Technical data
SP40S Multi-Function Facility Communication System Manual, Revision L 
1 
5  Operation 
5.1  Introduction 
This  chapter  describes  the  operating  characteristics  of  the  SP40S  Multi-Function  Facility 
Communication System. Included is information about the following panel features: 
  Supervision 
  Audio Notification Appliance Output Circuit Supervision 
  Amplifier Supervision 
  Actions that Initiate Alarms   
5.2  User Interface 
The  User  Interface  on  the  SP40S  displays  the  basic  status  of  the  unit  as  well  as  providing  a 
limited  number  of  user controls.  The  User  Interface  includes  a  Microphone  and  the  manual 
activation or recording of the eight messages. There is also a button to silence the audible trouble 
indicator.  Status  indicators  include  POWER  ON,  SYSTEM  TROUBLE,  AC  TROUBLE, 
ALARM ACTIVE, and STROBE ACTIVE (see Figure 3-3). 
5.3  Supervision 
A  SYSTEM  TROUBLE  LED  indicates  that  the  supervisory  functions  have  detected  a 
malfunction  in  the  panel.  When  a  trouble  condition  is  detected,  the  panel  may  not  be  able  to 
receive and/or broadcast messages from the control panel. 
If a trouble condition is detected by any of the supervisory functions,  the internal sounder 
operates the panel Form C TROUBLE relay (normally energized), changes state, and the yellow 
SYSTEM  TROUBLE LED turns “ON.” The  Trouble Status Relay (TB2) must be properly 
connected to and used by the control panel to indicate a system trouble. At the same time, one of 
the  yellow  trouble  location  LEDs  identifies  the  location  of  the  trouble  condition.  The  internal 
sounder can be silenced for 20 hours by depressing the “Trouble Acknowledge” Switch (SW1, on 
the  User  Interface).  Any  subsequent  troubles  cause  the  sounder  to  be  re-activated.  If  a  trouble 
condition is indicated, follow the procedures in Chapter 8 "Troubleshooting.” 
An AC Loss can be selected to be reported as a system trouble after 170 minutes (SW2-Position 2 
= ON). This is desirable for off-premise trouble reporting. If SW2-Position 2 is OFF, AC Loss is 
reported as a system trouble after 30 seconds. 