Gas Fired Residential Floor and Wall Mount Combi Boilers Installation Start-Up Maintenance Parts Warranty WBRC**140 / 199* WBRUC**140 / 199* Models * “F” Denotes Floor Model; “W” Denotes Wall Mount Model, ** “NG” Denotes Natural Gas; “LP” Denotes Propane Gas Heat Exchanger Bears the ASME “H” Stamp ! DANGER This manual must only be used by a qualified service technician. Read all instructions in this manual before installing. Perform steps in the given order.
! WARNING WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. • Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor’s phone.
Foreword This manual is intended to be used in conjunction with other literature provided with the boiler. This includes all related control information. It is important that this manual, all other documents included in this system, and additional publications including the National Fuel Gas Code - ANSI Z223.1 (latest versions), be reviewed in their entirety before beginning any work.
NOTICE IMPORTANT In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, Westinghouse has provided this boiler with multiple features designed to save energy by reducing the boiler water temperature as heating load decreases. These features include: • A modulating combustion system that adjusts firing rate based on heat demand. • Adjustment of boiler set point based on inferred heat load as determined by an outdoor sensor.
D. Piping the Boiler E. Applications F. CH and DHW Pressure Relief Valves Part 5 - Venting A. General B. Approved Materials for Exhaust Vent and Intake Pipe C. Additional Requirements for Installation in Canada D. Exhaust Vent and Intake Pipe Location E. Exhaust Vent and Intake Pipe Sizing F. Tightening Boiler Collar to Exhaust Vent and Intake Pipe G. Exhaust Vent and Intake Pipe Installation H.
NOTICE ! WARNING This boiler must be installed by a qualified service technician. Improper installation and/or operation can cause a potentially hazardous situation, which, if not avoided, could result in serious injury or death, and will void the warranty. The manufacturer cannot anticipate every circumstance that might involve a potential hazard. Each installation has its own specialized characteristics, requirements, and possible hazards.
D. When Servicing the Boiler ! WARNING Be sure to disconnect electrical power before opening boiler cabinet or performing service. Label all wires while performing service to ensure proper re-wiring of the boiler. Wiring errors can cause improper or dangerous operation. Failure to do so could result in an electrical shock, improper boiler operation, property damage, serious personal injury, or death. discontinue use of the boiler and contact an authorized technician or licensed professional.
H. Water Temperature Adjustment and Scalding This boiler can deliver scalding water. Be careful whenever using hot water to avoid scalding injury. Certain boilers such as dishwashers and automatic clothes washers may require increased water temperatures. By setting the thermostat on this heater to obtain the increased water temperature required by these boilers you may create the potential for scald injury. To protect against injury, install a mixing valve in the water system.
Part 2 - Before You Start Open the shipping crate of the boiler. NOTICE UNCRATING THE BOILER - Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee. A.
• Condensate Removal Pump (Part # 554200) • 2” Mesh Vent Screens (Part # 7850P-088) NOTE: When using an optional system sensor, pipe insulation must be wrapped around it to improve temperature measurement accuracy and increase overall system efficiency. Part 3 - Prepare the Boiler Installation Remove all sides of the shipping crate to allow the boiler to be moved into its installation location.
CAUTION Correct Installation Incorrect Installation Figure 1 - Leveled Boiler (Floor Model) ! WARNING The space must be provided with combustion / ventilation air openings correctly sized for all other boilers located in the same space as the boiler. The boiler cover must be securely fastened to prevent the boiler from drawing air from the boiler room. This is particularly important if the boiler is in a room with other boilers.
! WARNING Do not attempt to vent this appliance by any means other than those described in this manual. Doing so will void the warranty and may result in severe personal injury or death. Vents must be properly supported. Appliance exhaust and intake connections are not designed to carry heavy weight. Vent support brackets must be within 1’ of the appliance and the balance at 4’ intervals. Appliance must be readily accessible for visual inspection for first 3’ from the appliance.
