Technical data
    Chapter 3: Overview  
SP40S Multi-Function Facility Communication System Manual, Revision L 
19 
3.7.3 LED Descriptions 
Head 
Description 
Additional 
D1 
Audio Output Open 
ON = Audio Output is open or missing EOLR 
D2 
Audio Output Short 
ON = Audio Output is shorted 
D3 
DV, Digital Voice Section 
ON = DV Audio is low or DV is damaged 
D4 
MIC, PTT MIC Missing or inoperable 
ON = MIC missing or inoperable; 
Blinking = MIC preamp trouble 
D5 
AMP, Amplifier Section Trouble 
ON = Amplifier trouble or audio current limiting; 
Blinking = AUX preamp trouble 
D6 
External AC Wiring trouble 
ON = SPB SUP missing EOLR 
D8 
Battery Trouble 
ON = BATT missing or low 
D29 
Audio Peak/Overload 
ON = Audio level is too high 
D44 
AUX IN Trouble 
ON = CC Open, RMX, or Remote MIC Trouble 
D47 
User Interface trouble 
User Interface is improperly connected 
D55 
DV1 – IN1 OPEN 
ON = IN1 open or missing EOLR 
D58 
DV3 – IN3 OPEN 
ON = IN3 open or missing EOLR 
D62 
DV2 – IN2 OPEN 
ON = IN2 open or missing EOLR 
D65 
DV4 – IN4 OPEN 
ON = IN4 open or missing EOLR 
D67 
GF, Ground Fault Trouble 
D75 
DV5 – IN5 OPEN 
ON = IN5 open or missing EOLR 
D78 
DV7 – IN7 OPEN 
ON = IN7 open or missing EOLR 
D84 
DV6 – IN6 OPEN 
ON = IN6 open or missing EOLR 
D87 
DV8 – IN8 OPEN 
ON = IN8 open or missing EOLR 
D93 
Battery Charger Trouble 
ON = Battery charger circuit in trouble 
D96 
Strobe Short 
ON = Short on strobe out 
D97 
Strobe Open 
ON = Strobe out open or missing EOLR 
D100 
(Green) Power 
ON = AC and or BAT Power is present 
D109 
(Green) AC Power 
ON = AC Power is present 