4.9   Installing AC Power and Batteries 
NOTE: Power-limited and non-power limited wiring must be separated. Wire non-power limited wiring (AC 
power  and  battery)  to the  left of  the  motherboard.  Wire  power  limited  wiring  to  the  right  and  top of  the 
motherboard. 
 WARNING:  Two different sources of power should be connected to this unit. 
Disconnect both  sources of  power before  servicing. Failure to  disconnect both 
power sources before servicing could result in serious injury or death to you and/or 
others. 
CAUTION:  Observe  correct  polarity  requirements  on  all connections.  Failure  to  do  so may 
damage the equipment. 
CAUTION: Always apply AC voltage before applying battery backup voltage. Failure to do  so 
may cause damage to the SP40S Multi-Function Facility Communication System. 
4.9.1 Installing AC Power 
1.  Refer  to  Figure  4-13  and  connect  the  line  and  neutral    input  wiring  to  the  L  (Line)  and  N  (Neutral) 
terminals on the terminal block TB9 (see Figure 4-1 for location) in the lower left corner of the chassis. 
2.  Ensure  that  the ground input wiring is connected to the ground terminal  (TB9) on  the  left  side  of the 
chassis. 
3.  Secure the wire with the caps nut located in the hardware package. 
AC Field Wiring
(non-power limited)
LINE, GROUND
and NEUTRAL
Thread wire out 
knockout on the 
left side of the 
enclosure.
Grounding
Terminal
Block
Figure 4-13 VAC Input Connection 