Products to Avoid Areas Likely to Have Contaminants Spray cans containing fluorocarbons Dry cleaning / laundry areas and establishments Permanent wave solutions Swimming pools Chlorinated waxes / cleaners Metal fabrication plants Chlorine-based swimming pool chemicals Beauty shops Calcium chloride used for thawing Refrigeration repair shops Sodium chloride used for water softening Photo processing plants Refrigerant leaks Auto body shops Paint or varnish removers Plastic manufacturing pl
I. Technical Specifications Model 140 Installation Minimum / Maximum Input (Btu/Hr) 199 Indoor, Wall Mounted Model or Floor Model, Fully Condensing Central Heating (CH) Domestic Hot Water (DHW) 19,900 / 140,000* 14,000 / 140,000 19,900 / 199,000* Flue System Category IV, Sealed Combustion Direct Vent, Power Vent Vent Run 2” (50 feet), 3” (100 feet), Schedule 40 PVC, CPVC, PP AFUE 96% 95% 35oF Rise 7.1 GPM 9.9 GPM 45oF Rise 5.5 GPM 7.7 GPM 77oF Rise 3.2 GPM 4.
BOTTOM TOP Figure 3 - Wall Mount Model Dimensions Description Diameter A Automatic Air Vent - B Air Intake Adapter C Exhaust Vent Adapter D Pressure Relief Valve Adapter E CH Supply Adapter F CH Return Adapter G DHW Outlet Adapter H DHW Inlet Adapter I K L M 140 17.3 34 15.4 3/4” NPTF 1” NPT 3/4” NPT Gas Inlet Adapter J Table 9 - Adapter Specifications - All Models Model 3” N Condensate Adapter 1/2” NPT (3/4” PVC Socket on Floor Models) O P Q R S T U V 6.
Figure 4 - Floor Model Dimensions Model K L M N O P Q 140 17.3 19.1 16.8 12 9.5 7 5.3 199 19.7 21.5 18.2 13.3 10.8 8.3 6.6 Table 11 - Floor Model Specifications and Dimensions R 3 4.3 S T U V W X Y 2.5 4 5 6.5 7.3 9.5 13.5 System Safeties – The boiler is provided with many safety features to ensure reliable and safe operation. Each safety is connected to the boiler control. The boiler will alert the user if an unsafe condition occurs and needs to be addressed.
Figure 5 - Components Number Component Description Number Component Description Number Component Description 1 Air Vent 11 CH Return Adapter 21 Control Panel 2 Relief Valve Adapter 12 CH Pressure Gauge 22 Heat Exchanger 3 Air / Gas Mixing Pipe 13 DHW Outlet Adapter 23 Ignition Transformer 4 Gas Valve 14 Gas Inlet Adapter 24 Flame Detecting Sensor 5 Internal Storage Tank 15 DHW Inlet Adapter with Filter and Flow Restrictor 25 BLDC Fan 6 Main PCB 16 Condensate Adapt
! WARNING This boiler is too heavy for one person to lift. It is highly recommended to install the boiler with two people. Use caution as to not drop the boiler, which could damage the boiler and cause property damage and/or severe personal injury. Verify that the boiler is properly and securely mounted before leaving unsupervised. Failure to comply with the above and properly mount the boiler could result in substantial property damage, severe personal injury, or death.
Figure 8 - Water Pressure vs. Flow through the Restrictors - 140 Models Figure 9 - Water Pressure vs. Flow through the Restrictors - 199 Models Part 4 - Water Piping ! WARNING Failure to follow the instructions in this section WILL VOID the warranty and may result in property damage, severe personal injury, or death. CAUTION Do not apply a torch within 12” of the boiler. If sweat connections are used, sweat tubing to the adapter before fitting adapter to the water connections on the boiler.
• Pipe material must be suitable to meet local codes and industry standards. • The pipe must be cleaned and without blemish before any connections are made. • The size of the DHW pipes should be 3/4” diameter, and the CH pipes should be 1” diameter. • Isolation (shutoff valves) should be used on both the CH and DHW loops to ease future servicing. • All piping should be insulated. It is recommended to install a sweat shut-off valve and a union in the return and supply piping to ease future servicing.
