Specifications
WSE • 3/21/97 16720 — iii Alto 818 Access Control System
Table of Contents
PART I GENERAL................................................................................................................................................................1
.1 SECTION INCLUDES........................................................................................................................................1
A. Section includes specifications for an integrated security management system
which shall perform the following general services:..........................................................1
1. Access control. ......................................................................................................................1
2. Alarm monitoring.................................................................................................................1
3. Reporting functions..............................................................................................................1
4. Security management functions.........................................................................................1
.2 SYSTEM DESCRIPTION ...................................................................................................................................1
A. Access Control System:....................................................................................................................1
1. Access management system (System) shall monitor and control access to
areas defined herein. .................................................................................................1
2. System shall be capable of supporting multiple access control technologies
at each door, as well as alarm inputs and control outputs. .................................1
3. System shall consist of a microprocessor based controller, card readers
and/or Keypads [and host software]........................................................................1
4. System shall be capable of operating with or without host software station. .............1
5. Specific types of devices and their functions shall be addressed in relevant
sections. .......................................................................................................................1
B. Description of work:.........................................................................................................................1
1. The Systems Integrator shall include all necessary labor, tools, equipment,
and ancillary materials required to furnish and install a complete and
operational access control and alarm monitoring system...................................1
2. Access Control System will manage access to [building] [and] [selected
areas] using [encoded cards.] [and/or] [coded Keypads.] .....................................1
3. The extent of Access Control System work is defined to include, but not by
way of limitation: .......................................................................................................1
4. Requirements are indicated elsewhere in these specifications for work
including, but not limited to, raceways and electrical boxes and
fittings required for installation of control equipment and wiring: not
the work of this section.............................................................................................1
.3 SUBMITTALS.....................................................................................................................................................1
A. Product Data: Submit for prior approval, [__________] copies of manufacturer’s
data on Proximity or Magnetic Stripe Access Control System and components.............1
B. Shop Drawings: Submit dimensioned drawings of [proximity] [and/or] [Magnetic
Stripe] [and/or] [Keypad] Access Control System and accessories including,
central controller, external keyboard and printer, [proximity card reading
sensors] [or magnetic stripe card readers,] [Keypads,] power supplies
switches and ancillary equipment. ........................................................................................1
C. One Line Diagram: Submit a one line diagram of the system configuration
proposed if it differs from that illustrated in the riser diagram included in
these specifications. Submittals indicating typical riser diagrams are not
acceptable. .................................................................................................................................2
D. Operator’s Manual: Submit for prior approval, [__________] copies of
manufacturer’s manual for programming and operating the Alto 818SC/SX
system and its related components. ......................................................................................2
.4 QUALITY ASSURANCE:....................................................................................................................................2
A. Manufacturer: Manufacturer of products defined in this section must have: .........................2
1. Industry experience: Company must have at least 20 years experience in
manufacturing and servicing access management systems................................2
2. ISO 9001 Certification: Manufacturing process of company must meet
stringent standards of ISO 9001 Certification.........................................................2
B. Systems Integrator: ..........................................................................................................................2
1. Company with a minimum of [5 (five)] years system design, engineering
supervision, and installation experience in the alarm, building
automation, or Access Control industry. ................................................................2
2. Company that is trained and authorized to install manufacturer products.................2
C. System Checkout: .............................................................................................................................2
1. Pre-testing: All components and assemblies of the control unit are to be
pre-tested at the factory prior to shipment.............................................................2
2. Burn-in: 1,000 hours at normal operating conditions or equivalency. ........................2
3. On-site testing: Manufacturer trained and authorized Systems Integrator
shall functionally test each component in the system after