Specifications

11
Evaporator fan will not start. Blown fuse. Inspect fuse size and type. Replace, if needed.
Loose connection. Inspect connection. Tighten if needed.
Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
Open fan overload. Test continuity of overloads.
Faulty thermostat. Test continuity of thermostat and wiring. Replace, if needed.
Shorted or open capacitor. Test capacitor.
Faulty fan relay. Test continuity of coil and contacts.
Open control circuit. Test control circuit with voltmeter.
Faulty evaporator fan motor. Repair or replace.
Condenser fan will not start. Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
Open fan overload. Test continuity of overloads.
Shorted or open capacitor. Test capacitor.
Faulty compressor contactor. Test continuity of coil and contacts. Replace, if needed.
Shorted or grounded fan motor. Test motor windings.
Faulty defrost control. Test control.
Compressor runs—goes off on
overload.
Loose connection. Inspect connection. Tighten if needed.
Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
Shorted or open capacitor. Test capacitor.
Shorted or grounded compressor. Test motor windings.
Compressor stuck. Use test cord.
Faulty compressor contactor. Test continuity of coil and contacts. Replace, if needed.
Low voltage. Test voltage.
Overcharge of refrigerant. Recover part of charge.
Dirty outdoor coil. Inspect coil and clean, if needed.
Improperly located thermostat. Relocate thermostat.
Wrong type of expansion valve. Replace valve.
Expansion valve restricted. Remove restriction or replace valve.
Undersized expansion valve. Replace valve.
Inoperative expansion valve. Check valve operation. Replace if needed.
Faulty reversing valve. Replace valve or solenoid.
Compressor cycles on overload. Shorted or open capacitor. Test capacitor.
Compressor stuck. Use test cord.
Low voltage. Test voltage.
Improper cooling anticipator. Check resistance of anticipator.
Shortage of refrigerant. Test for leaks. Add refrigerant.
Restricted liquid line. Replace restricted part.
Overcharge of refrigerant. Recover part of charge.
Dirty outdoor coil. Inspect coil and clean, if needed.
Noncondensibles. Recover charge. Evacuate and recharge.
Recirculation of condensing air. Remove obstruction to airflow.
Wrong type of expansion valve. Replace valve.
Expansion valve restricted. Remove restriction or replace valve.
Undersized expansion valve. Replace valve.
Problem
No Cooling/Heating Cause/Test Method and/or Solution