Technical data
Chapter 3: Overview
SP40S Multi-Function Facility Communication System Manual, Revision L
17
SW6 (Initiation mode select for Aux IN)
SETTING
DESCRIPTION
CC
Contact Closure Mode for use with RMX or
SPRM
NAC
8 to 33VDC NAC Input
SW7 (DV IN Supervision and Auxiliary Timeout)
PIN
FUNCTION
ON
1
DV MES 1 CC Supervision
10k EOLR supervision ON for IN1
2
DV MES 2 CC Supervision
10k EOLR supervision ON for IN2
3
DV MES 3 CC Supervision
10k EOLR supervision ON for IN3
4
DV MES 4 CC Supervision
10k EOLR supervision ON for IN4
5
DV MES 5 CC Supervision
10k EOLR supervision ON for IN5
6
DV MES 6 CC Supervision
10k EOLR supervision ON for IN6
7
DV MES 7 CC Supervision
10k EOLR supervision ON for IN7
8
DV MES 8 CC Supervision
10k EOLR supervision ON for IN8
9
AUX Input Timeout
Timeout active
10
unused
--
SW9
PIN
FUNCTION
ON
1
Sync mode (NAC input)
Standard Sync
(OFF = PASS THRU SYNC MODE)
2
Sync mode (Alarm)
Standard Sync (OFF = 28 volts)
3
unused
--