Technical data
Chapter 3: Overview  
SP40S Multi-Function Facility Communication System Manual, Revision L 
16 
SW4 (Tone Types) 
PIN 
FUNCTION 
ON 
1 
Tone Type - DV1 
Code 3 (OFF = continuous) 
2 
Tone Type - DV2 
Code 3 (OFF = continuous) 
3 
Tone Type - DV3 
Code 3 (OFF = continuous) 
4 
Tone Type - DV4 
Code 3 (OFF = continuous) 
5 
Tone Type - DV5 
Code 3 (OFF = continuous) 
6 
Tone Type - DV6 
Code 3 (OFF = continuous) 
7 
Tone Type - DV7 
Code 3 (OFF = continuous) 
8 
Tone Type - DV8 
Code 3 (OFF = continuous) 
9 
Backup tone 
Code3 (OFF = slow whoop) 
10 
unused 
-- 
SW5 (Pre-tone/Post-tone Enable) 
PIN 
FUNCTION 
ON 
1 
Pre-tone - DV1 
Pre-tone ON for Message 1 
2 
Pre-tone - DV2 
Pre-tone ON for Message 2 
3 
Pre-tone - DV3 
Pre-tone ON for Message 3 
4 
Pre-tone - DV4 
Pre-tone ON for Message 4 
5 
Pre-tone - DV5 
Pre-tone ON for Message 5 
6 
Pre-tone - DV6 
Pre-tone ON for Message 6 
7 
Pre-tone - DV7 
Pre-tone ON for Message 7 
8 
Pre-tone - DV8 
Pre-tone ON for Message 8 
9 
Post-tone - All 
Post-tones enabled (Post-tone Matches Pre-tone) 
10 
Message Repeat 
ON = Message plays a minimum of 3 times 
OFF = Message plays a minimum of 1 time* 
*NOTICE  TO  USERS,  INSTALLERS,  AUTHORITIES  HAVING  JURISDICTIONS  AND  OTHER  INVOLVED 
PARTIES:  In order for this product to comply with the requirements in the Standard for Control Units and Accessories for 
Fire  Alarm  Systems,  UL  864,  Position  10  of  SW5  must  be  kept  in  the  ON  position.    UL  864,  9
th
  Edition,  section  34.2.1.1 
requires the alert tone/prerecorded message combination shall be repeated a minimum of 3 times. 










