Use and Care Manual

3
INSTALLATION REQUIREMENTS
Electrical Requirements—All Models
The electrical ratings for air conditioner are listed on the model
and serial number label. The model and serial number label is
located on the right-hand side of the air conditioner cabinet.
Specic electrical requirements are listed in the "Electrical
Requirements" sections. Follow the requirements for the type of
plug shown in these sections.
Model BTUs—Cooling Only 115 V 8000,
10000, 12000
All models
115 V − (103.5 min. - 126.5 max.)
If there is a "Single Circuit Only" label on the unit, use on a
dedicated single-outlet circuit only.
If a dedicated single-outlet circuit is not available, then it is
the customer’s responsibility to have a single-outlet circuit
installed by a qualied electrician.
If there is no "Single Circuit Only" label on the unit, the unit
may be used on any branch circuit of correct voltage and
adequate current protection rating.
8,000 BTU 115 V Cooling Only models
0-8 A
10 A time-delay fuse or circuit breaker
10,000-12,000 BTU 115 V Cooling Only models
0-12 A
15 A time-delay fuse or circuit breaker
Model BTUs—
Cooling and Heating 115 V 8000;
230V 10000, 12000, 14000
Cooling Only 230V 10000, 12000, 14000
10,000-14,000 BTU 230 V Cooling Only models
230 V (208 min. - 240 max.)
0-8 A
10 A time-delay fuse or circuit breaker
8,000 BTU 115 V and 10,000-14,000 BTU 230 V Cooling &
Heating models
4-15 A
20 A time-delay fuse or circuit breaker
If there is a "Single Circuit Only" label on the unit, use on a
dedicated single-outlet circuit only.
If a dedicated single-outlet circuit is not available, then it is
the customer’s responsibility to have a single-outlet circuit
installed by a qualied electrician.
If there is no "Single Circuit Only" label on the unit, the unit
may be used on any branch circuit of correct voltage and
adequate current protection rating.
Recommended Grounding Method
This air conditioner must be grounded. This air conditioner is
equipped with a power supply cord having a grounded 3 prong
plug. To minimize possible shock hazard, the cord must be
plugged into a mating, grounded 3 prong outlet and grounded
in accordance with all local codes and ordinances. If a mating
outlet is not available, it is the customer’s responsibility to have a
properly grounded 3 prong outlet installed by a qualied electrical
installer. It is the customer’s responsibility:
To contact a qualied electrical installer.
To assure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70—
latest edition, and all local codes and ordinances.
Copies of the standards listed may be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269