Instruction manual

17
WAHMV42 Continuous
Blower
X 700 600 500 400
Cooling ** X X 1,400 1,200 1,000 800
Heating X 1,400 1,200 1,000 800
Auxillary
Heat
X X *** *** *** *** 1,400 1,400 1,000 1,000
Emergency
Heat
X X *** *** *** *** 1,400 1,400 1,000 1,000
WAHMV48 Continuous
Blower
X 800 700 600 500
Cooling ** X X 1,600 1,400 1,200 1,000
Heating X 1,600 1,400 1,200 1,000
Auxillary
Heat
X X *** *** *** *** 1,600 1,600 1,200 1,200
Emergency
Heat
X X *** *** *** *** 1,600 1,600 1,200 1,200
WAHMV60 Continuous
Blower
X 900 800 700 600
Cooling ** X X 1,800 1,600 1,400 1,200
Heating X 1,800 1,600 1,400 1,200
Auxillary
Heat
X X *** *** *** *** 1,800 1,600 1,400 1,200
Emergency
Heat
X X *** *** *** *** 1,800 1,600 1,400 1,200
**Humidistat will reduce cooling airflow by 10% in high humidity.
***Airflow is greater of Cool and Heat when both electric heat and heat pump are
operating.
NOTES:
Adjust the Control Board Tap (+) will increase airflow by 10%, while the Control Board
Tap (-) will decrease airflow by 12%.
Adjust the Control Board Tap (-) test will cause the motor to run at 70% of full airflow.
Use this for troubleshooting only.
At the start of a call for cooling, there is a short run at 82% of airflow for 7.5 minutes.
At the end of a call for cooling, there is a blower delay of 1 minute.
Application Table—Variable Speed Motor Control Board Taps
Energized Thermostat
Ter m in al
Cool Heat
Model Mode HUM EM W1 O Y2/Y1 G A B C D A B C D
CFMCFMCFMCFMCFMCFMCFMCFM