Technical data

Chapter 3: Overview
SP40S Multi-Function Facility Communication System Manual, Revision L
16
SW4 (Tone Types)
PIN
FUNCTION
ON
1
Tone Type - DV1
Code 3 (OFF = continuous)
2
Tone Type - DV2
Code 3 (OFF = continuous)
3
Tone Type - DV3
Code 3 (OFF = continuous)
4
Tone Type - DV4
Code 3 (OFF = continuous)
5
Tone Type - DV5
Code 3 (OFF = continuous)
6
Tone Type - DV6
Code 3 (OFF = continuous)
7
Tone Type - DV7
Code 3 (OFF = continuous)
8
Tone Type - DV8
Code 3 (OFF = continuous)
9
Backup tone
Code3 (OFF = slow whoop)
10
unused
--
SW5 (Pre-tone/Post-tone Enable)
PIN
FUNCTION
ON
1
Pre-tone - DV1
Pre-tone ON for Message 1
2
Pre-tone - DV2
Pre-tone ON for Message 2
3
Pre-tone - DV3
Pre-tone ON for Message 3
4
Pre-tone - DV4
Pre-tone ON for Message 4
5
Pre-tone - DV5
Pre-tone ON for Message 5
6
Pre-tone - DV6
Pre-tone ON for Message 6
7
Pre-tone - DV7
Pre-tone ON for Message 7
8
Pre-tone - DV8
Pre-tone ON for Message 8
9
Post-tone - All
Post-tones enabled (Post-tone Matches Pre-tone)
10
Message Repeat
ON = Message plays a minimum of 3 times
OFF = Message plays a minimum of 1 time*
*NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTIONS AND OTHER INVOLVED
PARTIES: In order for this product to comply with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864, Position 10 of SW5 must be kept in the ON position. UL 864, 9
th
Edition, section 34.2.1.1
requires the alert tone/prerecorded message combination shall be repeated a minimum of 3 times.