E. Applications Figure 10 - Piping Symbol Legend whl-648 Rev. 001 Rel. 000 Date 4.11.
Figure 11 - Primary / Secondary Piping with Zone Valves - DHW Priority and Outdoor Reset NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
Figure 12 - Primary / Secondary Piping with Pumps - DHW Priority and Outdoor Reset NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
Figure 13 - Primary / Secondary Piping with Pumps - DHW Priority and Outdoor Reset with Recirculation NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
Figure 14 - Primary / Secondary Piping with Pumps - DHW Priority and Outdoor Reset with Recirculation and Boiler Primary Pump NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
Figure 15 - Primary / Secondary Piping with Pumps - DHW Priority and Outdoor Reset - Floor Model NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
Figure 16 - Primary / Secondary Piping with Pumps - DHW Priority and Outdoor Reset with Recirculation and Boiler Primary Pump - Floor Model NOTES: 1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 4.
F. CH and DHW Pressure Relief Valves An external pressure relief valve must be installed on this boiler for both the CH and DHW loops. When installing, observe the following guidelines. Pressure relief valves must be installed as close to the boiler as possible. No other valves should be placed between the pressure relief valve and the boiler. Failure to comply with these guidelines can result in substantial property damage, personal injury, or death.
Part 5 - Venting ! DANGER ! DANGER The boiler must be vented as detailed in this section. Ensure exhaust vent and intake piping complies with these instructions regarding vent system. Inspect finished exhaust vent and intake piping thoroughly to ensure all joints are well secured, airtight, and comply with all applicable code requirements, as well as the instructions provided in this manual. Failure to properly install the vent system will result in severe personal injury or death. A.
B.
D. Exhaust Vent and Intake Pipe Location INSIDE CORNER DETAIL G E A H E B B E OPERABLE C FIXED CLOSED FIXED CLOSED D E E I E OPERABLE F M I B E E K E I E B J A K I B L LP-179-CC 03/28/17 E Exhaust Vent Terminal I Intake Pipe Terminal Area Where Intake Terminal Is Not Permitted Figure 18 - Exit Terminals for Direct Vent Systems - ANSI Z223.1 / NFPA 54 for US and CAN/CSA B149.
E. Exhaust Vent and Intake Pipe Sizing 1. The exhaust vent and intake pipe size is 3”. 2. The total equivalent length of 2” exhaust vent and intake pipe should not exceed fifty (50) feet; 3” exhaust vent and intake pipe should not exceed one hundred (100) feet. a. The equivalent length of elbows, tees, and other fittings are listed in the Friction Loss Table. b.
the vent pipe. 10. The exhaust vent must terminate where vapors cannot make accidental contact with people or pets, or damage shrubs or plants. 11. In vacant chimney applications, install and seal a rain cap over existing chimney openings. 12. All piping must be fully supported. Use pipe hangers at a minimum of 4 foot intervals to prevent sagging of the pipe where condensate may form. 13. Do not use the boiler to support any piping. 14.
Two Pipe Sidewall Venting with Elbow (Intake) and Coupling (Exhaust) EXTERIOR WALL Two Pipe Roof Venting with Elbow (Intake) and Coupling (Exhaust) 1" MIN. 12" MIN.
EXHAUST A AIR INTAKE B FRONT VIEW 24.00 C Exhaust D EXHAUST Intake E AIR INTAKE LP-325-PP 03/31/11 SIDE VIEW F LP-325-OO 02/04/15 Figure 23 - Horizontal (Snorkel) Venting NOTES: A. For every 1” of overhang, the exhaust vent must be located 1” vertical below overhang (overhang means top of building structure and not two adjacent walls [corner of building]). B. Typical installations require 12” minimum separation between bottom of exhaust outlet and top of air intake. C.
