Technical data
    Chapter 4: Installation   
SP40S Multi-Function Facility Communication System Manual, Revision L 
15 
4.5  Wiring the System 
4.5.1 Wiring Guidelines 
Although  the  SP40S  panel  incorporates  signal  verification  and  noise  filtering  circuitry  on  its  inputs,  induced 
voltages or noise on the input wiring can cause improper operation. Therefore, use shielded twisted pair wire for 
all dry contact input wiring. 
  Connect the shield of each cable only at one end. 
  Connect each shield of each cable that connects to the panel to the grounding points provided near the 
knockout locations on the chassis (see Figure 4-2). 
The  National  Electrical  Code  defines  two  types  of  circuits  for  protective  signaling  systems:  power  limited 
circuits and non-power limited circuits. All outputs (STB OUT, AUDIO OUT, and  ± 24VDC auxiliary power 
source) are power-limited circuits. 
 WARNING: Route all SP40S Multi-Function Facility Communication System 
audio wiring away from any high voltage or high current wiring (such as AC or DC 
power wiring, audio power wiring, and motor or relay actuation wiring). Failure to 
do so may cause electrical shock, resulting in serious injury or death to you and/or 
others. 
CAUTION: The National Electric Code limits the maximum number of conductors that can be 
installed in conduit and wiring boxes depending on the size of  the  conduit, the volume of  the 
boxes,  and  the  gauge  of  the  wire  used.  Make sure that  wiring  used  for  SP40S  installation 
complies with the latest NEC, NFPA, Local, State, County, or Province requirements. 
4.5.2 Field Wiring Connections 
All SP40S wiring terminals are designed to accept #12 AWG through #18 AWG wiring for one wire per 
terminal  or  #16  AWG  to  #18  AWG for  two  wires  per  terminal.  Proper  wire  gauge  considerations  for the 
Notification Circuit must take into account current requirements versus length of run. 
NOTE: Only speakers with DC blocking capacitors provide for proper speaker supervision. 
4.5.3 Preparing a System Wiring Diagram 
Prepare  a  system-wiring  diagram  to  include  all  Notification  Appliances,  and  internal  connections  and  power 
sources as required. 
NOTE: Separate the AC input power wiring from the other input and output wiring. Wire the AC input power to 
the left side of the motherboard (Figure 4-13) and the other input and output wiring to the right. 










