Technical data
    Chapter 4: Installation   
SP40S Multi-Function Facility Communication System Manual, Revision L 
19 
4.6  Performing System Checkout 
For guidelines on testing notification systems, refer to the latest NFPA 72 code. 
4.6.1 System Control Settings 
Figures  3-4  thru  3-8  show  the  location  of  the  controls  used  to  configure  the  SP40S  Multi-Function  Facility 
Communication System. Table 4-1 identifies and explains the functions of the terminal blocks, Section 3.7 the 
other user settings. The following procedure is a basic setup for the panel. 
1.  Ensure that the AC and Battery Power are not connected. 
2.  Plug in the microphone. 
3.  Select the proper audio output (25V or 70V) on J1 Audio Output Select. 
4.  Connect the speaker circuit(s) to terminal block TB4 AUD OUT. Verify that the speaker circuit has a UL 
Listed 10K Ohm, ½ W EOLR. 
5.  If applicable, connect the strobe circuit to TB12 STB OUT. Verify that the strobe circuit has a UL Listed 
10K Ohm, ½ W EOLR. 
6.  If Strobe synchronization is to be defeated, turn OFF positions 1 and 2 of SW9 Strobe Synchronization 
Defeat. 
4.6.2 Checkout Procedure 
  WARNING:  Always  connect  the  AC  power  source  before  connecting  the 
battery  backup  power.  Always  disconnect  the  AC  power  source  before 
disconnecting the battery backup power. 
NOTE:  All terminal blocks, jumpers, switches, LEDs, Fuses, and Potentiometers are illustrated in Figures 3-4 
thru 3-8. 
  Connect the interface ribbon cable to J6. 
  Connect AC power, then connect the batteries. 
When  the  AC  power  source  is  applied  to  the  panel,  the  battery  voltage  check  circuitry  is  activated.  If 
batteries  are  not  connected  within  20  seconds,  the  panel  trouble  circuit  activates.    The  battery  voltage 
check  circuitry re-checks  for  batteries  every  two  minutes.  If  the  batteries  are  installed  during  the  two-
minute period, the panel remains in trouble mode until the next re-check. 
  D100 PWR LED and POWER ON (Interface) LED should be “ON” to indicate normal operation.  
  If  SYSTEM  TROUBLE  (Interface)  LED  (Yellow)  is  “ON,”  and  the  internal  sounder  is  operating,  a 
trouble condition is indicated.  
  In such a case, STOP TESTING. Refer to Chapter 8 of this manual, then troubleshoot and correct the 
problem before you resume testing. See Figures 3-7 for location of LEDs. 
  Perform the following tests: 