2. Venting Through an Existing System This appliance may be vented through an existing unused vent system. The inner diameter of the existing vent system is utilized for the combustion air source. Two methods have been approved for such venting: Concentric Venting Through an Existing System and Venting as a Chase. ! DANGER Do not install the appliance into a common existing vent with any other appliance.
3. Power Venting, Indoor Combustion Air in Confined or Unconfined Space This appliance requires fresh, uncontaminated air for safe operation with doors, are considered part of the space. and must be installed in a mechanical room where there is adequate Confined space is space with volume less than 50 cubic feet per combustion and ventilating air. NOTE: To prevent combustion air 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of contamination, see Table 7.
Part 6 - Installing the Condensate Drain CAUTION This condensing high efficiency boiler has a condensate removal system. Condensate is water vapor derived from combustion products, similar to that produced by an automobile when it is initially started. It is very important that the condensate line is sloped down away from the boiler and to a suitable drain. The condensate line must remain unobstructed.
Part 7 - Connecting Electrical Service ! WARNING Install wiring and electrically ground boiler in accordance with the authority having jurisdiction or, in the absence of such an authority, follow the National Electrical Code, NFPA 70, and/or CSA C22.1 Electrical Code-Part 1 in Canada.
Figure 33 - Electrical Wiring Diagram whl-648 Rev. 001 Rel. 000 Date 4.11.
Figure 34 - Ladder Diagram whl-648 Rev. 001 Rel. 000 Date 4.11.
Connector No.
Connector No. of Location Pin 1 8 2 9 3 10 CN7 LWD1140-14 4 11 5 12 6 13 7 14 CN14 SMW250-09 CN3 SMW250-06 CN5 SMW250-10 Description Board Silk F.S Flame Sensor OP.S Operating Water Temperature Sensor DH.S DHW Temperature Sensor I.S NOT USED BG.S Exhaust Temperature Sensor ST.S NOT USED SP.
Part 8 - Gas Connections ! WARNING FIRE AND/OR EXPLOSION HAZARD To avoid serious injury or death, the gas line installation and the gas line inlet pressure test must be done by a licensed professional. Ensure the gas on which the boiler will operate is the same type specified on the rating plate (natural gas or LP gas). This boiler must be converted into propane operation unless specifically manufactured for use with propane. Follow Gas Conversion Manual instructions (separate document).
! WARNING C. Additional Precaution for Excess Flow Valve (EFV) If an excess flow valve (EFV) is in the gas line, check the manufacturer’s minimum and maximum flow capacity ratings. An improperly sized EFV will not allow for a full flow of gas to the boiler and will cause the boiler to malfunction. See Figure 38. It is required to use a calibrated combustion analyzer to verify final adjustment according to the combustion chart (Table 25).
Part 9 - Controls A. Control and Display Overviews Figure 40 - Control Panel Detail Figure 41 - LCD Display The LCD display also features a backlit lamp that will illuminate: • When a user action is detected (a button is pressed) • The display has timed out for approximately 2 minutes After start-up, the display appears as follows. B. Start-Up Sequence After the boiler is powered ON, the LCD display shows a sequence of information.
C. Changing the DHW Set-Point Press the button when the display panel is powered ON to change the DHW Set-Point. The display will appear as follows. Figure 44 - CH Set-Point Screens Factory CH Set-Point is 180oF (82oC). Initial CH Set-Point range is 86 – 180oF (30 – 82oC). Turn the dial counterclockwise to lower and clockwise to raise the CH set-point. After changing the temperature, press the button to save the set-point.
H. Status Display Status Display will activate when button is pressed and held for five seconds at Standby Mode when the display panel is powered ON. Figure 46 - Status Display Screens Display (Main Menu) Display (Sub Menu) Detail Description O:ot Outdoor Temperature Current Outdoor Sensor Temperature (When --- is displayed, outdoor sensor is not connected.
