Instruction manual

P84515 E Sheet 4 of 23
1.2 SPECIFICATIONS
Approvals:
UL Listed 864 Standard for Control Units for Fire Protective Signaling Systems
Pending: FM
Pending: MEA approved – NYC Dept. of Buildings
Pending: California State Fire Marshall (CSFM) approved
Pending: Bureau of Fire Protection (BFP) Chicago
NFPA 72 compliant
Inputs:
120VAC, 50/60Hz, 5.0 Amps or 240VAC, 50/60Hz 3.0 Amps Operating Power in Alarm
12/24VDC Battery Backup Connection
Two (2), 12VDC or 24VDC NAC Initiating Circuits (8-33VDC at 5mA)
Two (2) “Dry” Contact initiating Circuits
Accepts two Class “A” or two Class “B” circuit inputs
Built in battery charger for sealed lead acid or gel type batteries
Outputs:
Switch selectable 12VDC or 24VDC power limited outputs
8 Amp in alarm supply current at 12VDC or 24VDC
Capable of four (4), Class "B" circuits (2.0 Amps each)
Capable of two (2) Class “A” circuits (3.0 Amps each)
Capable of one (1) Class “A” circuit (3.0 Amps) and two (2) Class “B” circuits (2.0 Amps each)
Capable of two (2) Class “B” circuits (3.0 Amps each) and (2) Class “B” circuits (2.0 Amps total)
Temporal (Code 3) or constant voltage output generation
Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits
Input and output can be synchronized with “IN>OUT SYNC” mode (SM, DSM or 2
nd
PS-12/24-8CP is
required)
Audible silence capability
Filtered and electronically regulated output
0.06 Amp continuous auxiliary power for 60 hours, which is power limited with reset capability.
0.2 Amp continuous auxiliary power for 24 hours, which is power limited with reset capability.
Supervision:
Compatible with 12VDC or 24VDC FACP
Signaling appliance loops are supervised and steered to either IN1 or IN2
2.2K Ohm, 1 Watt (Wheelock Model #MPEOL) End of Line Resistor (EOLR) for supervision of all outputs
Common input and output trouble circuits
Automatic switchover to standby battery when AC fails
Thermal and short circuit protection with auto reset
Input and output status LED indicators
AC fail supervision (Form C contact, 1 Amp 28VDC)
Battery presence and low battery supervision (Form C contact, 1 Amp 28VDC)
Ground Fault Detection
1.3 TERMINOLOGY
CLASS “A” = STYLE Z
CLASS “B” = STYLE Y
FACP = Fire Alarm Control Panel
EOLR = End of Line Resistor
NAC = Notification Appliance Circuit
SM = Wheelock Sync Module with single output.
DSM = Wheelock Dual Sync Module with two outputs.
C = Common
NC = Normally Closed
NO = Normally Open
AH = Ampere/Hour