Instructions / Assembly

26
WHL-004 REV. 5.26.17
2. Direct Vent, Optional Horizontal and Vertical Vent Kits
Figure 11 Direct Vent, Vent Terminations (With Optional Kits)
All vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of ¼” per foot back to the appliance to
allow drainage of condensate. When placing support brackets on vent piping, the first bracket must be within 1 foot of the appliance and
the balance at 4 foot intervals on the vent pipe. Appliance venting must be readily accessible for visual inspection for the first three feet
from the appliance.
3. Screen Installation
After connecting the intake air and exhaust vent pipes, it is required to install the included screens into the exhaust vent and intake pipe
terminations to prevent damages to the unit due to blockages. See Figure 12 for installation detail.
Figure 12 - Screen Installation - NOTE: Vent termination elbow is meant to be installed open end facing the ground.
Orientation in Figure 12 is meant to demonstrate proper Vent Screen installation ONLY.
SAFETY INSTRUCTIONS
Do not connect any other appliance vents to the water heater exhaust vent or intake pipes.