Instructions / Assembly

34
WHL-590 REV. 7.27.16
Figure 26 Water Heater with Storage Tank and Recirculation NOTE: There is a Built-In Flow Check in the Internal
Recirculation Pump Loop
NOTES:
1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow
preventer and the cold water inlet.
3. All circulators should have an integral flow check.
4. Drains and check valve between water heater and piping will assist in purging air from system.
5. These drawings are meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by
local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.
6. Mixing valve application is optional, but recommended to help prevent scalding.
7. Always shut off power to the water heater or isolate the heater from the system if ANY plumbing work is to be done. Running the
water heater without water will result in dry-firing.
8. When using unit with storage tank, the setpoint of the water heater needs to be at least 5
o
F higher than the setpoint of the Aquastat
on the tank.
NOTE: These drawings are meant to show system piping concept only. Installer is responsible for all equipment and detailing required
by local codes.