Instruction manual

41
Induced draft
blower runs
continuously
with no further
furnace
operation.
Integrated
control module
diagnostic LED
is flashing
3flashes.
3 flashes
Pressure switch
circuit is not
closed.
Induced draft
blower is
operating.
Pressure switch hose
blocked, pinched or
connected improperly.
Blocked flue and/or inlet
air pipe, blocked drain
system or weak induced
draft blower.
Incorrect pressure
switch setpoint or
malfunctioning switch
contacts.
Loose or improperly
connected wiring.
Inspect pressure
switch hose. Repair/
replace, if necessary,
Inspect flue and/or
inlet air piping for
blockage, proper
length, elbows and
termination.
Check drain system.
Correct as necessary.
Correct pressure
switch setpoint or
contact motion.
Tighten or correct
wiring connection.
Turn off power
prior to repair.
Replace pressure
switch with
correct
replacement part.
Replace induced
draft blower with
correct
replacement part.
Circulator
blower runs
continuously.
No furnace
operation.
Integrated
control module
diagnostic LED
is flashing
4flashes.
4 flashes
Primary limit or
auxiliary limit
circuit is open.
Insufficient conditioned
air over the heat
exchanger. Blocked
filters, restrictive
ductwork, improper
circulator blower speed,
or failed circulator
blower.
Faulty primary limit
switch.
Loose or improperly
connected wiring.
Check primary limit
switch. Replace if
necessary.
Check filters and
ductwork for blockage.
Clean filters or remove
obstruction.
Check circulator
blower speed and
performance. Correct
speed or replace
blower if necessary.
Tighten or correct
wiring connection.
Turn off power
prior to repair.
Replace primary
switch with
correct
replacement part.
Replace
circulator blower
with correct
replacement part.
Induced draft
blower and
circulator
blower runs
continuously.
No furnace
operation.
Integrated
control module
diagnostic LED
is flashing
5flashes.
5 flashes
Flame sensed
with no call for
heat.
Short to ground in flame
sense circuit.
Correct short at flame
sensor or in flame
sensor wiring.
Turn off power
prior to repair.
No furnace
operation.
Integrated
control module
diagnostic LED
is flashing
6flashes.
6 flashes
Rollout limit
switch open.
Integrated
control module
fuse is blown.
Flame rollout.
Misaligned burners,
blocked flue and/or air
inlet pipe or failed
induced draft blower.
Loose or improperly
connected wiring.
Short in 24-volt AC
control circuits or safety
circuits.
Faulty rollout limit
switch.
Check burners for
proper alignment.
Check flue and air inlet
piping for blockage,
proper length, elbows
and termination.
Correct as necessary.
Check rollout limit
switch. Replace if
necessary.
Check induced draft
blower for proper
performance. Replace
if necessary.
Tighten or correct
wiring connection.
Repair short in 24-volt
AC control/safety
circuit(s).
Replace integrated
control module fuse
(3A).
Turn off power
prior to repair.
Replace induced
draft blower with
correct
replacement part.
Replace
integrated control
module fuse with
3A automotive
fuse.
Read precautions
in “Electrostatic
Discharge”
section of
manual.
Replace rollout
limit switch with
correct
replacement part.
See “Vent/Fluie
Pipe” section for
piping details.
Symptoms of
Abnormal
Operation
Associated
LED Code Fault Description Possible Causes Corrective Actions
Notes and
Cautions