I. Installer Mode Installer Mode will activate when button is pressed and held for five seconds while the boiler display is powered Off. Figure 47 - Installer Mode Screens Display Default Detail 1:EH E0.00 Error history up to 10 Check ten most recent Error Codes (E0 - E9) 2:cE OFF Clear Error History Select “ON” to Clear Error History.
Display Default Detail Description 17:cL 86F Minimum Supply Temperature Sets the minimum design supply temperature based on the maximum outdoor design temperature. Minimum supply temperature must be set 9oF above the maximum supply temperature.
See Figure 48 to set your Outdoor Reset Curve. To check the CH Target Temperature while using Outdoor Temperature Mode, press the display panel is powered on. button while the boiler is operational and the Figure 48 - Outdoor Reset Curve - See Installer Mode for Curve Setting Descriptions K. 0-10 Volt Input 1. A signal from a building management system may be connected to the boiler to enable remote control. This signal should be a 0-10 volt positive-going DC signal.
Part 10 - Troubleshooting A. Error Code When the boiler encounters an error, the display will flash “Er” followed by a numerical code. The boiler shall enter a soft lockout condition if the error is such that it can return to normal operation once the condition relieves itself (overheat conditions, NTC open or shorts, etc.). The boiler shall enter a hard lockout if the condition indicates something more serious (flame, ignition, condensate line, etc.
Error Code Error Code Description Possible Remedies Er:31 Return Temperature Sensor Open or Short This Error Code will go away when operating temperature decreases. If Error happens again: 1. Check return temperature sensor. Ensure connections are secure. 2. Check return sensor resistance. If resistance is zero, replace the sensor. 3. If the problem persists, replace the main control. Er:32 DHW Sensor Open or Short This Error Code will go away when outlet DHW temperature decreases.
Error Code Error Code Description Er:68 Mixing Valve Operation Error (Mixing Valve Stuck in Initial Position) This Error Code will go away when the condition is remedied. If Error happens again: 1. Turn power OFF and ON at the main power switch internal to the boiler. 2. Check wiring connections to mixing valve. Ensure all are secure. 3. Replace mixing valve. 4. If the problem persists, replace the main control.
B. Error Tree Analysis 1. Flame Detection Figure 50 - Flame Detection Error Analysis Tree 2. Air Pressure Switch / Burner Overheat Limit / Condensate Block Switch Figure 51 - APS / Burner Overheat Limit / Condensate Block Switch Error Analysis Tree 3. DHW / Operating Temperature / CH Overheat / Exhaust Sensors Figure 52 - DHW / Operating Temperature / CH Overheat / Exhaust Sensors Error Analysis Tree whl-648 Rev. 001 Rel. 000 Date 4.11.
C. Suggested Corrective Actions Problem Possible Causes Possible Remedies No electrical power to the boiler 1. Is the plug on the power supply cord unplugged from the electrical outlet? 2. Is electrical panel’s 10 Amp circuit breaker tripped? 3. Is the fuse on the circuit board good? 4. Is there a power outage to the home? 1. Reset the plug. 2. Reset the circuit breaker. 3. If the display panel is blank, unplug the unit or contact a qualified service technician. 4. Contact the power company.
Display Condition Diagnostic Possible Corrective Actions Ensure service switch and/or circuit Turn on service switch or circuit breaker to breaker to boiler is turned ON power boiler Troubleshoot and correct the power supply to the manual switch Is there 120V at the service switch Nothing appears on the display control panel and no other boiler components are operating Control is not receiving 120V power Is the ON/OFF switch inside the boiler Turn ON the manual power switch inside the cabinet is t
Part 11 - Start-Up CAUTION Thoroughly clean and flush any system that has used glycol before installing the boiler. Provide the customer with a material safety data sheet (MSDS) on the fluid used. A. Check / Control Water Chemistry CAUTION Chemical imbalance of the water supply may affect efficiency and cause severe damage to the boiler and associated equipment. It is important that the water chemistry on both the domestic hot water and central heating sides are checked before installing the boiler.
