Installation manual

17
Low head—high
suction
Incorrect flowrator
Defective compressor valves
Flowrator not seating properly
Replace with correct flowrator.
Replace compressor.
Check for debris under flowrator or deformed flowrator. Remove
debris or replace flowrator.
Unit will not run.
Power off or loose electrical
connection
Thermostat out of calibration; set
too high
Defective contactor
Blown fuses or tripped circuit
breaker
Transformer defective
High or low pressure control
(optional) open
Compressor overload contacts open
Check for unit voltage at contactor in unit.
Reset thermostat.
Check for 24 volts at contactor coil. Replace if contacts are
open.
Replace fuse or reset circuit breaker. Check wiring. Replace
transformer.
Reset high pressure control or check unit charge.
High pressure control opens at 610 psig, and low pressure
control opens at 22 psig.
Replace compressor.
NOTE: Wait at least 2 hours for overload to reset.
Condenser fan runs;
compressor does not
run.
Loose connection
Compressor stuck
Grounded or open winding
Open internal overload
Low voltage connection
Capacitor weak, open or shorted
Check for unit voltage at compressor.
Check and tighten all connections.
Wait at least 2 hours for overload to reset. If still open, replace
the compressor.
At compressor terminals, voltage must be within 10% of
nameplate volts when unit is operating.
Check capacitor. Replace if defective.
Low suction—cool
compressor, iced
evaporator coil
Low indoor airflow Increase speed of blower or reduce restriction.
Replace air filters.
Compressor short
cycles
Defective overload protector
Unit cycling on low pressure control
High pressure switch cuts out
Replace overload protector. Check for correct voltage.
Check refrigerant charge and/or airflow.
Check airflow (indoor and outdoor).
Registers sweat
Low airflow Increase speed of blower or reduce restriction.
Replace air filters.
High suction pressure Excessive load
Defective compressor
Reversing valve not seating
properly.
Recheck load calculation
Replace compressor.
Replace reversing valve.
Insufficient cooling
Improperly sized unit
Improper airflow
Incorrect refrigerant charge.
Incorrect voltage
Recalculate load.
Check airflow—should be approximately 400 CFM per ton.
Charge per procedure attached to unit service panel.
At compressor terminals, voltage must be within 10% of
nameplate volts when unit is operating.
Evaporator coil freezing
or frosting
Low airflow
Low refrigerant charge
Operating unit in cooling mode
below 65ºF (18ºC) outdoor
temperature
Check airflow—should be approximately 400 CFM per ton.
Check for dirty air filters and that all duct outlets are open.
Properly charge unit.
Install or check low ambient control—should be open below 65ºF
(18ºC) outdoor temperature.
Symptom Possible Cause Remedy