Tech Sheet

FOR SERVICE TECHNICIAN’S USE ONLY
2
IMPORTANT: The following operations are allowed only during the  rst 5 minutes after the power cycle.
SELECTION DOT
Step
No.
Keypad Pressed Setting Control
Display
Diagnostics Mode Operation Descriptions
1 Press the timer “+” and “-” keys (see
image below) in the following sequence:
- > + > - > + > OK\Key Lock
1st “CO” Con guration mode
2 Press the timer “+” and “-” keys to scroll
the different modes and press
“OK/Key Lock” to con rm.
2nd “FS” Failure Show
3rd “DE” Delete Failure
3 Once any one of the modes “CO”, “FS” or “DE” is selected, it is possible to operate them or to exit them, and return to the
Idle screen, by pressing any one of the ON/OFF buttons. The system also automatically returns to the Idle screen if no button
is pressed for 60 seconds.
To Complete con guration procedure:
SW Con guration:
1. Enter in Con guration mode (CO), the digits of the top left and top right zones display “0” and “0”.
2. The number displayed on the top left and top right zones represents the number of the con guration: the left digit represents the
tenths, the right digit represents the units. E.g. “3”,”5”, is con guration number 35.
3. The numbers of the tenths and of the units are selected separately. The number selected is indicated by the SELECTION DOT. The
digit with the selection dot ON is the digit selected. One only digit at a time can be selected.
4. When one of digit of the tenths or the units is selected, its value can be selected from 0 to 9 by using the “+” and “-” button of the
timer.
5. In order to change the digit selected, press any one of the “-” or “+” buttons of the top left or top right zone. By pressing “+” or “-”
of the top left zone the tenths digit will be selected; by pressing “+” or “-” of the top right zone the units digit will be selected.
6. Once the proper con guration number has been selected and visually by the timer digits, press “KEY LOCK” to con rm.
7. After that, the HMI starts the con guration of itself and the IPCs of the system (2 or 3 IPCs depending on the system
con guration).
8. If the system con guration is completed:
Successfully (i.e all boards correctly con gured) then the HMI resets;
Not successfully (i.e one or more boards not correctly con gured) then the HMI generates the ERROR feedback.
In case of error, turn off the system for at least 30 seconds and then repeat the procedure
.
COMMERCIAL CODE SW Con guration
WCI55US4JB 53
UCIG245KBL 53
WCI55US0JB 54
WCI55US0JS 54
JIC4324KB 55