C. Freeze Protection (When Used) ! WARNING NEVER use automotive or standard glycol antifreeze. Do not use ethylene glycol made for hydronic systems. Use only freezeprotection fluids certified by fluid manufacturer as suitable for use with stainless steel boilers, verified in the fluid manufacturer’s literature. Thoroughly clean and flush any system that has used glycol before installing the new boiler. Provide the boiler owner with a material safety data sheet (MSDS) on the fluid used. 1.
from the internal pump: 1. Use a flat head screwdriver and turn the pump bleed screw one (1) turn counterclockwise. 2. When water comes out the pump has been bled. 3. Turn the screwdriver clockwise and reseat the bleed screw. Figure 54 - Bleeding the Internal Pump Run pumps as required to help bleed out all entrapped air. Some good indicators that air is removed include the absence of gurgling noises in the pipes and pump operation becoming very quiet.
Part 12 - Installation Checklist Before Installing Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Is there enough space to ensure proper installation? Does installation location allow for proper service clearances? Are water and gas lines properly sized and set at proper pressures for the installation? Is boiler location as near the exhaust vent / intake pipe terminations as possible? Have combustible materials been cleared from the installation location? Is there a drain close
Start-Up, Adjust, and Test Yes No Yes No Has the boiler been started? If necessary, has the boiler gas valve been adjusted? Has the installation been customized per installation location requirements? Have all customized system parameters been tested? Has proper boiler operation been confirmed? Burner Flame Has the burner flame been checked? Have combustion values been verified with a calibrated combustion analyzer? If the flame does not appear normal, it may need to be cleaned by a qualified servic
• If you notice flue gas leaking from the opening, this indicates a dry condensate drain trap. If problem persists, contact a qualified service technician to inspect the boiler and condensate line and refill the condensate trap. • If applicable, check the condensate neutralizer and ensure it is full of condensate neutralizing marble chips. Check the Air Vent Loosen cap one counterclockwise turn to allow air vent to operate. See Figure 55.
pump outlet and the cold water inlet line to valve V4. Connect the other hose (D2) to the circulation pump inlet and place the free end in the bucket. 10. Turn on the gas valve. Turn on electrical power to the boiler and press the Power button to turn the boiler on. 11. Reinsert the filter and ensure the filter cap is securely tightened. 12. Connect electrical power to the boiler.
6. Fill the condensate trap with fresh water prior to reassembly on Maintenance Report the boiler. 7. Install the condensate trap on the condensate hose from the heat exchanger. Use the hose clamp to secure the trap. Attach the In unusually dirty or dusty conditions, care must be taken to keep clear plastic hose onto the hose barb. Reinstall the condensate hose boiler cabinet door in place at all times. Failure to do so VOIDS clamp to detach the condensate trap from the drain tube.
INSPECTION ACTIVITIES DATE LAST COMPLETED PIPING 1st YEAR Near boiler piping Check boiler and system piping for any sign of leakage. Leaking pipes could cause property damage. Make sure all piping is properly supported. Flush tankless heat exchanger annually (more in hard water conditions). See User’s Information manual for instructions. Vent Check condition of all vent pipes and joints. Ensure all vent piping is properly supported. Check for obstructions exhaust and intake termination points.
Part 14 - Moving Adapters from Left to Right (Floor Models) 1. It is recommended to do this procedure before the appliance is installed. However, if appliance is installed, ensure the water and gas are shut off and all water is drained from the appliance. Disconnect the water, gas, and condensate lines from the appliance. 6. Use a Phillips Head screwdriver to secure the removed right side panel to the left side of the appliance stand with the eight (8) screws removed in Step 3. 7.
