POWERPATH PS-12/24-8CP (103047) POWER BOOSTER POWER SUPPLY Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web Site: www.wheelockinc.com e-mail: info@wheelockinc.com Copyright 2004 Wheelock, Inc. All rights reserved.
Thank you for using our products. Use this product according to this instruction manual. Please keep this instruction manual for future reference. TABLE OF CONTENTS 1.0 - INTRODUCTION AND SPECIFICATIONS 3 1.1 - INTRODUCTION 3 1.2 - SPECIFICATIONS 4 1.3 - TERMINOLOGY 4 1.4 - TERMINAL IDENTIFICATION 5 1.5 - LED STATUS 7 1.6 - BATTERY MAINTENANCE 7 2.0 - INSTALLATION INSTRUCTIONS 7 2.1 - UNPACKING 7 2.2 - MOUNTING 7 2.3 - WIRING 9 2.4 - RELAY STATUS CONNECTIONS 9 3.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol letters. . All WARNINGS are printed in bold capital WARNING: READ THIS INSTRUCTION MANUAL CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS, AND WARNINGS COULD RESULT IN IMPROPER APPLICATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 1.0 INTRODUCTION AND SPECIFICATIONS: 1.
1.2 SPECIFICATIONS Approvals: • UL Listed 864 Standard for Control Units for Fire Protective Signaling Systems • Pending: FM • Pending: MEA approved – NYC Dept. of Buildings • Pending: California State Fire Marshall (CSFM) approved • Pending: Bureau of Fire Protection (BFP) Chicago • NFPA 72 compliant Inputs: • 120VAC, 50/60Hz, 5.0 Amps or 240VAC, 50/60Hz 3.
1.4 TERMINAL IDENTIFICATION Table 1: Terminal Identification Terminal Block Identification Numbers (Figure 1) TB4-1, 2 Terminal Identification IN1+,IN1- TB4-3, 4, RET1+, RET1- TB5-1, 2 TB5-5, 4 TB4-5, 6 IN2+, IN2RET2+, RET2C “DRY1” NC TB5-5, 6 C “DRY2” NC TB6-1, 2 TB6-3, 4 TB6-5, 6 TB6-7, 8 +OUT1+OUT2+OUT3+OUT4- TB7-1-3 “NO” “C” “NC” (COMMON TROUBLE OUTPUT) + AUX - TB7-4, 5 P84515 E Function/Description These terminals connect to the input voltage source (i.e. 12VDC or 24VDC FACP).
AC POWER 120VAC, 50/60Hz OR 240VAC, 50/60Hz (NONPOWER-LIMITED, SUPERVISED) MADE IN USA WITH PRIDE (LINE OR BLACK LEAD) L1 (NEUTRAL OR WHITE LEAD) L2 (GROUND OR GREEN LEAD) EARTH TB1 F1 G L2 G L1 SW1 AC POWER SELECTION 120/240VAC 10 AMP 250V 115V AC POWER FUSE OUT TRB D9 D8 OUT1 D13 OUT2 D15 SW2 SW3 1 2 3 4 OUTPUT1 IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT OUTPUT2 IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT SW5 SW6 ON OFF ON AC INP2 GND FAULT BATT 1 2 3 4 OUT4 D19 1 2 3 4 OUT
1.5 LED STATUS Table 2 lists status of the LED indicators. The ALARM condition occurs when the input causes the output circuits to energize. TROUBLE condition occurs when the circuit is no longer supervised correctly. The TROUBLE LED’s for OUT1, OUT2, OUT3, OUT4 and, GND FAULT latch ON when the trouble occurs. They are turned OFF when an alarm condition occurs or the PS12/24-8CP system rest (SW8) is pressed. The trouble relay follows any trouble condition and is not latching.
1.060" 10.000" .544" 13.950" Figure 2: Mounting Dimensions DIMENSIONS (H x W x D) - 16” x 12.25” x 5” NOTE: All dimensions shown are measured in inches.
