Technical data
    Chapter 4: Installation   
SP40S Multi-Function Facility Communication System Manual, Revision L 
23 
4.8.3 Calculating Backup Battery Requirements 
A Worksheet for assisting in calculating battery backup is available in Chapter 11. 
Due to  the current drain on  the battery,  the maximum  battery size for  the SP40S  Multi-Function  Facility 
Communication System is 33 Amp-Hours (Ah). The enclosure can accommodate up to 12 Ah. Batteries greater 
than 12 Amp-Hours (Ah) are required to be installed in a UL listed battery box. 
It is necessary to calculate the current draw for battery backup requirement. The current requirement depends on 
the system configuration and the appliances connected to the Speaker output circuits. Battery Backup current has 
two separate calculations that are added together: Standby Current and Alarm Current. 
4.8.3.A Standby Current 
The  Standby  Current  consumes  the  largest  part  of  the  storage  battery  capacity.  The  Standby  Current  of  the 
SP40S  Multi-Function Facility  Communication  System  is  0.130  Amps.  Multiply  this  value  by  the  number  of 
standby hours required. Normally this is 24 hours. This represents the total Standby current in Amp-Hours for 
the panel. 
4.8.3.B Alarm Current 
The maximum Alarm Current for the SP40S Multi-Function Facility Communication System is 4.70 Amps (1.6 
Amps for audio, 2.0 Amps for strobe, and 0.5 Amps for auxiliary power). 
1.  Calculate the strobe output current by adding the current draw of all strobes. Current draw is in Amps. 
2.  Calculate speaker output current by totaling all the speaker wattage settings. Multiply the sum by 0.040. 
The result is the current draw in Amps. 
3.  Add the strobe current, the speaker current, and auxiliary current together. The result is the total Alarm 
Current in Amps.  
Alarm circuits are required to operate for 15 minutes on battery power. Multiply Step 3 by 0.25 hrs. The result is 
the total Alarm Capacity Required in Amp-Hours. 
4.8.3.C Battery Calculations 
Good engineering practices recommend the total Amp-hours required for backup should not exceed 90% 
of the Backup Battery capacity. The SP40S Multi-Function Facility Communication System has been UL 
approved  for  a  maximum  of  33  Ah  batteries.  The  enclosure  can  accommodate  up  to  12  Ah.    Batteries 
greater than 12 Amp-Hours (Ah) are required to be installed in a UL listed battery box. 
1.  Add the total Standby Capacity Required to the total Alarm Capacity Required. 
2.  Multiply Step 1 by 1.25. This is the minimum Backup Battery requirement for this panel. 
3.  Record results on worksheet. 










