Instruction manual

P84515 E Sheet 14 of 23
Example 5: IN>OUT SYNC MODE with External Sync Module with Audible Silence
(CLASS B)
POWERPATH
OUT1-4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
TO NEXT
APPLIANCE
OR EOLR
-
+
IN1
-
+
RET1
+ OUT1
+ IN1
MINUS 1
+ AUDIBLE
SM/DSM
F
A
C
P
EOLR
- AUDIBLE
EOLR
2.2K OHMS
EOLR
2.2K OHMS
+
OUT4
-
+
OUT3
-
EOLR
2.2K OHMS
-
+
OUT2
+
-
OUT1
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
1
23
4
ON
1
23
4
ON
1
23
4
ON
1
2
3
4
ON
SW9
NOTE: When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur
with
Wheelock sync appliances.
Example 6: WHEELOCK SYNC MODE without Audible Silence (CLASS B)
POWERPATH
OUT1-4
IN>OUT SYNC
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
IN1
+
-
IN2
+
-
TO NEXT APPLIANCE
OR EOLR
+
RET2
-
P
C
A
F
RET1
+
-
-
OUT4
-
+
OUT3
+
OUT2
-
+
EOLR
2.2K OHMS
EOLR
2.2K OHMS
EOLR
2.2K OHMS
+
-
OUT1
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
1
23
4
ON
1
23
4
ON
1
23
4
ON
1
2
3
4
ON
SW9
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
If only strobes are connected to the POWERPATH outputs, the initiating input to IN2 is not required.
When synchronized horns are used on the two wire output of the POWERPATH, IN2 must be connected as
shown or the horns will not operate.