Specifications

8
Normal Operating Pressures (-42 to -60)
Make Electrical Connections
IMPORTANT:
Electrical wiring, disconnect means and over-current
protection are to be supplied by the installer. Refer to the
rating plate for the maximum over-current protection,
minimum circuit ampacity, and operating voltage. See wiring
diagrams later in this section.
Install an adequately sized branch circuit disconnect,
according to the NEC, within sight of and readily accessible
from heat pump.
The cable or conduit and fittings connected from the
disconnect to the heat pump shall be rated for outdoor use.
W2GH342A W2GH348A W2GH360A
Air Temperature Entering
Outdoor Coil ºF (ºC) Liquid Suction Liquid Suction Liquid Suction
Cooling
65 (18) 139 67 147 78 146 67
75 (23.9) 163 74 173 79 170 74
85 (29.4) 191 81 203 80 199 81
95 (35) 220 84 236 81 230 84
105 (40.6) 256 85 273 83 266 85
115 (46.1) 294 87 315 84 306 87
Heating
50 (10) 204 59 212 59 214 60
40 (4.4) 195 49 195 40 202 50
30 (1.1) 184 39 189 39 191 40
20 (-6.7) 178 32 179 31 181 33
NOTE: Values provided are typical pressures. Indoor unit match-up, indoor air quality and indoor load will cause pressures to vary.
WARNING
Rating Plate Ampacity
Less than 15
16 - 20
21 - 30
AWG
14
12
10
8
31 - 50
Electrical Shock Hazard
Electrically ground condensing unit or heat pump.
Connect ground wire to ground lug.
Use copper wire for supply connection.
Correct wire gauge is shown in the chart below.
Failure to follow these instructions can result in
death or electrical shock.