Technical data

Chapter 4: Installation
SP40S Multi-Function Facility Communication System Manual, Revision L
5
Terminal
Block
Symbol
Alarm Connections
Definitions
TB7
Terminal
Block 7
Section 7
Internal Digital Voice Module Input Connections
IN 1
Input 1
Digital Voice Initiating connection for message #1 (contact
closure). Priority 3.
IN 2
Input 2
Digital Voice Initiating connection for message #2 (contact
closure). Priority 4.
IN 3
Input 3
Digital Voice Initiating connection for message #3 (contact
closure). Priority 5.
IN 4
Input 4
Digital Voice Initiating connection for message #4 (contact
closure). Priority 6.
TB8
Terminal
Block 8
Section 8
Internal Digital Voice Module Input Connections
IN 5
Input 5
Digital Voice Initiating connection for message #5 (contact
closure). Priority 7.
IN 6
Input 6
Digital Voice Initiating connection for message #6 (contact
closure). Priority 8.
IN 7
Input 7
Digital Voice Initiating connection for message #7 (contact
closure). Priority 9.
IN 8
Input 8
Digital Voice Initiating connection for message #8 (contact
closure). Priority 10.
TB9
Terminal
Block 9
Section 9
Primary Power (VAC) Connections
AC
Primary Power (AC)
AC Input Voltage. Make sure Line (L), Neutral (N), and Ground
(G) are connected. Non-power limited. Make sure power cord is
run properly (see wiring diagram Figure 4-13 in Section 4.9.1).
TB10
Terminal
Block 10
Section
10
Secondary Power (Battery) Connections
BAT
Secondary Power (Battery)
24VDC, up to 33 Ah Battery input connection. The enclosure can
accommodate up to 12 Ah. Batteries greater than 12 Amp-Hours
(Ah) are required to be installed in a UL listed battery box. Non-
power limited.
TB12
Terminal
Block 12
Section
11
Strobe Connections. See Appendix E for strobe compatibility list.
STB
OUT
Strobe Output
8-33 VDC, Regulated, 2A Maximum Strobe NAC Output
Supervised with UL Listed 10k Ohm, ½ W EOLR. (Power limited).
RET
Return
Strobe Input Return for connecting additional strobe circuits, or
UL Listed 10k Ohm, ½ W EOLR.
STB IN
Strobe Input
8-33 VDC, Strobe NAC Input. Triggers strobe in Alarm condition.
NOTE: All Outputs (Strobe Output, Audio Output, and 24VDC Auxiliary Power Source) are power limited
circuits.