Content Section 1 Overview 1.1 1.2 ...................................................................................................................................................... 1-1 SK-4224 Description ................................................................................................................................ 1-1 How to Contact Silent Knight ..................................................................................................................
Model SK-4224 Fire Control Panel Installation/Operation Manual 4.6 4.7 Door Release Wiring ................................................................................................................................ 4-8 Optional Accessories Installation ............................................................................................................. 4-9 4.7.1 Installing the Serial Driver Board (Model SK-2884) .......................................................................
Section 1 Overview 1.1 SK-4224 Description The Model SK-4224 is a four zone, 24-volt fire control panel having the following features: • Zone inputs can be configured as: Four Class B zones Or Two Class A zones • 2.5 amp power supply • Two notification circuits rated at 2.5 amp max. • Dedicated alarm and trouble relays • Auxiliary power output (.5 amp max.) for powering special applications, such as door holders.
Model SK-4224 Fire Control Panel Installation/Operation Manual 1-2 151068
Section 2 Agency Requirements 2.1 FCC Warning This device has been verified to comply with FCC Rules Part 15. Operation is subject to the two following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. 2.2 Underwriters Laboratories (UL) The SK-4224 is UL listed as a control unit for use in NFPA 72 systems.
Model SK-4224 Fire Control Panel Installation/Operation Manual 2-2 151068
Section 3 Before You Begin Installing 3.
Model SK-4224 Fire Control Panel Installation/Operation Manual 3.2 Optional Accessories Table 3-2 is a list of optional accessories that can be used with the Model SK-4224 Fire Control Panel. Table 3-2: Option Accessories for the SK-4224 Model Number * 3-2 Name Description SK-2884 Serial Driver Board Used to interface all SK-4224expansion device to the SK4224 panel. Supports1 Dialer (Model 2104) and any combination of 4 LED Annunciators (Model 2865) or I/O Modules (Model 2880).
Before You Begin Installing 3.3 SK-4224 Board Layout Figure 3-1 shows the SK-4224 circuit board including location of terminals, connectors, dip switches, and LEDs.
Model SK-4224 Fire Control Panel Installation/Operation Manual 3.4 Electrical Specifications Table 3-3: Electrical Specifications Circuit Rating Primary AC *120 Vrms at 60 Hz, or 230 Vrms at 50 Hz @ 1.5 Amps Total External DC Load 2.5A @ 24 VDC +24V Auxiliary Power 19.8 V to 28.0 V, 0.5 A max. Trouble & Alarm Relays 2.5 A @ 30 VDC resistive Notification Appliance Power 19.8 V to 28.0 V, 2.5 A max. Smoke Detector Power 19.8 V to 28.0 V, 1.0 A max. Battery Charging Voltage 27.0 - 27.
Before You Begin Installing 3.6 Mounting the SK-4224 Read the environmental specifications in Section 3.5 before mounting the cabinet. The panel should be accessible to main drop wiring runs. It should be mounted as close to the center of the building as possible and located within a secured area, but should be accessible for testing and service. End-users responsible for maintaining the panel should be able to hear alarms and troubles.
Model SK-4224 Fire Control Panel Installation/Operation Manual 3.7 Assembly The components listed in Table 3-1 are all packed with in the cabinet and require some assembly. Follow these steps to assemble the cabinets inside the cabinet: 1. Remove keys from small manila envelope taped to the top of the cabinet. 2. Unlock the cabinet door. 3. Remove the packing material and the SK-4224 components. 4. Snap the bezel into the opening in the front of the cabinet. See Figure 3-3.
Before You Begin Installing 3.8 Wiring Specifications Induced noise (transfer of electrical energy from one wire to another) can cause false alarms or interfere with control panel operation in other ways. To avoid induced noise, follow these guidelines: • Isolate input wiring from high current output and power wiring. Do not pull one multiconductor cable for the entire panel.
Model SK-4224 Fire Control Panel Installation/Operation Manual 3.9 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs for your installation. 3.9.1 Worksheet Requirements The following steps must be taken when determining SK-4224 current draw and standby battery requirements. Filling in the Current Draw Worksheet, Table 3-6 (Section 3.9.3) 1.
Before You Begin Installing 3.9.3 Current Draw Worksheet Use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.
