User manual

INSTALLATION
1. Using a spirit level mark a vertical centre line on the wall where the hood is to be positioned, and a horizontal line
at the hood base position. (See Figure 4 for relevant model)
NOTE. The height of the underside of the hood body must be a minimum of 600mm* to a maximum height of 800mm.
* If the instructions of the hob specify a greater distance than the minimum above, then that shall be the minimum
height for installation.
2. Mark the location for the flue cover wall mounting brackets and rangehood mounting points and anti-tilt fixing
points above the hood base using the hood base as a reference point
Fig. 6
WRC613S WRC913S
A
B
600 mm
440 mm
900 mm
550 mm
Max. 1160 mm
An lt fixing point
Range hood
mounng points
Flue cover wall
mounng brackets
Min. 600 mm*
Max. 800 mm
ceiling
130 mm
250 mm
230mm
250 mm
A
587 mm
307 mm
51 mm
B
Top of hob
7