Instruction manual

Table 3-2
Jumper/Switch/Variable Resistor Functions
Jumpers Name Description
W1 Auxiliary In CC EOLR Detection Jumper in place – EOLR not detected
Jumper removed – Detection enabled for 10K Ohm
EOLR.
W4 Not Used - Jumper shall remain in place .
W5 Wheelock Sync Disable (SPB-80/4
Only)
Jumper in place – Wheelock Sync enabled.
Jumper removed – Wheelock Sync disabled. Pass
through sync or constant NAC enabled.
W6 Ground Fault Disable Jumper in place – Ground Fault Circuit enabled.
Jumper removed – Ground Fault Circuit Disabled.
W7 Audio Input Installed EOLR (For
Wheelock Host Voice Evacuation
Panel)
Jumper in place – Audio Input EOLR enabled.
Jumper removed – Audio Input EOLR disabled.
W8 Not Used - Jumper shall remain in place .
W10 Shorted Audio Output Non Emergency
Defeat
Jumper in place – Telephone Page, BGM, NR disabled.
Jumper removed – Telephone Page, BGM, NR enabled
J1A/J1B Audio 1 Output Voltage Select Selects Output Voltage 25V or 70V in conjunction with J3.
J2 Audio Input Select Selects 25V or 70.7V for Audio input (AUD IN) by moving
jumper.
J3 Audio 1 Output Voltage Select Selects Output Voltage 25V or 70V in conjunction with J1.
J4 Audio 2 Output Voltage Select SPB-160 Only. Selects Output Voltage 25V or 70V in
conjunction with J5.
J5 Audio 2 Output Voltage Select SPB-160 Only. Selects Output Voltage 25V or 70V in
conjunction with J4.
Switches Name Description
SW1 Auxiliary In NAC/CC Select Selects auxiliary input type 8-33VDC NAC or Contact
Closure (CC). Switch depressed to the left for CC.
SW4 Strobe In NAC/CC Select SPB-80/4 Only. Selects strobe input type 8-33VDC NAC
or Contact Closure (CC). Switch depressed to the left for
CC.
Variable
Resistors
Name Description
R23 (LVL) Audio Input Volume Control Adjusts audio input volume.
Checkout Procedure.
CAUTION: Always connect the AC power source before connecting the battery backup
power. Always disconnect the AC power source before disconnecting the battery backup power
.
1. Connect AC power, then connect battery backup.
NOTE: When the AC power source is applied to the panel, the battery voltage check circuitry is
activated. If batteries are not connected within 20 seconds the panel trouble circuit will be
activated. The battery voltage check circuitry will re-check for batteries every 2 minutes. If the
batteries are installed during the 2-minute period, the panel will remain in trouble until the next re-
check.
D59 AC LED (Green) should be “ON” to indicate normal operation. If D24 TROUBLE LED
(Yellow) is “ON”, a trouble condition is indicated. STOP TESTING
. Refer to Chapter 7 of this
manual, troubleshoot and correct the problem before you resume testing. See Figure 7-1A (SPB-
160) and 7-1B (SPB-80/4) on Pages 49 and 50 for location of LEDs.