Model SK-4224 Fire Control Panel Installation/Operation Manual 3-10 151068
Section 4 Hardware Installation 4.1 AC Power At installation, connect the transformer AC inputs to the AC power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection. The AC inputs are rated as 120 VAC, 60 Hz (for transformer P/N 115061) or 230 VAC,50 Hz (for transformer P/N 115031). See Table 3-1 for more information.
Model SK-4224 Fire Control Panel Installation/Operation Manual 4.2 Battery Connection The SK-4224 battery charge capacity is 7.0 AH. Use two 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Table 3-6). Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. Note: The SK-4224 cabinet supports two 7.0 AH batteries.
Hardware Installation 4.3 4.3.1 Initiation Circuit Installation Contact Wiring Wire normally open contacts as shown in Figure 4-3. This is the type of wiring that would typically be used for water flow switches, heat detectors and other normally open devices. Figure 4-3 N.O. Contact Wiring 4.3.2 Two-Wire Smoke Detector Wiring Figure 4-4 shows how to connect two-wire smoke detectors to the SK-4224 loops. The figure uses Silent Knight's SLK-24F with HSB-224 base as an example.
Model SK-4224 Fire Control Panel Installation/Operation Manual 4.3.3 Class A Smoke Detector Installation Figure 4-5 illustrates how to connect a UL listed smoke detector to the SK-4224 in a Class A configuration. Refer to the Appendix for a list of compatible devices. Information on selecting zone configuration options is in Section 6.
Hardware Installation 4.3.4 Four-Wire Smoke Detector Figure 4-6 shows how to connect four-wire smoke detectors to the SK-4224 loops. The figure uses Silent Knight's SLK-24F with HSC-4R base as an example. You can use any UL listed device. Refer to the Appendix for a list of compatible devices. Information on selecting zone configuration options is in Section 6.
Model SK-4224 Fire Control Panel Installation/Operation Manual 4.3.5 Notification Circuit Installation Notification appliances used with the SK-4224 must be UL listed for compatibility with the SK-4224. Refer to the list in the Appendix at the end of this manual for a list of compatible devices. For proper operation, you must use polarized notification devices with a model 7628 4.7k ohm end-of-line (EOL) resistor on each loop. Select ANSI output pattern, if desired.
Hardware Installation 4.3.6 Class A Notification Circuit Installation For proper operation, you must use polarized notification devices. Select ANSI output pattern, if desired. Output is configured as steady (continuous sound) at the factory. See Section 6 for information on changing the pattern. Figure 4-8 Class A Notification Circuit 4.4 Alarm and Trouble Relays The SK-4224 has built-in relays for alarm and trouble. The alarm relay is energized during any alarm condition.
Model SK-4224 Fire Control Panel Installation/Operation Manual 4.6 Door Release Wiring Figure 4-9 shows how to configure a door release using an ESL DH series door holder.
Hardware Installation 4.7 Optional Accessories Installation This section describes how to install the optional accessories compatible with the SK-4224 control panel. 4.7.1 Installing the Serial Driver Board (Model SK-2884) The SK-2884 is required if the installation uses any SK-4224 expansion devices such as Model SKC-2880 (I/O Module), Model SK-2865 (LED Annunciator), or Model 2104 (Dialer Board). The SK-2884 interfaces all the expansion devices to the SK-4224 control panel.
Model SK-4224 Fire Control Panel Installation/Operation Manual Wiring the SK-2884 to an Expansion Device The SK-2884 uses a three wire connection to all of the SK-4224 compatible expansion devices (see Table 3-2). Connect all the expansion devices to the SK-2884 as follows: Table 4-1: SK-2884 Wiring Connections 4.7.
Hardware Installation 3. Terminate the wiring as shown in Figure 4-11. See also Table 4-2.
Model SK-4224 Fire Control Panel Installation/Operation Manual Setting the SK-2865’s address The range of valid addresses is 0-3. Each device requires a unique address. Set the dip switches as shown in Table 4-3. See also Figure 4-11. Table 4-3: SK-2865 Addresses Per Dip Switch Setting Dip Switch Position Equivalent Address Both Open (off) 0 One Closed (on) 1 Two Closed (on) 2 Both Closed (on) 3 Mounting the SK-2865 The SK-2865 mounts into a standard 4” square electrical box.
Hardware Installation 4.7.3 SK-2880 Installation The SK-2880 is an Input/Output module. The SK-2880 has 33 pre-defined open collector outputs (see Table 4-6) that can be used to drive LEDs, interface with other controls or systems, or control one of the three built-in Form C relays. See Figure 4-13, Figure 4-15 and Figure 4-16. The SK-2880 also has two supervised inputs used for Reset and Silence. See Figure 4-16.
