Too cool/warm and then too warm/
cool.
Faulty thermostat. Test continuity of thermostat and wiring. Replace, if needed.
Improper cooling anticipator. Check resistance of anticipator.
Improperly located thermostat. Relocate thermostat.
Airflow unbalanced. Readjust air volume dampers.
Not cool enough on warm days. Dirty air filter. Inspect filter; clean or replace as needed.
Dirty indoor coil. Inspect coil and clean, if needed.
Not enough air across indoor coil. Check blower speed. Check duct static pressure and
filter.
Noncondensibles. Recover charge. Evacuate and recharge.
Recirculation of condensing air. Remove obstruction to airflow.
Infiltration of outdoor air. Check windows, doors, vent fans, etc.
System undersized. Refigure cooling load.
Wrong type of expansion valve. Replace valve.
Expansion valve restricted. Remove restriction or replace valve.
Undersized expansion valve. Replace valve.
Certain areas too cool, others too
warm.
Dirty air filter. Inspect filter; clean or replace as needed.
Dirty indoor coil. Inspect coil and clean, if needed.
Not enough air across indoor coil. Check blower speed. Check duct static pressure and
filter.
Infiltration of outdoor air. Check windows, doors, vent fans, etc.
Airflow unbalanced. Readjust air volume dampers.
Compressor is noisy. Overcharge of refrigerant. Recover part of charge.
Broken internal parts. Replace compressor.
Broken valves. Test compressor efficiency. Replace if needed.
Expansion valve bulb loose. Tighten bulb bracket.
Loose hold-down bolts. Tighten bolts.
Heating Only—System runs—blows
cold air in heating.
Internal compressor overload open. Test continuity of overload.
Compressor stuck. Use test cord.
Shortage of refrigerant. Test for leaks. Add refrigerant.
Open element or limit on electric heater (heating only). Test heater element and
controls.
Overcharge of refrigerant. Recover part of charge.
Noncondensibles. Recover charge. Evacuate and recharge.
Broken internal parts. Replace compressor.
Inefficient compressor. Test compressor efficiency.
Faulty reversing valve. Replace valve or solenoid.
Faulty defrost control. Test control.
Faulty defrost thermostat. Test defrost thermostat.
Heating Only—Unit will not
terminate defrost.
Faulty reversing valve. Replace valve or solenoid.
Faulty defrost control. Test control.
Faulty defrost thermostat. Test defrost thermostat.
Heating Only—Unit will not defrost. Faulty reversing valve. Replace valve or solenoid.
Faulty defrost control. Test control.
Faulty defrost thermostat. Test defrost thermostat.
Problem
No Cooling/Heating Cause/Test Method and/or Solution