Specifications

10
113312-2-BA (1093)
Kohler Co., Kohler WI
8. FIELD WIRE ELECTRONICS
A. IDENTIFY ELECTRICAL REQUIREMENTS
The model number is printed on a plate at the pump end
of the module.
The model number identifies electrical rating. Electrical
connections for each model vary.
S K-1457-AA: 60 Hz
(Follow Step B. below.)
S K-1457-J1-AA: 60 Hz
(Follow Steps C. and D. below.)
S K-1457-JA-AA: 50 Hz
(Follow Steps E. and F. below.)
See Electrical Requirements section on page 6 of
Product Requirements.
B. WIRING INFORMATION - 120V, 60 HZ
(EXCLUDING -J1 MODELS)
WARNING: Risk of electrical shock. To reduce
the risk of electric shock, connect only to a properly
grounded, grounding-type receptacle, protected
by a Ground-Fault Circuit-Interrupter (GFCI). Do
not remove the plug’s grounding pin. Do not use a
grounding adapter.
Your Kohler Whirlpool bath is equipped with a cord and
plug. All wiring of the pump and control has been
completed at the factory. A licensed electrician must
install a GFCI protected, 120 Volt, 15 Amp, grounded
outlet. Your whirlpool may then be plugged into this
outlet. No other load should be on this circuit.
C. LOCATE FIELD WIRING COMPARTMENT -
120V, 60 HZ (-J1 MODELS ONLY)
WARNING: Risk of electrical shock. Make sure
the power has been disconnected before
performing the following procedures. Refer to
Important Safety Instructions located on page 2.
CAUTION: Risk of electrical shock. All services
must have a Class A Ground-Fault
Circuit-Interrupter (GFCI) which will provide
additional protection against line-to-ground shock
hazard.
A licensed electrician should make a routine service
connection to the field wiring compartment of the pump
containing black and white wires and ground screw.
NOTE: Electrician must supply a listed strain/relief
bushing in accordance with local codes.
* For bonding in accordance with National and Local
Codes.
Air
Actuator
Air
Actuator
Tubing
Field Wiring
Compartment
Bonding
(Earthing)
Screw*
Pump