Model SK-4224 Fire Control Panel Installation/Operation Manual 4.7.3.1 Connecting the SK-2880 to the SK-2884 The control panel communicates to the I/O module through the Serial Interface Board (see also Section 4.7.1). Figure 4-14 illustrates how to properly wire the I/O module to the Serial Interface Board. Supervised Power Limited SK-2880 SK-2884 Figure 4-14 I/O Module Wiring 4.7.3.2 Setting the SK-2880 Address The range of valid addresses is 0-3. Each device requires a unique address.
Hardware Installation 4.7.3.3 Open Collector Outputs (P1, P2, and P3) Each pin on the Pin Connectors (P1, P2, and P3) have a predefined output. Table 4-6 lists the Pin Connectors and describes what each pin outputs. Table 4-6: Pin-outs for Open Collector Outputs Pin Connector P1 Pin 2 151068 Pin Number Output Description Pin 1 Zone 1 Alarm/Supervisory Outputs when there is an alarm or supervisory on Zone 1. Pin 2 Zone 1 Trouble Outputs when a trouble condition exists on Zone 1.
Model SK-4224 Fire Control Panel Installation/Operation Manual Table 4-6: Pin-outs for Open Collector Outputs Pin Connector Pin Number Output Description Pin 1 NAC 1 Trouble Outputs when a trouble condition exists on NAC 1. Pin 2 NAC 2 Trouble Outputs when a trouble condition exists on NAC 2. Pin 3 NAC 3 Trouble Outputs when a trouble condition exists on NAC 3. Pin 4 Dialer Trouble Outputs when any type of trouble occurs with the dialer, such as, no line voltage or a communication failure.
Hardware Installation 4.7.3.4 SK-2880 Input Switches and Relay Wiring This section describes the components of terminal strip 2 (see Figure 4-13) on the SK-2880. Terminal strip 2 provides two input switches (Reset & Silence) and three Form C relay. Figure 4-16 illustrates how to configure the inputs switches and the Form C Relays. Any Open Collector Output 4.7 KΩ UL Listed EOL Model 7628 Supervised Power Limited 4.
Model SK-4224 Fire Control Panel Installation/Operation Manual 4.7.3.5 Mounting the SK-2880 The I/O module must be mounted in a UL Listed enclosure. Follow these steps to mount the SK-2880: 1. Remove the SK-2880’s cover. A small screw driver can be used. 2. Remove the SK-2880 circuit board from the base by pushing outward on the base retaining tabs and lift the circuit board out. See Figure 4-17. Circuit Board Base Retaining Tabs Base Figure 4-17 Circuit Board and Plastic Base Components 3.
Section 5 Notification Expansion Mode The SK-4224 can be used to expand the power capabilities of an existing system’s notification circuits. The SK-4224 does this buy connecting the notification circuits of an existing or host fire alarm control panel to the FACP input of the SK-4224, which can trigger the SK-4224 notification cicuits when the host panel goes into alarm. Note: The SK-4224 does not go into the alarm state when the host control panel triggers the SK-4224’s notification cicuits. 5.
Model SK-4224 Fire Control Panel Installation/Operation Manual 5.2 Class B Notification Expansion Wiring Figure 5-2 shows Class B supervised wiring from a host fire alarm control panel to the SK4224 control panel. Use an EOL resistor as shown in to supervise the FACP input. The host fire alarm control panel may use an EOL with a value other than 4.7 KΩ, used by the SK4224. In this case, use an UL listed EOL for the host panel you are using.
Section 6 System Configuration To configure the SK-4224 system set the dipswitch that controls the option you want to select. The following chart shows how to program the dipswitches that control system, zone, and notification appliance operation. Refer to Figure 3-1 for location of the dipswitches. Important! When you change a dipswitch, be sure to perform a system reset (press [RESET]) or power down the panel. Dipswitch changes will have no effect until after the system has been reset.
Model SK-4224 Fire Control Panel Installation/Operation Manual Table 6-1: System Configuration To Enable For Entire Panel (DIP 3) DIP Position ON = Serial Annunciator connected to the control panel. SW5 Serial Accessory Devices *SW6 OFF = No Serial Annunciator connected to the control panel. ON = Serial Dialer connected to the control panel OFF = No Serial Dialer connected to the control panel. ON = 6 hour delay on AC loss report. AC loss report delay SW7 OFF = No delay on AC.