2.3 WIRING Review the Operation Section (3.0) in order to select the proper hook-up and use of the POWERPATH. Set switches and wire the POWERPATH as follows: Terminal locations are shown in Figure 1. Set Power Supply switch (SW1) for 120VAC or 240VAC operation. See Figure 1. A. B. C. D. E. Set Power Supply switch (SW4) for desired output voltage (Down for 24VDC, Up for 12VDC). See Figure 1. Set output DIP Switch(s) to follow corresponding input (IN1, IN2) and desired output mode.
AC POWER NON-POWER LIMITED 120VAC, 5 AMPS, 50/60Hz 240VAC, 3 AMPS, 50/60Hz TB1 F1 G L2 G RELAY CONTACTS L1 SW1 AC POWER SELECTION 120/240VAC 10 AMP 250V 115V AC POWER FUSE OUT3 D16 OUT4 INPUT SELECT OUTPUT2 IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT 1 2 3 4 OUTPUT1 IN>OUT SYNC WHEELOCK SYNC TEMPORAL D19 SW2 SW3 SW5 SW6 ON OFF ON AC INP2 GND FAULT BATT D71 POWER SUPPLY DC 1 2 3 4 D14 D18 1 2 3 4 INPUT CIRCUITS POWER-LIMITED D10 INP1 OUTPUT3 IN>OUT SYNC WHEELOCK SYNC TEMPOR
3.0 OPERATION: 3.1 MODES OF OPERATION The PS-12/24-8CP POWERPATH can provide a 12VDC or 24VDC output when initiated by a 8VDC to 33VDC appliance (IN1 or IN2) or an open contact (DRY1 or DRY2). The output will remain on until the deactivation of the input returns it to standby mode. The outputs can be configured as four Class “B” circuits, two Class “A” circuits, or two Class “B” and one Class “A” circuits. Each Class "A" circuit is 3.0 Amps and each Class "B" circuit is 3.0 Amps.
3.3 CLASS “B” OPERATION Class “B” outputs can be controlled from either IN1 or IN2. Switch SW9 position 1 & 2 on the board are in the “OFF” position. The following are examples of Class “B” connections. A FACP is used as a representative input. • IN1 and/or IN2 can be used for connection to the FACP. The INPUT SELECT Switch (1) selects which input is to be used to activate the output. • Board switch SW9 position 1 & 2 control Class “A” or Class “B” configuration. SW9 position 1 controls Outputs 1 and 3.
Example 3: IN>OUT SYNC MODE from CODED INPUT SOURCE (CLASS B) CODED + + IN1 4 - 3 1 - 2 ON RET2 OUT1 IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT OUT2-4 4 3 CONSTANT 2 + 1 F A C P TO NEXT APPLIANCE + OR EOLR IN2 - TO NEXT APPLIANCE + OR EOLR - TO NEXT APPLIANCE OR EOLR (2.2K OHMS) OUT1 ON SW9 + TO NEXT APPLIANCE OR EOLR (2.2K OHMS) IN>OUT SYNC WHEELOCK SYNC TEMPORAL OUT2 INPUT SELECT - POWERPATH RET2 OUT3 + - EOLR 2.2K OHMS SW9 ON 1 2 3 OUT4 4 + - EOLR 2.
Example 5: IN>OUT SYNC MODE with External Sync Module with Audible Silence (CLASS B) SM/DSM + 4 + MINUS 1 1 F A C P TO NEXT APPLIANCE OR EOLR 2 - + OUT1 + IN1 3 IN1 ON + RET1 - EOLR + AUDIBLE OUT2 POWERPATH - AUDIBLE TO NEXT APPLIANCE OR EOLR (2.2K OHMS) OUT1-4 IN>OUT SYNC WHEELOCK SYNC OUT1 TEMPORAL INPUT SELECT OUT3 + - + - EOLR 2.2K OHMS EOLR 2.2K OHMS SW9 ON OUT4 + - 1 2 3 4 EOLR 2.
Example 7: WHEELOCK SYNC MODE with Audible Silence (CLASS B) + + IN>OUT SYNC OUT1 WHEELOCK SYNC TEMPORAL INPUT SELECT 3 2 1 F A C P TO NEXT APPLIANCE + OR EOLR ON RET1 - OUT2 AUDIBLE SILENCE + - POWERPATH + - TO NEXT APPLIANCE + OR EOLR - IN2 OUT3 + - EOLR 2.2K OHMS EOLR 2.2K OHMS RET2 SW9 ON OUT4 + - 1 • TO NEXT APPLIANCE OR EOLR (2.2K OHMS) OUT1-4 4 IN1 - 2 4 3 EOLR 2.
