 SW1-3 SW1-4
100 95 ON ON ON ON
90 ON ON OFF ON
85 ON ON ON OFF
80 0N 0N 0FF 0FF
95 90 OFF ON ON ON
85 OFF ON ON ON
80 OFF ON OFF OFF
75 OFF ON OFF OFF
90 85 ON OFF ON ON
80 ON OFF OFF ON
75 ON OFF ON OFF
70 ON OFF OFF OFF
85 80 OFF OFF ON ON
75 OFF OFF OFF ON
70 OFF OFF ON OFF
65 OFF OFF OFF OFF
Pickup (%) Dropout (%) SW2-1 SW2-2 SW2-3 SW2-4
100 95 ON ON ON ON
90 ON ON OFF ON
85 ON ON ON OFF
80 0N 0N 0FF 0FF
95 90 OFF ON ON ON
85 OFF ON ON ON
80 OFF ON OFF OFF
75 OFF ON OFF OFF
90 85 ON OFF ON ON
80 ON OFF OFF ON
75 ON OFF ON OFF
70 ON OFF OFF OFF
85 80 OFF OFF ON ON
75 OFF OFF OFF ON
70 OFF OFF ON OFF
65 OFF OFF OFF OFF
EMERGENCY SOURCE
Undervoltage Sensing Programming
Table 3
Undervoltage Pickup and Dropout
Pickup (%) Dropout (%) SW1-5 SW1-6 SW1-7 SW1-8
105 110 ON ON ON ON
115 ON ON OFF ON
120 ON ON ON OFF
125 0N 0N 0FF 0FF
110 115 OFF ON ON ON
120 OFF ON OFF ON
125 OFF ON OFF OFF
130 OFF ON ON OFF
115 120 ON OFF ON ON
125 ON OFF OFF ON
130 ON OFF ON OFF
135 ON OFF OFF OFF
120 125 OFF OFF ON ON
130 OFF OFF OFF ON
135 OFF OFF ON OFF
140 OFF OFF OFF OFF
Overvoltage Sensing Programming
Table 2
Overvoltage Pickup and Dropout
Pickup (%) Dropout (%) SW2-5 SW2-6 SW2-7 SW2-8
105 110 ON ON ON ON
115 ON ON OFF ON
120 ON ON ON OFF
125 0N 0N 0FF 0FF
110 115 OFF ON ON ON
120 OFF ON OFF ON
125 OFF ON OFF OFF
130 OFF ON ON OFF
115 120 ON OFF ON ON
125 ON OFF OFF ON
130 ON OFF ON OFF
135 ON OFF OFF OFF
120 125 OFF OFF ON ON
130 OFF OFF OFF ON
135 OFF OFF ON OFF
140 OFF OFF OFF OFF
Overvoltage Sensing Programming
Table 4
Overvoltage Pickup and Dropout