Section 7 System Operation The annunciator on the SK-4224 board is used for all system operation. It contains the switches for enabling silencing, resetting, and so on. The LEDs that indicate system status are also located on the annunciator. Figure 7-1 On-Board Annunciator 7.1 Meaning of LEDs The chart below explains the meaning of LEDs on the system board.
Model SK-4224 Fire Control Panel Installation/Operation Manual Table 7-1: Meaning of LEDs LED (Color) GND FAULT (yellow) Function ON = Ground fault condition exists and was acknowledged OFF = No fault Comments If flashing press the ACK button to acknowledged the condition. FLASHING = A ground fault condition detected LOW BATTERY (yellow) ON = Battery low condition that has been acknowledged OFF = Good battery condition If flashing press the ACK button to acknowledged the condition.
System Operation 7.2 Operation Keys (Switches) All system operation are performed from the on-board keys (switches) as described in the chart below. Table 7-2: Operations and Instructions Operation Disable notification appliance circuit. To re-enable the circuit, press [NAC DISABLE] again. Disable a zone Keystrokes Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm condition.
Model SK-4224 Fire Control Panel Installation/Operation Manual 7-4 151068
Appendix A Compatible Devices This section of the manual lists devices (smoke detectors and notification appliances) that are compatible with the SK-4224. Contact Silent Knight if you have a question about whether a device not listed here is compatible. A.1 Smoke Detectors This section of the manual contains information about smoke detectors that are compatible with the SK-4224. SK-4224 Identifier Voltage Range 24F 16.2-27.
Model SK-4224 Fire Control Panel Installation/Operation Manual A.1.2 Two-Wire Smoke Detectors The table below lists two-wire smoke detectors that are compatible with the SK-4224. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used. Note: The check mark by manufacturers name indicates that this device can be used in enhanced mode.
Compatible Devices Table A-1: Compatible Two-Wire Smoke Detectors Manufacturer Enhance Mode Compatible Compatibility ID Model Name or Number (Base model name or number in parentheses.
Model SK-4224 Fire Control Panel Installation/Operation Manual A.2 Notification Appliances The chart below lists notification appliances compatible with the SK-4224. Note: Units that operate at 12 or 24 VDC must be selected for 24 VDC operation.
Compatible Devices Table A-3: Compatible Notification Devices Manufacturer Model Type Faraday 5522B-( )-14-24-DC 4” Square Sync Strobe (flush) Faraday 6126B-U-14-24 VDC Horn/Strobe Faraday 6223B-0-14-24-DC Horn (flush) Faraday 6224B-0-14-24-DC Horn (surface) Faraday 6225B-0-4-24-DC Horn (ceiling) Faraday 6226B-( )-14-24-DC Horn/Strobe (flush) Faraday 6227B-( )-14-24-DC Horn/Strobe (surface) Faraday 6228B-( )-4-24-DC Horn/Strobe (ceiling) Faraday 6243B-0-14-24-DC Electron-Mechani
Model SK-4224 Fire Control Panel Installation/Operation Manual Table A-3: Compatible Notification Devices Manufacturer A-6 Model Type Gentex SHG24-15 Horn/Strobe Gentex GMH-24-X Horn Gentex GMS-24-X Horn/Strobe Gentex GMS-24-X Horn/Strobe Gentex G0T24 Horn Gentex G0S24-X Horn Gentex WGMS-24-X Horn/Strobe System Sensor MASS241 Horn/Strobe System Sensor MASS24110ADA Horn/Strobe System Sensor MASS2415ADA Horn/Strobe System Sensor MASS2475ADA Horn/Strobe System Sensor SS41
