Instruction manual
P83601 F
Sheet 5 of 11
LIGHT DISTRIBUTION PER UL 1971:
Table 4: Horizontal Plane
Horizontal 15cd 1575cd* 30cd 75cd 110cd
Angle (in deg.) UL Min. Typ. 15cd Typ. 1575cd UL Min. Typ. 30cd UL Min. Typ. 75cd UL Min. Typ. 110cd
0 15.0 24 94 30.0 46 75.0 103 110.0 149
5 13.5 24 93 27.0 46 67.5 103 99.0 152
10 13.5 24 88 27.0 45 67.5 104 99.0 151
15 13.5 24 87 27.0 46 67.5 100 99.0 151
20 13.5 23 85 27.0 43 67.5 101 99.0 148
25 13.5 23 80 27.0 43 67.5 98 99.0 140
30 11.3 21 75 22.5 41 56.3 94 82.5 135
35 11.3 20 71 22.5 40 56.3 89 82.5 129
40 11.3 14 62 22.5 39 56.3 83 82.5 124
45 11.3 18 52 22.5 41 56.3 81 82.5 133
50 8.3 18 35 16.5 36 41.3 77 60.5 121
55 6.8 12 32 13.5 27 33.8 60 49.5 85
60 6.0 11 34 12.0 30 30.0 59 44.0 95
65 5.3 13 27 10.5 35 26.3 71 38.5 113
70 5.3 17 19 10.5 29 26.3 73 38.5 81
75 4.5 13 11 9.0 22 22.5 53 33.0 72
80 4.5 8 9 9.0 17 22.5 35 33.0 50
85 3.8 7 10 7.5 15 18.8 30 27.5 38
90 3.8 6 10 7.5 15 18.8 30 27.5 43
Table 4A: Vertical Plane
Vertical 15cd 1575cd* 30cd 75cd 110cd
Angle (in deg.) UL Min. Typ. 15cd Typ. 1575cd UL Min. Typ. 30cd UL Min. Typ. 75cd UL Min. Typ. 110cd
0 15.0 24 94 30.0 46 75.0 103 110.0 149
5 13.5 24 83 27.0 46 67.5 103 99.0 149
10 13.5 24 30 27.0 46 67.5 103 99.0 137
15 13.5 24 19 27.0 45 67.5 102 99.0 120
20 13.5 24 17 27.0 41 67.5 104 99.0 110
25 13.5 21 16 27.0 48 67.5 89 99.0 129
30 13.5 23 15 27.0 40 67.5 96 99.0 114
35 9.8 22 12 19.5 45 48.8 91 71.5 119
40 6.9 13 11 13.8 39 34.3 57 50.6 109
45 5.1 9 10 10.2 24 25.5 36 37.4 66
50 4.0 9 9 8.1 16 20.0 33 29.7 45
55 3.3 8 9 6.6 15 16.3 31 24.2 43
60 2.7 8 9 5.4 15 13.5 31 19.8 40
65 2.4 8 9 4.8 14 12.0 31 17.6 40
70 2.3 8 10 4.5 15 11.3 31 16.5 39
75 2.0 8 10 4.0 14 10.0 31 14.3 39
80 1.8 8 9 3.6 13 9.0 27 13.2 36
85 1.8 7 9 3.6 13 9.0 27 13.2 37
90 1.8 3 9 3.6 9 9.0 12 13.2 28
* 1575W models are UL Listed for 15cd and meet 75cd on axis.
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING
PARTITIONS OR OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE
LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED
VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S
ORIENTATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.