Example 9: TEMPORAL MODE (CLASS A) OUT1 OUT2 - ON OUT4 3 3 OUT2 + - 4 4 2 2 1 1 IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT ON 1 RET1 + - 2 ON + 3 1 F A C P 2 - TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A") OUT1 4 3 IN1 OUT3 IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT 4 + ON POWERPATH OUT3 + SW9 ON OUT4 + 1 2 3 4 CAUTION: Strobes require constant voltage and will not operate properly in the TEMPORAL MODE.
Example 11: IN>OUT SYNC MODE with External Sync Module without Audible Silence (CLASS A) SM/DSM 2 1 MINUS 1 IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT 3 + IN1 OUT1-4 - 4 F A C P + IN1 + OUT1 TO NEXT APPLIANCE + OR EOLR RET1 + - ON - + AUDIBLE OUT1 OUT2 + - POWERPATH - AUDIBLE - OUT3 + SW9 ON OUT4 + 2 1 4 3 NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur with Wheelock sync appliances.
Example 13: WHEELOCK SYNC MODE without Audible Silence (CLASS A) OUT1-4 4 3 2 IN1 1 F A C P + - IN>OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT + - ON - RET1 + OUT2 + - POWERPATH + - TO NEXT APPLIANCE OR EOLR OR RETURN TO FACP (CLASS "A") IN2 - OUT3 + - RET2 + SW9 ON OUT4 2 1 • • • OUT1 - + 4 3 This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
3.5 MASTER REMOTE OPERATION: Example 15: Synchronized Multiple PS-12/24-8MP or PS12/24-8CP Using a Master PS12/24-8MP or PS12/24-8CP (in the WHEELOCK SYNC MODE) Without Audible Silence, and Using Input #1.
Example 16: Synchronized Multiple PS-12/24-8MP or PS-12/24-8CP Using a Master PS12/24-8MP or PS12/24-8CP (in the WHEELOCK SYNC MODE) With Audible Silence, and Using Input #1 GND L2 L1 TB1 GND F1 MASTER 115V OUT2 D9 INP1 D15 INP2 OUT3 D16 FAULT OUT4 D19 BATT OUT1 D14 D18 NOTE 2 SW3 SW2 OUTPUT1 IN>OUT SYNC SW1 D10 AC OUT TRB D8 D13 TEMPORAL INPUT SELECT INPUT SELECT OUTPUT2 IN>OUT SYNC OUTPUT4 IN>OUT SYNC WHEELOCK SYNC PROGRAMMED AUDIBLE SILENCE +NAC + NAC INPUT IN ALARM CONDITIO
4.0 TROUBLESHOOTING: WARNING: THE PS-12/24-8CP POWERPATH CONTAINS VOLTAGES THAT CAN CAUSE DEATH OR SERIOUS INJURY. ALWAYS OBSERVE PROPER ELECTRICAL SAFETY PRECAUTIONS AND WARNINGS. Always follow good troubleshooting procedures: • When trouble occurs, observe all visual indications and note them. • If the problem is obvious or it can be located on the Troubleshooting Table, note it. • Press SYS RESET (SW8) and wait 30 seconds check for a trouble indication.
5.0 BATTERY CALCULATION SHEET: PS-12/24-8CP BATTERY CALCULATION SHEET STANDBY CURRENT CALCULATIONS Amps 1. The Standby Current for the PS-12/24-8CP is .060 Amps. 2. Enter the AUX current draw (0.06 Amps, 60 hour operation maximum)** (0.20 Amps, 24 hour operation maximum) 3. Add Steps 1 and 2 together Amps Amps 4. Multiply Step 3 by the number of hours required. 24 Hours - Multiply by 24 60 Hours - Multiply by 60** TOTAL STANDBY CURRENT IN Amp HOURS. AH ALARM CURRENT CALCULATIONS 1.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT’S APPLICATION, OPERATION. INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER, AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE. 6.