Compatible Devices Table A-3: Compatible Notification Devices Manufacturer Model Type Wheelock AES-EL1-WH-24-VF-R Multitone Horn Wheelock AES-DL1-WM-24-VF-R Multitone Horn Wheelock AES-EL1-WM-24-VF-R Multitone Horn Wheelock AH-24-R Horn Wheelock AH-24WP-R Horn Wheelock AMT-12\24-R Strobe Horn Wheelock AMT-24-LS-VFR Strobe Horn Wheelock AMT-24-LSM-VFR Strobe Horn Wheelock AMT-24-IS-VFR Strobe Horn Wheelock AS2415W-FR Audible Strobe Wheelock AS241575W-FR Audible Strobe Whee
Model SK-4224 Fire Control Panel Installation/Operation Manual Table A-3: Compatible Notification Devices Manufacturer A-8 Model Type Wheelock CH70-2475W-FR Chime Strobe Wheelock CH70-24110W-FR Chime Strobe Wheelock CH-CF1 Chime Wheelock CH-CF1-R Chime Wheelock CH-CF1-W Chime Wheelock CH-DF1 Chime Wheelock CH-DF1-R Chime Wheelock CH-BF1-WS-24-HF-R Strobe Chime Wheelock CH-CF1-LS-24 Strobe Chime Wheelock CH-CF1-MS-24 Strobe Chime Wheelock CH-CF1-IS-24 Strobe Chime Wheelo
Compatible Devices Table A-3: Compatible Notification Devices Manufacturer Model Type Wheelock EH-EL1-WH-24-VF-R Strobe Horn (dual input) Wheelock EH-DL1-WM-24-VF-R Strobe Horn (dual input) Wheelock EH-EL1-WM-24-VF-R Strobe Horn (dual input) Wheelock HSW-24-HFR Remote Strobe Wheelock HS2W-24-HFR Remote Strobe Wheelock HSPW-24-HFR Remote Strobe Wheelock IS-24-VFR Remote Strobe Wheelock IS1-24-VFR Remote Strobe Wheelock IS3-24-VFR Remote Strobe Wheelock ISP-24-HFR Remote Strobe
Model SK-4224 Fire Control Panel Installation/Operation Manual Table A-3: Compatible Notification Devices Manufacturer A-10 Model Type Wheelock MIZ-24-IS-VFR Mini-Horn/Strobe Wheelock MIZ-24-WS-VF-R Mini-Horn/Strobe Wheelock MIZ-24-WS-VF-W Mini-Horn/Strobe Wheelock MIZ-24-WH-VF-W Mini-Horn/Strobe Wheelock MIZ-24-WM-VF-W Mini-Horn/Strobe Wheelock MT-12/24-R Strobe Horn Wheelock MT4-12/24-R Multitone Appliance Wheelock MT4-115-R Multitone Appliance Wheelock MT-24-LS-VFR Strobe H
Compatible Devices Table A-3: Compatible Notification Devices Manufacturer Model Type Wheelock RSP-2415-VFR Strobe Wheelock RS-241575-VFR Strobe Wheelock RSP-241575-VFR Strobe Wheelock RS-2430-VFR Strobe Wheelock RS-2430-HFR Strobe Wheelock RS-2475-VFR Strobe Wheelock RSP-2475-HFR Strobe Wheelock RS-24110-HFR Strobe Wheelock RSP-24110-HFR Strobe Wheelock RSS-2415W-FR Strobe Wheelock RSS-241575W-FR Strobe Wheelock RSS-2430W-FR Strobe Wheelock RSS-2475W-FR Strobe Whee
Model SK-4224 Fire Control Panel Installation/Operation Manual Table A-3: Compatible Notification Devices Manufacturer A-12 Model Type Wheelock SH2W-24-VFR Synchronized Remote Strobe Wheelock SHPW-24-VFR Synchronized Remote Strobe Wheelock SCM-24-R Controller for Synchronized Strobes Wheelock SM-12/24-R Sync Module Wheelock SR-2415-VFR Sync Strobe Wheelock SRP-2415-HFR Sync Strobe Wheelock SR-241575-VFR Sync Strobe Wheelock SRP-241575-VFR Sync Strobe Wheelock SR-2475-VFR Sync
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • All new fire products manufactured by Silent Knight after September 1, 1997 have a limited warranty period of 18 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. • This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, or have been modified in any manner whatsoever.
Model SK-4224 Fire Control Panel Installation/Operation Manual • A new or refurbished board will be shipped to the customer. The customer will initially be billed for the replacement board but a credit will be issued after the repairable board is received at Silent Knight. • The defective board must be returned within 30 days of shipment of replacement board for customer to receive credit. No credit will be issued if the returned board was damaged due to misuse or abuse.
SK-4224 BasicOperating Instructions P/N 151066 These instructions must be framed and displayed next to the SK-4224 panel in accordance with NFPA 72 fire code for Local Fire Alarm System.