Instruction manual

Activation Inputs
The panel audio output is activated by applying a 25V or 70.7V at 1.2 Watts maximum input signal to
AUD IN.
The AUX IN is triggered using 8 – 33VDC at 10mA in NAC mode or with contact closure in CC mode.
Outputs
Table 8-4 Outputs
Visual Notification Appliance
Output (SPB-80/4 only)
2 output circuits. 2.0 amps
at 24VDC. Supervised.
Central Amplified Audio Output (SPB-80/4) 1 output circuit.
Selectable 25 or 70.7 Volt
output at 80W max.
Supervised.
(SPB-160) 2 output circuits.
Selectable 25 or 70.7 Volt
output at 80W max for
each. Supervised.
Trouble Contact Form C contact normally
energized. Contacts
transfer during trouble: 1.0
amps at 24VDC max,
resistive load (see following
warning). Non-Supervised.
WARNING: DO NOT EXCEED THE RATINGS OF THE STATUS CONTACTS. EXCEEDING
THIS RATING MAY CAUSE THE RELAY TO FAIL AND PREVENT A TROUBLE CONDITION
FROM BEING INDICATED.
Wiring Connections
Table 8-5 Wiring Connections
Screw terminals Accepts #12 to #18 AWG for single
wire connection, or #16 to #18
AWG for double wire connection.
End of Line Resistor (EOLR)
Table 8-6 EOLR
Visual Notification Appliance
Outputs
UL Listed 10K Ohm, EOLR
Audio Notification Appliance
Outputs
UL Listed 10K Ohm, EOLR
58