Instruction manual

13
Alternate Furnace Connections
If the standard locations are undesirable for a specific installation,
alternate side panel locations are available for both combustion
air inlet and vent/flue pipe connections. These locations may be
of particular benefit to upright upflow installations requiring
additional access to an A coil, or to upright counterflow
installations requiring additional access to a filter or electronic air
cleaner, or to horizontal installations desiring vent/flue (and
combustion air intake) piping run vertically from the side of the
cabinet.
NOTE: Standard and alternate locations can be combined (for
example, an installation may use the standard combustion air
intake location but use the alternate vent/flue location or vice
versa), if needed.
Alternate Vent/Flue Location
The alternate vent/flue location is the large hole directly in line
with the induced draft blower outlet. To use the alternate vent/flue
location, refer to the following steps and the “Alternate Vent/Flue
Location” illustration.
NOTE: Counterflow instructions follow the upflow instructions.
Upflow Units
1. Remove and save the 4 screws securing the vent/flue
coupling to the furnace top panel.
Counterflow Units
Remove and save the 4 screws securing the vent/flue
coupling to the furnace base pan. Also remove the 3 screws
securing the furnace’s internal vent/flue piping to the blower
deck.
Upflow and Counterflow Units
2. Loosen the worm gear hose clamps on the rubber elbow and
detach the rubber elbow from both the induced draft blower
and the vent/flue pipe.
3. Remove the vent/flue pipe from the furnace.
Upflow Units
4. Cut the vent/flue pipe 3³⁄₄" (9.5 cm) from the flanged end of
the pipe. See “Vent/Flue Pipe Cuts” illustration.
NOTE: The section of pipe attached to the coupling will reach
through the side panel to the induced draft blower.
5. Discard remaining pipe and elbows.
Counterflow Units
Cut the vent/flue pipe 3³⁄₄" (9.5 cm) from the blower deck
coupling. See “Vent/Flue Pipe Cuts” illustration
Save vent/flue pipe attached to the blower deck coupling for
use in the alternate location.
Discard remaining pipe and elbows.
Vent/Flue Pipe Cuts
Upflow Units
6. Remove the plastic plug from the alternate vent/flue location.
7. Relocate and install the plastic plug in the standard vent/flue
location (top cover).
Counterflow Units
Remove the plastic plug from the alternate vent/flue location.
Relocate and install the plastic plug in the standard vent/flue
location (base pan).
Plug remaining hole in the blower deck with the plastic plug
included in the drain kit bag.
Upflow and Counterflow Units
8. Insert the cut section of the vent/flue pipe and coupling into
the alternate vent/flue location.
9. Attach the vent/flue pipe and coupling to the induced draft
blower using a rubber coupling and worm gear hose clamps
provided in the drain kit bag.
10. Secure the coupling to the cabinet using the screws removed
in Step 1 or with field-supplied ³⁄₈" #8 self-drilling screws.
11. For upright installations, externally mount the rubber elbow to
the vent/flue coupling using a worm gear hose clamp.
12. Secure the field-supplied vent/flue piping to the rubber elbow
using a worm gear hose clamp.
NOTE: Use of the alternate vent/flue location for upright
installations, requires the drain trap to be installed on the
same side of the furnace as the flue pipe.
13. For horizontal installations, externally secure the field
supplied vent/flue pipe directly to the vent/flue coupling using
a PVC or ABS coupling or elbow.
Edges of sheet metal holes may be sharp. Use gloves as
a precaution when removing hole plugs.
WARNING
A. Flange
B. Cut location
C. 3
³⁄₄
" (9.5 cm)
A
B
C
Placeholder
The rubber elbow is not designed to support a load.
When the rubber elbow is mounted externally to the
furnace cabinet, extreme care must be taken to adequately
support field-supplied vent/flue piping, as damage can
result in leaks causing bodily injury or death due to
exposure to flue gases, including carbon monoxide.
WARNING