Technical data
Chapter 8: Troubleshooting  
SP40S Multi-Function Facility Communication System Manual, Revision L 
12 
8.2.19 Procedure S 
If the green PWR LED is "ON," the yellow SYSTEM TROUBLE LED is "ON," and one of the 
IN#  LEDs  (D55,  D58,  D62,  D65,  D75,  D78,  D84,  or  D87)    are  "ON,"  a  DV  Contact  Closure 
Wiring Trouble exists. 
Perform the following: 
1.  If a particular Contact Closure is not being used, make sure nothing is on the 
corresponding  terminal  block  (TB7  or  TB8)  and  the  corresponding  IN  CC 
Supervision is turned OFF at switch SW7. 
2.  If a particular Contact Closure is being used, make sure that a UL approved 10k Ohm 
½ W EOLR is installed on the proper terminals. 
8.2.20 Procedure T 
If the unit is in normal standby mode yet excessive noise is being heard from the speakers, the 
unit may not be properly grounded to the enclosure. 
Perform the following: 
1.  Verify that the 4 metal standoffs are installed and securely fastened.  Refer to figure 
3-9 for location of the grounding standoffs. 
2.  Verify that the 4 screws are installed and securely fastened.  Refer to figure 3-9 for 
location of the grounding screws. 