Specifications

CI-8 Installation and Operation
P/N 66104700001 Rev. F 2-5
Figure 2-3: Power Connections
Battery input fuses, F1 and F2, and should be checked periodically. Replace bad fuses with 1-
amp fuses only. The CI-8 does not charge the batteries; an external battery charger must be used
and the charge level checked periodically.
Failure to follow the battery connection instructions below can result in a blown fuse.
1. Connect the first battery's negative terminal to the BATT- terminal of the CI-8, and connect
the battery's positive terminal to the COMM terminal of the CI-8.
2. Connect the second battery's negative terminal to the COMM terminal of the CI-8, and the
battery's positive terminal to the BATT+ terminal of the CI-8.
Figure 2-4: Battery Connection