Installation Instructions

Instruction Sheet W10367612 Rev A 12/10 - 1 -
Installation Instructions
for 49572A L.P. (Propane and Butane)
Gas Conversion Kit
Converting 22,000 BTU/hr Gas Burners from Natural Gas to Liquefied
Petroleum (Bottled Gas)
Parts included in Kit:
1 Instruction Sheet
1 Blocking Pin
1 Orifice, Burner-Butane No. 55
1 Orifice, Burner-Propane No. 54
1 Label, Rating Plate Conversion (English)
1 Label, Rating Plate Conversion (French)
1 Label, Conversion Record (English)
1 Label, Conversion Record (French)
1 Label, Burner Baseplate (English/French )
NOTE: This instruction sheet contains information for converting two different design gas valves. Read
instructions thoroughly and follow steps.
Warning: This conversion kit shall be installed by a qualified
service agency in accordance with the manufacturer’s
instructions and all applicable codes and requirements of the
authority having jurisdiction. The information in these
instructions must be followed to minimize the risk of fire or
explosion or to prevent property damage, personal injury, or
death. The qualified service agency is responsible for the
proper installation of this kit. The installation is not proper and
complete until the operation of the converted appliance is
checked as specified in the manufacturer’s instructions
supplied with this kit.
NOTE: A qualified service technician is any person or
representative of a company who is experienced or trained in
servicing gas equipment and is familiar with necessary
precautions.
Canada Only
THIS CONVERSION KIT SHALL BE CARRIED OUT IN
ACCORDANCE WITH THE REQUIREMENTS OF THE
PROVINCIAL AUTHORITIES HAVING JURISDICTION AND
IN ACCORDANCE WITH THE REQUIREMENTS OF THE
CAN-B49.1 AND CAN1-B149.2 INSTALLATION CODE.
NOTE: Read these instructions before proceeding.
IMPORTANT: The LP Conversion Kit you received is an
approved kit for converting your gas dryer from natural to LP
propane or butane gas. The kit no. shown on the Burner Data
Label located on the Burner Base may not match the kit you
receive due to kit consolidation.
Do not use on burner assembly no. 693037.
This dryer has been manufactured for use with Natural (city)
gas. Installation of this conversion kit converts the dryer for use
with L.P. gas with manifold pressure of 10” water column and
supply pressure between 8” and 13” water column. If this dryer
is converted for use with L.P. gas by means of this kit, the input
rating will be 22,000 BTU’s per hour, for altitudes up to 10,000
feet. For installations above 10,000 feet, contact a qualified
service agency
GAINING ACCESS TO BURNER ASSEMBLY
1. Unplug dryer or disconnect power.
2. Turn off gas supply using the shut-off valve that supplies
the dryer.
3. Fill out information on conversion decal and apply in a
conspicuous location adjacent to model and serial tag
located in the door well.
4. Remove toe panel. On some models, a small flat-head
screwdriver is required to release the clips at the top of the
toe panel. Then proceed to step 10. If dryer has full front
panel proceed to step 5.
5. Remove the lint screen. Remove the two (2) screws from
the lint screen area.
6. Raise dryer top by pulling forward on the back corners and
up on front corners (top is hinged at rear). Lean dryer top
toward the wall, taking precautions not to damage the
dryer top or wall. Position top so it cannot fall.