Specifications

13
Unsatisfactory Cooling/Heating
Compressor is noisy. Overcharge of refrigerant. Recover part of charge.
Broken internal parts. Replace compressor.
Broken valves. Test compressor efficiency. Replace if needed.
Expansion valve bulb loose. Tighten bulb bracket.
Loose hold-down bolts. Tighten bolts.
Heating Only—System runs—blows
cold air in heating.
Internal compressor overload open. Test continuity of overload.
Compressor stuck. Use test cord.
Shortage of refrigerant. Test for leaks. Add refrigerant.
Open element or limit on electric heater (heating only). Test heater element and
controls.
Overcharge of refrigerant. Recover part of charge.
Noncondensibles. Recover charge. Evacuate and recharge.
Broken internal parts. Replace compressor.
Inefficient compressor. Test compressor efficiency.
Faulty reversing valve. Replace valve or solenoid.
Faulty defrost control. Test control.
Faulty defrost thermostat. Test defrost thermostat.
Heating Only—Unit will not
terminate defrost.
Faulty reversing valve. Replace valve or solenoid.
Faulty defrost control. Test control.
Faulty defrost thermostat. Test defrost thermostat.
Heating Only—Unit will not defrost. Faulty reversing valve. Replace valve or solenoid.
Faulty defrost control. Test control.
Faulty defrost thermostat. Test defrost thermostat.
System Operating Pressures
Low suction pressure. Faulty evaporator fan motor. Repair or replace.
Shortage of refrigerant. Test for leaks. Add refrigerant.
Restricted liquid line. Replace restricted part.
Dirty air filter. Inspect filter; clean or replace as needed.
Dirty indoor coil. Inspect coil and clean, if needed.
Not enough air across indoor coil. Check blower speed. Check duct static pressure and
filter.
Dirty outdoor coil (heating only). Inspect coil and clean, if needed.
Wrong type of expansion valve. Replace valve.
Expansion valve restricted. Remove restriction or replace valve.
Undersized expansion valve. Replace valve.
Inoperative expansion valve. Check valve operation. Replace if needed.
Faulty defrost control (heating only). Test control.
Faulty defrost thermostat (heating only). Test defrost thermostat.
Low head pressure. Shortage of refrigerant. Test for leaks. Add refrigerant.
Restricted liquid line. Replace restricted part.
Too much air across indoor coil (heating only). Reduce blower speed.
Broken valves. Test compressor efficiency. Replace if needed.
Inefficient compressor. Test compressor efficiency.
Wrong type of expansion valve. Replace valve.
Expansion valve restricted. Remove restriction or replace valve.
Faulty reversing valve (heating only). Replace valve or solenoid.
Faulty defrost control (heating only). Test control.
Faulty defrost thermostat (heating only). Test defrost thermostat.
Flowrator not seating properly. Check flowrator and seat, or replace flowrator.
Problem
No Cooling/Heating Cause/Test Method and/or Solution