Technical data
Chapter 4: Installation   
SP40S Multi-Function Facility Communication System Manual, Revision L 
16 
4.5.4 Visual Notification Appliance Output Wiring 
Wire gauge selection involves consideration of all factors including, wire loop length, maximum current draw of 
each appliance, number of appliances, and maximum voltage drop allowable. 
  Strobe NAC has a regulated 24VDC, 2.0 Amps maximum output. 
  Strobe NAC meets Class B supervision requirements for notification appliance circuits. 
  For the strobe output circuit, install a UL Listed 10K Ohm, ½ W EOLR across the last visual notification 
appliance. If the output is unused, place a UL Listed 10K Ohm, ½ W EOLR across the output terminals. 
4.5.5 Speaker Notification Appliance Output Wiring 
Wire gauge may vary for each audio appliance output on the panel. When: 
  Speaker  (with  transformer) appliances  are  used  with  supervised  audio  amplifier  module.    Wire  gauge 
selection involves consideration of  all  factors including, wire length, appliance power ratings,  and the 
number of appliances. 
  The amplified output is either a selectable 25 or 70.7Vrms audio output, rated for 40 watts maximum. 
  The output meets Class B supervision requirements for notification appliance circuits. 
  To meet Class A requirements, a Cooper Notification splitter (SP4-A/B or SP4-APS) is required. 
  For the audio output circuit, install a UL Listed  10K Ohm, ½  W EOLR installed across  the last 
notification  appliance.  If  the  output  is  unused,  place  a  UL  Listed  10K  Ohm,  ½  W  EOLR  across  the 
output terminals.  
4.5.6 Wiring Diagrams for Audio/Visual Notification Appliances 
+
-
STROBE
UL LISTED 10K OHM, 1/2 W
END OF LINE RESISTOR
Figure 4-8 Wiring Diagram for Visual Only Notification Appliances 
CAUTION: Do not loop wire under terminals.  Break wire run to provide supervision of the 
connection. 