Installation Manual

67
WHL-016 REV. 3.4.15
Function 24
Cascade Rotation
CASCADE ROTATION
48 HOURS 24
Sets the amount of hours before the first boiler in the cascade firing rotation will be changed. NOTE: If this parameter is
set to 0, the firing order of the boilers will not rotate. Default: 48 hours (Range: 0 240 hours).
Function 25
Cascade DHW Mode
NOT USED
NOT USED 25
Not used on this product.
Function 26
System Freeze Protect
SYS FREEZE PROT
PROTECT OFF 26
NOTE: This parameter is only present if the boiler is a cascade master. Allows the user to set the freeze protection
when a system pump is used. Factory Default: OFF. Selection of temperature activates freeze protection. (Range:
OFF, -40
o
F 104
o
F).
Function 27
Error System Sensor
ERROR SYSTEM SENS
ON 27
Allows the user to set the control to display an error message if the system sensor is open or shorted. NOTE: This
error does not stop the boiler (or boilers) from running. Factory Default: ON (Range: ON / OFF).
Function 28
Freeze Protection
FREEZE PROTECTION
ON 28
Allows the user to set freeze protection on the boiler. Factory Default: ON (Range: ON / OFF).
Function 29
DHW Modulation Mode
DHW MODULATE MODE
NORMAL MOD 29
This parameter controls how the boiler modulates for a DHW demand. In NORMAL MOD mode, the boiler will
modulate down from high fire when there is a DHW demand. In LOW MOD mode, the boiler will modulate up from low
fire when there is a DHW demand. This mode is useful to minimize short cycling when a large boiler and small indirect
tank are used together. Factory Default: NORMAL MOD (Range: NORMAL MOD / LOW MOD).
Function 30
Extra Boiler Mode
EXTRA BOILER MODE
OFF 30
Allows for a non Westinghouse boiler to be controlled when the cascade output has risen above the percent of the
cascade firing rate set in this parameter. Factory Default: Off (Range: 50% - 100%).
Function 31
System Sensor Mode
SYSTEM SENSOR MODE
OFF 31
Suppresses the ‘NO FOLLOWER’ message on the display if the boiler is used as a cascade master boiler with no
follower boilers connected. Factory Default: OFF (Range: ON / OFF).
Function 32
Service Schedule
SERVICE SCHEDULE
OFF 32
Allows the user to select a service date or time based on the boiler run hours to program the boiler maintenance
schedule. Factory Default: OFF (Range: Date or Run Hours). NOTE: Without setting this function, Functions
33/34/35/36 will not display.
Function 37
Modbus Mode
MODBUS MODE OFF
37
Enables Modbus Mode on the appliance. Factory Default: OFF (Range: OFF, ON, AUTO). NOTE: Turning Modbus
Mode “ON” will open a number of additional parameters to customize Modbus installation. See Modbus Instructions (lp-
372) for details. NOTE: Turning this Mode “ON” without a connected and powered Modbus communication adapter
(p/n 7350P-629) will result in improper appliance operation. Service calls associated with this ARE NOT covered by
warranty.
Table 21 System Setting Menu Screens
NOTE: For the following functions, you must have your maintenance function turned on. To change, press ENTER. The left most digit
will begin to blink. Use the up or down ▼ arrows to change the digit. Use the arrow keys to switch between digits. When you’ve
made your selection, press ENTER again.
SCREEN
DESCRIPTION
Function 33
Year
SERVICE SCHEDULE
YEAR 00/00/2000 33
Allows the user to set the year of the next service reminder.
Hours
SERVICE SCHEDULE
10000’s 000000h 33
Allows the user to set the left two digits of the amount of run hours before next service reminder.
Function 34
Month
SERVICE SCHEDULE
MONTH 00/00/2000 34
If the date function was selected, this function allows the user to program the month. If you selected the run hour
function, you will need to program 10,000 hours, if required.
Hours
SERVICE SCHEDULE
10000’s 000000 34
Allows the user to set the two middle digits of the amount of run hours for the next service reminder.
Function 35
Day
SERVICE SCHEDULE
DAY 00/00/2000 35
Allows the user to set the day of next service reminder.
Hours
SERVICE SCHEDULE
10000’s 000000 35
Allows the user to set the 2 right digits of the amount of run hours for the next service reminder.
Function 36
Telephone
TELEPHONE #
000 000 0000 36
Allows the user to input a telephone number that will be displayed when maintenance is required.
Table 22 Maintenance Reminder Function Screens