16 15 B-6 15 16 17 15-1 B-3 B-10 15-2 B-10 15-4 16-1 15-3 15-5 15-6 32 16-2 15-7 15-8 20 B-5 18 19 B-3 33 B-5 28 B-12 22 B-6 34 21 B-6 B-5 23 24 B-3 30 B-6 25 B-13 31 B-3 26 B-8 B-3 27 29 Figure 61 - Cabinet Replacement Parts - 140 Floor and Wall Mount Models NUMBER DESCRIPTION PART NUMBER NUMBER DESCRIPTION PART NUMBER 15 Exhaust Duct Assembly 7855P-002 21 Ignition Transformer 7855P-007 15-1 Exhaust/Intake Duct Clamps (Φ100) 7855P-332 22 Control Board
36-1 36-1 36 36-2 40 42-1 36-3 36-2 36-3 41 42 36-3 36-3 37-1 42-2 B-16 58-1 55 36-3 55-1 56 50-1 50 36-3 49 57-2 45 51 57 46 37-2 52 37-1 B-4 53 42-2 48 46-1 51 37-1 37-2 B-3 B-4 44 37-1 59 B-4 46-1 57-1 58-2 38 42-2 55-1 B-16 37-2 43 42-1 58 37 39 B-4 47 52 B-4 54 Figure 62 - Water Piping Replacement Parts - 140 Floor and Wall Mount Models NUMBER DESCRIPTION PART NUMBER NUMBER DESCRIPTION PART NUMBER 36 DHW Outlet Pipe 7855P-242 47 DHW
For 140kBTU Appliances with Serial Numbers Before 051818SA301041 B-3 66 67 64-1 61 B-1 68-1 64-2 N-1 62-1 64-3 62 63 B-6 60 64-1 64-4 B-2 69 68 64-5 64-6 B-12 64-7 64-8 64-9 68-2 75 64 70 64-10 65 71 72 B-11 73 B-8 74-2 NOTE: Parts 64-1, 64-9, and 64-10 are not available for field replacement.
For 140kBTU Appliances with Serial Number 051818SA301041 and After Figure 64 - Heat Exchanger Replacement Parts - 140 Floor and Wall Mount Models NUMBER DESCRIPTION PART NUMBER NUMBER DESCRIPTION PART NUMBER 60 Exhaust Pipe Assembly 7855P-237 67 Air Vent 7855P-063 61 Storage Tank Clamp 7855P-297 68 CH Supply Upper Pipe 7855P-239 7855P-349 62 Exhaust Temperature Sensor Clip 62-1 Exhaust Temperature Sensor O-Ring 63 Exhaust Temperature Sensor 64 Heat Exchanger Assembly 7855P-0
79 N-2 79-1 83 79-2 79-3 84 85 B-14 87 86 78 80 88 B-7 82 89 81 90 B-5 B-2 87 90 91 90-1 90-2 90-3 90-2 90-5 90-4 B-9 B-4 87 92 B-5 Figure 65 - Combustion System Replacement Parts - 140 Floor and Wall Mount Models NUMBER DESCRIPTION PART NUMBER NUMBER DESCRIPTION PART NUMBER 78 Burner Inlet Channel Gasket 7855P-370 86 Mixer Clamp 7855P-376 79 Burner Inlet Channel (with Damper) 7855P-367 87 1/2” Gas Pipe Gasket 7855P-221 79-1 Air Damper 4G 7855P-368 88 Gas Pi
Figure 66 - Cabinet Replacement Parts - 199 Floor and Wall Mount Models NUMBER DESCRIPTION PART NUMBER NUMBER DESCRIPTION PART NUMBER 15 Exhaust Duct Assembly 7855P-002 23 Display Panel Bracket 7855P-413 15-1 Exhaust/Intake Duct Clamps (Φ100) 7855P-332 24 Ignition Transformer 7850P-271 15-2 Exhaust/Intake Gaskets 7850P-210 24-1 Ignition Transformer Bracket 7855P-441 15-3 Exhaust Duct 7855P-333 25 Control Board 7855P-268 15-4 Combustion Analyzer Port Plug O-Ring 7855P-334
Figure 67 - Heat Exchanger Replacement Parts - 199 Floor and Wall Mount Models NUMBER DESCRIPTION PART NUMBER NUMBER DESCRIPTION PART NUMBER 38 DHW Outlet Pipe 7855P-275 49 DHW Inlet Block Cap 7855P-283 38-1 3/4” Pipe Gasket 7855P-073 50 DHW Inlet Adapter 7855P-203 38-2 P18 O-Ring 7855P-047 51 CH Block Cap 7855P-283 38-3 1/2” Pipe Clip 7855P-246 52 CH Return Block with Filter 7855P-248 39 DHW Inner Block 7855P-251 52-1 P22 O-Ring 7855P-276 39-1 P22A O-Ring 7850P-26
For 199kBTU Appliances with Serial Numbers Before 051418SAB00161 NOTE: Parts 76-1, 76-8, and 76-9 are not available for field replacement.
