Specifications
WSE • 3/21/97 16720 — 2 Alto 818 Access Control System
C. One Line Diagram: Submit a one line diagram of the system configuration proposed if it differs from
that illustrated in the riser diagram included in these specifications. Submittals indicating typical riser
diagrams are not acceptable.
D. Operator’s Manual: Submit for prior approval, [__________] copies of manufacturer’s manual for
programming and operating the Alto 818SC/SX system and its related components.
.4 QUALITY ASSURANCE:
A. Manufacturer: Manufacturer of products defined in this section must have:
1. Industry experience: Company must have at least 20 years experience in manufacturing and
servicing access management systems.
2. ISO 9001 Certification: Manufacturing process of company must meet stringent standards of ISO
9001 Certification.
B. Systems Integrator:
1. Company with a minimum of [5 (five)] years system design, engineering supervision, and
installation experience in the alarm, building automation, or Access Control industry.
2. Company that is trained and authorized to install manufacturer products.
C. System Checkout:
1. Pre-testing: All components and assemblies of the control unit are to be pre-tested at the factory
prior to shipment.
2. Burn-in: 1,000 hours at normal operating conditions or equivalency.
3. On-site testing: Manufacturer trained and authorized Systems Integrator shall functionally test
each component in the system after installation to verify proper operation and confirm that the
panel wiring and addressing conform to the wiring documentation.
4. Service facility: Systems Integrator shall have service facilities within [_____] miles of the
installation.
D. Regulatory Requirements:
1. NEC Compliance: All electrical wiring work shall comply to NEC.
2. NEMA Compliance: Electrical equipment shall comply with applicable portions of NEMA.
3. FCC Emissions: All assemblies shall be in compliance with FCC emission standards.
a. Microprocessor based controller: Part 15, Subpart F, Class A.
b. Proximity Card Reading Sensors: Part 15, Subpart F (field disturbance sensors).
c. Dial-up modems: Part 68.
4. UL-1012 and CSA: All power supplies shall be in compliance with Underwriters Laboratories
standard 1012 and CSA standards for power supplies.
5. [UL-294: The system shall comply with Underwriters Laboratories standard 294 for Access
Control Systems. (Alto 818 SX only)]
E. Warranty:
1. Analog Proximity Command Cards: No less than 5 (five) years.
2. Digital Command Cards: No less than 1 (one) year.
3. System Components: 15 (fifteen) months from shipment date or 12 (twelve) months from date of
purchase by Systems Integrator, whichever comes first.