For 199kBTU Appliances with Serial Number 051418SAB00161 and After Figure 69 - Heat Exchanger Replacement Parts - 199 Floor and Wall Mount Models NUMBER DESCRIPTION PART NUMBER NUMBER DESCRIPTION PART NUMBER 74 Flame Sensor 7855P-031 75 Flame Sensor Cover 7855P-357 Heat Exchanger Assembly 7865P-029 63 Exhaust Temperature Sensor 63-1 Exhaust Temperature Sensor O-Ring 64 Exhaust Temperature Sensor Clip 7855P-349 76 65 Exhaust Pipe Assembly 7855P-415 76-2 Burner Body 7855P-606
Figure 70 - Combustion System Replacement Parts - 199 Floor and Wall Mount Models NUMBER DESCRIPTION PART NUMBER NUMBER DESCRIPTION PART NUMBER 78 Burner Inlet Channel (with Damper) 7855P-424 86 Air Intake Hose (Bottom Clamp) 7855P-429 79 Air Damper 19G 7855P-618 87 APS Hose Fitting 7855P-375 80 Air Damper Guide 7855P-369 88 Gas Valve Assembly 7855P-431 81 Fan Outlet Gasket 7855P-425 88-1 Gas Valve Outlet Adapter 7855P-232 82 Burner Inlet Channel Gasket 7855P-426 88-2
Figure 71 - Floor Model Replacement Parts Item # Description 140 Model 199 Model Item # Description 1 Base Assembly, Floor Stand 7865P-001 7865P-002 10 Locknut - Electrical - 1/2” 7700P-002 2 Screw M5 x 12MM 7865P-023 11 Barb Fitting 1/2” 7100P-044 3 Anchor and Wall Bracket 7850P-084 12 Screw M4 x 10MM 7855P-390 4 Screw M6 x 12MM (Not Shown) 7865P-024 13 3/4” ID SS Flex - 22” Long 7865P-017 5 Right Side Panel w/ Labels 14 3/4” ID SS Flex - 24” Long 7865P-018 7865P-010
Limited Warranty for WBRC Appliances Westinghouse warrants this appliance and its components to be free from defects in material and workmanship according to the following terms, conditions, and time periods. UNLESS OTHERWISE NOTED THESE WARRANTIES COMMENCE ON THE DATE OF INSTALLATION. This limited warranty is only available to the original consumer purchaser (herinafter “Owner”) of this appliance, and is nontransferable.
18. Failures (leaks) caused by operating the appliance in a corrosive or contaminated atmosphere. 19. Damages, malfunctions, or failures caused by operating an empty or partially empty appliance (“dry firing”), or failures caused by operating the appliance when it is not supplied with water, free to circulate at all times. 20. Any damage or failure of the appliance due to the accumulation of solid materials or lime deposits. 21. Any damage or failure resulting from improper water chemistry.
Notes whl-648 Rev. 001 Rel. 000 Date 4.11.
This Page Intentionally Left Blank whl-648 Rev. 001 Rel. 000 Date 4.11.
This Page Intentionally Left Blank whl-648 Rev. 001 Rel. 000 Date 4.11.
Customer Installation Record Form The following form should be completed by the installer for you to keep as a record of the installation in case of a warranty claim. After reading the important notes at the bottom of the page, please also sign this document.